Sunteți pe pagina 1din 6

ANALYSIS AND MITIGATION OF SUB-SYNCHRONOUS

RESONANCE OSCILLATIONS IN POWER SYSTEMS

D.Sree Chandana Bhargavi,


Department of Electrical Engineering,
A.U.College of Engineering (A),Visakhapatnam.

ABSTRACT: Series capacitive compensation is the most economical way to enhance


transmission capacity and to improve transient stability of transmission grids. How ever
their presence in the system may lead to the sub synchronous resonance (SSR)
phenomenon in the generating plants that are directly connected to the series capacitor
compensated transmission line. Investigation of sub synchronous resonance problems has
resulted in proposed and applied methods to mitigate or eliminate SSR damage to turbine
– generator sets. In this paper SSR phenomenon is studied and the analysis of SSR is
carried out and also describes the devices used, their theory of operation, strengths and
weaknesses for mitigating SSR problems.
KEYWORDS: Series compensated transmission line, Subsynchronous resonance (SSR) ,
Filtering and Damping , Generator protection

1. INTRODUCTION Damping of SSR currents, Relaying and


Protective Devices, System switching and
Generator tripping , Generator and System
The analysis of sub synchronous resonance modifications. The source of most SSR
is a complex technical problem observed in problems is the presence of series
series capacitor compensated power capacitors in the transmission system.
transmission and distribution systems. Therefore control of series capacitors may
When such an analysis is done , it reveals be used to mitigate the adverse SSR effects.
either an unstable system or an acceptable
risk of equipment damage during system
disturbances. Measures to resolve such
problems must be implemented. These 2. ANALYSIS OF SUB
measures include modifications to the SYNCHRONOUS RESONANCE
transmission system or restricted system
Sub synchronous resonance is an electric
operation or addition of equipments
power system condition where the electric
designed to meet the problems. Economic
network exchanges energy with a turbine -
analysis of all alternatives for either
generator at one or more of the natural
avoiding or solving the SSR problem is an
frequencies of the combined system below
important study procedure. During the past
the synchronous frequency of the system.
few years much effort has been expended
Sub synchronous resonance causes
in studying SSR problems. This paper
oscillations in the electric and mechanical
presents many of the solutions both tested
parts of the turbine – generator system
and untested for correcting SSR problem.
when coupled to a series capacitor
The discussion is divided into the following
compensated transmission system. The
sections – Analysis of Sub Synchronous
oscillatory energy exchange between the
Resonance, Torsional Interaction and
electric system and the turbine generator
Induction Generator Effect, Filtering and
system is lightly damped, undamped or 𝑓𝑟 = 𝑓𝑒𝑟 − 𝑓𝑜 (2)
even negatively damped. The terms sub
synchronous and super synchronous are The negative sequence currents cause a
used to denote frequencies below and field which rotates in the opposite direction
above the synchronous frequency of the and hence act like a brake on the rotor,
rotor. The electrical system for a simple absorbing energy and helping to damp. It
radial system has a resonant frequency 𝑓𝑒𝑟 usually disappears rapidly after a transient.
given by
𝑓𝑟 = 𝑓𝑒𝑟 + 𝑓𝑜 (3)
𝑋
𝑓𝑒𝑟 = 𝑓𝑜 √𝑋 " +𝑋 𝑐 +𝑋 (1) The induced rotor currents affect the rotor
𝑇 𝑒
magnetic field and also result in sub
synchronous frequency torques on the rotor
Where 𝑋 " is the subtransient reactance of
caused by interaction with steady magnetic
the generator , 𝑋𝑇 is the leakage reactance
field of the rotor. The variations in the rotor
of the transformer. Since in general 𝑋𝑐 <
magnetic field result in changes in the
𝑋𝑒 , 𝑓𝑒𝑟 is less than the synchronous
generator emf even if the rotational speed
frequency 𝑓𝑜
remains constant. The emf generated in the
Generally the series compensated stator has frequencies given by
transmission system is more complex and
𝑓𝑠 = 𝑓𝑟 ± 𝑓𝑜 (4)
will result in many subsynchronous
frequencies. A series capacitor placed in
the transmission line cancels a portion of
inductive reactance of the system and will 3. INDUCTION GENERATOR
always result in a frequency which is less EFFECT & TORSIONAL
than the line frequency and this will be INTERACTION
referred to as a sub harmonic. An
oscillation at the sub harmonic frequency
will tend to be damped by the line and 3.1 Induction Generator Effect :
transformer resistance. However any
rotating machinery on the system will feed
energy into the sub harmonic currents. The induction generator effect is caused by
the self excitation of an electrical system .
A balanced three phase set of armature When certain load dynamics are created in
currents of frequency 𝑓𝑒𝑟 produce a rotating the system, sub harmonic currents are
magnetic field in the air gap which rotates generated due to resonant circuit, these
with same frequency in a direction currents will set up a rotating flux , but at
determined by the sequence currents. The angular rotation of 2𝜋f electrical radians
subharmonic currents in any machine may per second where 𝑓𝑒 is the sub synchronous
be visualized as positive and negative frequency set up due to the resonance . The
sequence components at a frequency 𝑓𝑜 . rotor is rotating at a speed of 2𝜋f electrical
Positive sequence currents produce a field radian per second faster than the sub
which rotates in the same direction as the synchronous field. Since 𝑓𝑒 < 𝑓 the slip is
rotor and the effect of rotation of the negative and the machine is capable of
machine is to act like an induction converting mechanical energy to electrical
generator feeding energy into the positive energy at sub synchronous frequency. The
sequence sub harmonic. resistance of damper windings referred to
the stator is 𝑅2 /𝑠 and this quantity being introduces parallel resonance at rotor
negative contributes to negative damping. frequency. This causes the system
If the frequency of these currents and resonance to shift, such that the machine is
voltages correspond to the natural torsional isolated from the power system at critical
modes of turbine generator , the shaft will sub synchronous frequencies. The SBF
oscillate at a high torque . This effect is filter is tuned to protect a single individual
known as Induction Generator Effect. generating unit. It provides significant
control of torsional interaction and transient
3.2 Torsional Interaction torque effects.

4.2 Line filter


Whenever certain load dynamics appear in
a system , transient currents flow in the
stator winding of synchronous machine due It is an appropriately sized reactor
to resonant circuit ; these transient currents connected in parallel with an existing series
will be of sub synchronous frequency. The capacitor . This filter causes the flow of sub
sub synchronous frequency currents synchronous currents to be blocked. The
interact with the generator rotor and induce filter offers higher net capacitive reactance
sub synchronous torque on the rotor due to and hence allows only lesser current to
which generator rotor oscillations will build flow. The line filter is applicable to systems
up. These oscillations will induce voltage where there is only a single generator is
of subsynchronous frequency which involved. It is ineffective when new lines
sustains the sub synchronous torque . If the are added to the system.
magnitude of this torque exceeds the
inherent mechanical damping of the system 4.3 Bypass Damping Filter
, the system will become self excited. Such
interplay between the electrical and
mechanical system is termed as torsional It is connected in parallel across the series
interaction. capacitor. It acts like a bypass path for the
flow of sub synchronous frequency current
4. FILTERING AND DAMPING in the network. The filter is designed with a
damping resistor in series with a parallel
combination of a reactor and capacitor.
4.1 Static blocking filter This net circuit has a very high impedance
at system frequency. Hence no large power
losses occur in the damping resistor. At
The Static blocking filter is inserted in other frequencies the parallel combination
series with the generator step up has a reduced impedance and becomes an
transformer winding, on the neutral end of effective counter measure to sub
the transformer high voltage winding. The synchronous currents. This bypass damping
SBF is made up of separate LC filters ( filter can be successfully installed in a no.
tank circuits ) connected in series. Each of distribution circuits and potentially solve
section of the filter is a high Q , parallel the torsional and induction generator
resonant circuit tuned to block electric instability problems.
currents at frequencies corresponding to
the torsional mode. In addition the filter
impedance and transmission impedance
4.4 Dynamic filter damping where rotor oscillations are
present.
It is a powerful device placed in series with 4.5 Excitation System damper
the generator to null the sub synchronous
voltage generated by rotor oscillations and
hence prevent self excitation. Rotor In this the output of the excitation system is
oscillations give rise to sub synchronous modulated by taking a reference signal
and super synchronous armature voltages. derived from rotor oscillations. The
The super synchronous voltage will excitation system dampers provide
produce armature current which tend to effective damping of rotor oscillation and
damp the oscillations. The sub synchronous compensate for the filter performance in
voltage will produce armature currents case of deterioration caused due to filter
which tend to enhance the oscillations. detuning. The signals at different torsional
The dynamic filter with the help of suitable frequencies are separated using band pass
control circuitary produces a voltage in filters. The individual signals are phase
phase opposition to the sub synchronous shifted and amplified independently and
voltage generated in the armature by rotor fed into the automatic voltage regulator
motion and hence provides more net system. The self excitation caused by
damping. The filter is not affected by the torsional interaction is effectively reduced
system operating condition and is immune with help of excitation system damper.
to the system changes and the number of
series capacitors in service. The filter is 5. GENERATOR PROTECTION AND
expensive and is designed to provide TRIPPING
damping for large oscillations associated
with transient disturbances. 5.1 Torsional motion relay

4.5 Dynamic Stabilizer


This relay operates to disconnect the
machine from the transmission system in
The dynamic stabilizer is made up of the presence of excessive mechanical
thyristor modulated shunt reactors. By stresses in the turbine generator shaft
suitable firing of the thyristors , control of system. Rotor speed is taken as input to the
sub synchronous oscillations can be relay. This relay is mainly operated for
achieved in response to the measured protection from torsional interaction and
disturbance of the turbine –generator unit. generally is too slow to provide protection
Suitable design of the stabilizer causes the for SSR transients. The relay does not
cancellation of the generator armature provide reliable
currents occurring at sub synchronous
frequencies. An initial oscillation caused This device is used for continuous
due to a transient fault condition is monitoring of the turbine – generator
considered as the starting point for design system. The severity of the shaft torsional
calculation. The dynamic stabilizer does oscillations resulting from electrical
not provide protection against induction disturbances in the transmission network is
generator effect or transient torque assessed. This device senses rotor speed
problems but is useful in providing variations and converts the data by means
of analog circuits into oscillating torques on
each shaft. It has the ability to reduce the
transient electrical disturbance. This device tripping of the unit within this time is an
also allows the units which have tripped off acceptable solution.
line because of an SSR relay operation to
be returned to service much more rapidly. 5.4 Turbine generator modifications

5.2 System switching


A turbine generator has several sub
synchronous torsional natural frequencies.
When a system is prone to SSR damage These frequencies are governed by the
,protection can be provided by isolating the stiffness of the machine shaft and the
generator from the series capacitor. inertias of the main rotors . If it were
Isolation can be achieved by switching the possible to design machines for which the
protected machine onto an uncompensated lowest torsional natural frequency was
system. System switching is most effective greater than the synchronous frequency of
for control of SSR problems. It is relatively the system, the SSR problem would be
inexpensive and easy to implement. eliminated. However it offers only a little
However there are certain limitations solution to the SSR problem as future
associated with system switching. The growth of the network or line outages may
system switching disturbs normal system bring the machine back to resonance.
operations and usually results in less
reliable system configuration following the 5.5 Generator circuit series reactance
switching action. Reliability is less because
problem detection is difficult. Unusual
switching operations arise when Inserting series reactance between a
transmission line openings by circuit generator and the transmission system can
breaker are not directly connected to the provide SSR protection by detuning the
line to be opened. Care is to be taken while resonant network seen by the generators.
restoring the system to normal operation Studies have shown that generator step up
following a switching action. transformer reactance will alleviate some
SSR problems. Advantage of series
5.3 Unit tripping reactance are it is very reliable equipment
with minimal maintenance expense.

This scheme can be applied to provide SSR Addition of series reactance has most
transient torque protection for practical application when only one
predetermined system conditions and fault generator is there. However there are some
locations. This requires that all system disadvantages with the use of series
conditions and fault locations that produce reactance . The system stability margin is
excessive shaft torque to be predetermined reduced. Large series reactors consume
from studies. The knowledge of system reactive power which usually must be
sensing and logic circuitary is required to replaced by the generator or another source.
initiate unit tripping fast enough at Large series reactors are not commonly
accecptable levels. available. Installing reactance in series with
the generator circuit is relatively expensive
A finite time from fault inception is but may be less costly than other
required for shaft torque to grow from a alternatives.
steady state level to fault level . Therefore
6. CONCLUSION

Literature survey done by various


reseachers is reviewed and it has been
concluded that FACTS devices are very
effective in the SSR damping. The analysis
of SSR is divided into 2 main groups a)
induction generator effect b) torsional
interaction. It is necessary to avoid these
effects in a series compensated
transmission line. In this paper some SSR
solutions for the damping of sub
synchronous resonance torques in an
electro mechanical system are presented.
However better study techniques can be
developed to provide safe operation of
generators under SSR conditions.

REFERENCES
[1] IEEE Committee Report ,
“Countermearures to Subsynchronous
Resonance problems”, IEEE Trans
Vol PAS-99 , No.5 ,1980.
.
[2] Kirtan J Desai, Bhargav V Patel,
Chintan R Patel, “Simulation and
Analysis of Sub Synchronous
Resonance in a Series Compensated
Transmission System”, Journal of
Power Electronics & Power Systems,
ISSN : 2321- 4244 , Vol 5, Issue- 3.
[3] Saira B.Sheikh , U.Venkata Reddy ,
“Damping of Sub synchronous
Oscillations Using FACTS
Devices(TCSC , SSSC & UPFC): A
Review .” International Journal of
Electrical , Electronics and Data
Communication , ISSN :2320-2084,
Special Issue, June – 2015.

S-ar putea să vă placă și