Documente Academic
Documente Profesional
Documente Cultură
Service Manual
Contents
Illustrations
Figure Description Page
1 Convective Warming System ............................................... 5
2A/B Power Unit Mounting ........................................................... 5
3 Pole Mounting Height Limit .................................................. 5
4 Operator Control Panel ......................................................... 6
5 TC20 Test Tool .................................................................... 9
6 Temperature Sensor Location ............................................. 10
7 Troubleshooting Chart - NO HEAT ...................................... 19
8 Troubleshooting Chart - NO AIR FLOW ................................ 20
9 Drawing/Parts List .............................................................. 24
10 Drawing/Parts List .............................................................. 25
11 Drawing/Parts List .............................................................. 26
12 TC20 Test Tool Schematic ................................................. 27
13 Wiring Diagram .................................................................. 28
Tables
Table Description Page
1 Air Temperatures .................................................................. 4
2 Functional Check/Inspection Form ....................................... 16
1
Section 1 - Safety Precautions
2
Section 2 - Repair Policy
3
Section 3 - Specifications
3.5 Quilts
M ED 1 0 0 ° F ( 3 8 ° C) All Quilts are made of either a nonwoven layer
bonded to a plastic film, or two nonwoven layers.
CAUTION
5
Section 4 - Theory of Operation (cont’d)
6
Section 5 - Controls and Indicators
Section 6 - Preventive Maintenance
6.5 Hose
Clean the hose with a soft cloth lightly dampened
with a nonstaining hospital disinfectant. Place the
connector hose under the bed rail hooks when not
in use.
7
Section 7 - Functional Check and Safety Inspection
8
Section 7 - Functional Check and Safety Inspection (cont’d)
THERMOSTAT
BYPASS
OVERTEMP
HEAT
9
Section 7 - Functional Check and Safety Inspection (cont’d)
4. Set the two TC20 Test Tool toggle switches Verify that the REMOVE FROM USE light is lit.
as follows:
NOTE: It is acceptable if both thermostats
• THERMOSTAT BYPASS -- place in trip simultaneously, in which case the
center position; S2 and S3 indicators will both be off. If
this occurs, record the elapsed time and
• HEAT/OVERTEMP -- place in HEAT
temperature. Verify that the REMOVE FROM
position.
USE indicator is lit. Verify that both the
5. Locate the air temperature sensor at the S2 and S3 indicators light by toggling the
center of the end of the hose (fig. 6A). THERMOSTAT BYPASS switch from the S2
Secure the sensor with adhesive tape. Verify to S3 position. (If both thermostats have
that the sensor is located at the center of tripped, skip steps 11-14 and proceed to
the hose. step 15.)
6. Connect the hose to a Model TC1050, 11. Switch the TC20 THERMOSTAT BYPASS to
TC2050, TC2052, or TC2054 Quilt (fig. 6B). whichever thermostat (S2 or S3) is lit. This
will short out the thermostat which opened
7. Turn the Power Unit on. Select the first so that the second thermostat can be
HIGH (110°F, 43°C) setting.
tested.
8. Run the Power Unit for 5 to 10 minutes at the Switch the TC20 from OVERTEMP to HEAT
HIGH (110°F, 43°C) setting. The temperature to allow the Power Unit to return to normal
will oscillate. During this time interval,
operating temperature before testing the
familiarize yourself with the following steps 9 second thermostat.
through 14. Have a stopwatch ready.
12. Run the Power Unit again for 5 to 10 minutes
9. Place the HEAT/OVERTEMP switch to
in the HIGH (110°F, 43°C) setting. The
OVERTEMP. The temperature should start to
temperature will oscillate. Have a stopwatch
increase. When the air temperature reaches ready.
119°F (48°C), start the stopwatch.
13. Place the OVERTEMP/HEAT switch to
10. Allow the Power Unit to heat until either the
OVERTEMP. The temperature should start to
S2 or S3 Test Tool thermostat indicator is
increase. When the air temperature reaches
lit. Stop the stopwatch and note the highest 119°F (48°C), start the stopwatch.
temperature displayed. This is the upper
limit temperature for one of the thermostats. 14. Continue to monitor the TC20 Test Tool until
Record the time and temperature on the the second thermostat indicator is lit. Stop the
INSPECTION FORM. stopwatch and note the highest temperature
displayed. This is the upper limit temperature
for the other thermostat. Record the time and
10 temperature on the INSPECTION FORM
Section 7 - Functional Check and Safety Inspection (cont’d)
(table 2, pp. 16-17). Plot these values on table OVERTEMP. Allow the Power Unit to
2, page 18. operate. When the air temperature
reaches 119°F (48°C), start the
Verify that the REMOVE FROM USE light is lit.
stopwatch.
15. Thermostat trip acceptance
d. Allow the Power Unit to heat until the
Both thermostats must trip within the S3 thermostat indicator is lit. Stop
acceptance window (see table 2, p. 18). the stopwatch and note the highest
If this condition is not met, do not put the temperature displayed. This is the
Power Unit in service. Call Gaymar's Technical upper limit temperature for the S3
Service Department for assistance (see inside thermostat. Record the elapsed time
front cover for telephone numbers). and temperature.
16. Unplug the power unit. Open the enclosure to e. Verify that the REMOVE FROM USE
allow the Power Unit to cool for 5-10 minutes. light is lit.
17. Locate the two patient limit thermostats (item f. The S3 thermostat must trip within
18, fig. 11, p. 26). Reset S2 by gently pressing the acceptance window (see table
the center reset button. 2, p. 18). If this condition is not met,
do not put the Power Unit in service.
WARNING Call Gaymar's Technical Service
Department for assistance (see inside
Use care when resetting the
front cover for telephone numbers).
thermostats. Excessive force (force
greater than 5 pounds) can damage g. Unplug the Power Unit.
the overtemp protection device
h. Open the enclosure and allow the
and/or inadvertently alter the trip Power Unit to cool for 5-10 minutes.
temperature of the device.
i. Remove the filter retainer and nut.
Remove the filter. Remove the jumper
NOTE: Use care when resetting the from the S4 thermostat. Press the
thermostats since the power terminals S4 reset button and insure it is reset.
are delicate. Avoid flexing the terminals. Replace the filter, filter retainer, and
Thermostats with loose terminals should be nut.
replaced and retested. j. Reset both the S3 and S2
18. Press the center reset button of S3. Verify it thermostats by pressing their center
has reset (indicated by an audible "click" and reset buttons. (The S2 thermostat
tactile feedback). If it "clicks", proceed to step may have retripped.)
19. 19. Remove the TC20 Test Tool.
If you don't hear a "click", then what was WARNING
assumed to be the patient limit thermostat
S3 tripping was actually the heater overtemp After performing the preceding test
thermostat S4 in the same circuit. This will procedure, verify that the TC20
rarely occur. If it has occurred, proceed as Test Tool and all jumpers have been
follows: removed before returning the Power
Unit to patient use. Failure to do so
a. Remove the filter retainer and nut. may result in death, serious injury,
Remove the filter. Jumper out the S4 or equipment malfunction.
thermostat. Replace the filter, filter
retainer and nut.
b. Run the Power Unit for 5 to 10 minutes 20. Proceed to the FILTER SWITCH TEST
in the HIGH (110°F, 43°C) setting. (section 7.6, p. 14).
c. Bypass S2 by placing the THERMOSTAT
BYPASS switch in the S2 position.
Place the HEAT/OVERTEMP Switch to
11
Section 7 - Functional Check and Safety Inspection (cont’d)
7.5.2 ALTERNATE Test Jumper 26. Unplug the Power Unit. Carefully separate
Procedure (steps 21 to 50) the enclosure slightly.
21. Unplug the Power Unit. 27. Unplug the thermistor (item 13, fig. 10, p.
25) from the back of the control board.
WARNING NOTE: The power resistor on the back side
of the PC board may be hot to touch.
Always unplug the Power Unit
28. Put the enclosure back together and secure
before attaching or removing
it with adhesive (duct) tape.
jumpers and when resetting
thermostats. Failure to unplug 29. Plug in the Power Unit and turn it on. Leave
the Power Unit could result in unit in MED (100°F, 38°C) temperature
electrical shock and cause death setting. Have a stopwatch ready.
or serious injury.
NOTE: Do not set the TEMPERATURE
SETTINGS switch to MIN (fan only) since
22. There are two patient limit thermostats within this setting disables the heater.
the Power Unit and each must be tested. One 30. The temperature should increase. When the
16 gauge insulated stranded wire jumper air temperature reaches 119°F (48°C), start
with alligator clips will be required. To help the stopwatch. The Power Unit will heat until
remember to remove the test jumper, label the S2 thermostat trips. When this happens,
a LARGE, distinctive tag “REMOVE AFTER the blower and heater will shut off. Stop the
TEST” and tie the tag to the jumper. stopwatch and note the highest temperature
Remove the six screws on the back of the displayed. This is the upper limit temperature
unit. Install a jumper across thermostat S3 for thermostat S2. Record the time and
(item 18, fig. 11, p. 26). Temporarily secure temperature on the INSPECTION FORM (table
the two halves of the enclosure together with 2, pp. 16-17).
adhesive (duct) tape. 31. Verify that the REMOVE FROM USE light is lit.
23. Locate the air temperature sensor at the 32. Unplug the Power Unit.
center of the end of the hose (fig. 6A, p. 10).
Secure the sensor with adhesive tape. Verify 33. Open the enclosure and allow the Power Unit
that the sensor is located at the center of to cool for 5-10 minutes.
the hose. 34. Locate the two patient limit thermostats
24. Connect the hose to a Model TC1050, (item 18, fig. 11, p. 26). Gently press the
TC2050, TC2052, or TC2054 Quilt (fig. 6B, reset button in the center of each thermostat.
p. 10). Move the jumper across thermostat S2.
12
Section 7 - Functional Check and Safety Inspection (cont’d)
NOTE: If both thermostats reset, both 43. The temperature should start to increase.
thermostats have tripped. This is When the air temperature reaches 119°F
acceptable. (48°C), start the stopwatch. Allow the Power
Unit to heat until thermostat S3 trips. Stop the
NOTE: Use care when resetting the
stopwatch and note the highest temperature
thermostats since the power terminals
displayed. This is the upper limit temperature
are delicate. Avoid flexing the terminals.
for thermostat S3. Record the time and
Thermostats with loose terminals should
temperature on the INSPECTION FORM (table
be replaced and retested. Be certain the
2, pp. 16-17). Plot these values on table 2, p. 18.
thermostats have cooled for 5-10 minutes
before resetting. 44. Verify that the REMOVE FROM USE light is lit.
NOTE: If thermostat S2 does not reset, 45. Unplug the Power Unit.
the heater overtemp thermostat has
46. Open the enclosure and allow the Power Unit
tripped. In the unlikely event that this has
to cool for 5-10 minutes.
occurred, perform the following:
a) remove the filter retainer and nut; 47. Thermostat trip acceptance
b) remove the filter; Both thermostats must trip within the
c) jumper the S4 heater overtemp acceptance window (see table 2, p. 18).
thermostat; and If this condition is not met, do not put
d) replace the filter, filter retainer, and the Power Unit in service. Call Gaymar's
nut. Return to step 25. Technical Service Department for assistance
(see inside front cover).
35. Reconnect the thermistor to the control
board. 48. Remove the jumper from the patient limit
thermostat.
36. Put the enclosure back together and secure
it with tape. If a jumper was used on the S4 heater
overtemp thermostat, remove the filter
37. Plug in the Power Unit. Turn it on. retainer, nut, and filter. Remove the jumper
38. Run the Power Unit for 5-10 minutes in the from S4. Reset S4 (indicated by an audible
HIGH (110°F, 43°C) setting to stabilize the "click" and tactile feedback). Replace the filter,
system temperature. filter retainer, and nut.
WARNING
NOTE: Perform the following steps 39 through
44 as quickly as possible, to prevent the Power
Unit from cooling down: After performing the preceding test
procedure, verify that all test jumpers
39. Unplug the Power Unit. Carefully separate have been removed before returning
the enclosure slightly. the Power Unit to patient use.
Failure to remove test jumper(s)
40. Unplug the thermistor (item 13, fig. 10, p. may result in death, serious injury,
25) from the back of the control board. or equipment malfunction.
41. Put the enclosure back together and secure
it with tape.
49. Reconnect the thermistor connector to the
42. Plug in the Power Unit and turn it on. Leave back of the control board.
unit in MED (100°F, 38°C) temperature
setting. Have a stopwatch ready.
(continued)
NOTE: Do not set the TEMPERATURE
SETTINGS switch to MIN (fan only) since
this setting disables the heater.
13
Section 7 - Functional Check and Safety Inspection (cont’d)
50. Reset the thermostats by gently pressing the 6. Unplug the Power Unit. Install filter. (Install
center reset buttons. new filter every 1000 operating hours or 12
months, whichever occurs first.) Replace
WARNING the filter only with the Gaymar P/N listed
(see parts list, fig. 9, p. 24). Record the
Use care when resetting the hour timer reading onto the new filter label.
thermostats. Excessive force Reattach filter retainer and nut.
(force greater than 5 pounds) can
damage the overtemp protection CAUTION
device and/or inadvertently alter
the trip temperature of the device. The HEPA filter must be seated
properly. Failure to install the
filter correctly will prevent it from
NOTE: Use care when resetting the functioning properly, and could
thermostats since the power terminals allow unfiltered air to reach the
are delicate. Avoid flexing the terminals. patient and cause injury.
Thermostats with loose terminals should
be replaced and retested.
7. Replace the six screws holding the enclosure
together.
3. Repeat step 2 for MED setting. Average area on the underside of the I. V. pole clamp
temperatures and record. has been provided if needed for this test.
Measure at all combinations of:
Allowable MED temperature:
97°F to 103°F average • line polarity
(36.1°C to 39.4°C) • neutral open/closed
4. Repeat step 2 for HIGH setting. Average 2. The current leakage should not exceed 100
temperatures and record. microamperes in any condition.
Allowable HIGH temperature:
107°F to 113°F average
(41.7°C to 45.0°C)
5. If the temperatures in steps 2 through 4 are 7.10 Completing the Functional Check
not correct, do not put the Power Unit into and Safety Inspection
service. Call Gaymar's Technical Service
Department for assistance (see inside front If the Power Unit has passed the FUNCTIONAL
cover for phone numbers). CHECK AND SAFETY INSPECTION for all
requirements of procedures 7.1 through 7.9, the
6. Unplug the Power Unit. Power Unit should be considered operational and
suitable for return to service.
15
Section 8 - Inspection Form
TC3146
138
136 PASS (Safe range)
134
132
SYMPTOM: NO HEAT
DOES NO
GO TO NO AIR FLOW
QUILT
SYMPTOM
INFLATE?
YES
PRESS
EACH SETTING NO
CALL TECHNICAL
BUTTON. DOES
SERVICE
CORRESPONDING
LED LIGHT?
YES
UNPLUG UNIT;
MEASURE HEATER
RESISTANCE
IS
HEATER NO
RESISTANCE
REPLACE HEATER
BETWEEN 10.0
AND 12.5
OHMS?
YES
UNPLUG RT1
THERMISTOR NO SUSPECT PC
ASSY. TURN
BOARD; CONTACT
POWER ON.
TECHNICAL SERVICE
DOES
UNIT HEAT?
YES
REPLACE RT1
THERMISTOR ASSY
ENSURE UNIT IS
PLUGGED IN
YES
NO
IS
CALL TECH SERVICE
RFU LIT?
YES
UNPLUG
UNIT AND
OPEN IT
IS FILTER NO REINSTALL
INSTALLED
FILTER
CORRECTLY?
YES
NO YES
S4 HAS
PERFORM FUNCTION CHECK--
TRIPPED
RUN UNIT IN LOW NO POSSIBLE CAUSES:
DOES RFU
(90°F, 32°C) SETTING 1. TOO HIGH STORAGE TEMP
REOCCUR?
FOR 10 MINUTES 2. UNIT OUT OF CAL.
3. LOW SPEC ON S2, S3
RESET S4 YES
POSSIBLE CONTROLLER
FAILURE; CALL TECH
SERVICE
IS THERE A
POWER UP NO YES REMOVE BLOCKAGE;
BLOCKED,BENT,
UNIT. REPLACE/ALIGN
OR MISALIGNED
AIRFLOW? BLOWER WHEEL
BLOWER WHEEL?
YES NO
REPAIR/REPLACE
MOTOR
PERFORM
FUNCTIONAL
CHECK
10.0 Repair Procedures 3. Remove the filter retainer and nut. Remove
the HEPA filter.
WARNING
4. Remove the ten screws securing the filter
inlet plate.
Use only Gaymar replacement parts as
identified in the parts lists (pp. 24-27). 5. Remove the screw and lock washer
Use of substitute parts could result in securing the ground wire to the backing
power unit malfunction or patient injury. plate. Remove the two screws securing the
terminal block.
6. Carefully lift the filter inlet plate, exposing the
To identify replacement parts, refer to figures blower wheel.
9-11 (pp. 24-27). To order replacement parts,
7. Remove the blower wheel using 1/8" hex
contact Gaymar's Customer Service Department:
wrench through hole in one blade of blower
Telephone: 1 800 828-7341 wheel.
(716) 662-2551
8. Remove the two #6 screws holding the
Fax: (716) 662-8795 heater to the motor bracket.
9. Disconnect the short wire from the heater to
the motor.
10.1 Replacing the Patient Limit 10. Remove the red heater wire from terminal
block location TB1-3 (see figure 11).
Thermostat(s) (S2 & S3)
Remove cable ties.
To replace either thermostat (item 18, fig. 11):
11. Remove the heater.
1. Unplug the Power Unit.
12. Install the replacement heater.
2. Remove the six screws securing the
enclosure. Open the enclosure. 13. Reroute the red wire through the 4-hole
grommet.
3. Carefully unplug the terminals from the
thermostat. 14. Reconnect both wires. Refer to TB1
designators in the schematic (figure 13) and
4. Remove the two #4 nuts from the terminal block wiring designators in figure
thermostat. 11. Install cable ties.
5. Replace the thermostat. Reinstall the nuts. 15. Reinstall the blower wheel, making sure
6. Carefully replace the terminals. there is 0.10" (2.5 mm) clearance between
the wheel and the blower inlet ring (see
7. Perform the FUNCTIONAL CHECK AND fig. 9). NOTE: the hex screw must be
SAFETY INSPECTION (section 7, pp. 8-15). aligned with the flat on the motor shaft.
16. Place the filter inlet plate back on top of the
scroll. Secure the ten screws.
10.2 Replacing the Heater
17. Replace the terminal block. Reconnect the
To replace the heater (item 3, fig. 9): ground wire to the backing plate; make sure
1. Unplug the Power Unit. the lock washer is reinstalled.
2. Remove the six screws securing the 18. Replace the HEPA filter. Secure it with the
enclosure. Open the enclosure. filter retainer and nut.
19. Perform the FUNCTIONAL CHECK AND
SAFETY INSPECTION (section 7, pp. 8-15).
21
Section 10 - Repair Procedures (cont’d)
8. Depending on the method of mounting, either 10. Remove the two #8 screws and two #8
use wire cutters to remove the spring clip, or nuts from the bottom of motor.
loosen the speed nut securing the thermistor 11. Loosen the two #8 screws on top of motor.
assembly to the filter inlet plate. Slide filter support bracket off. Loosen
9. Replacement thermistor assemblies may be corresponding screws on new motor and
slightly larger than the original. If necessary, replace filter support bracket. Tighten
open hole slightly, to 1/4". screws.
10. Replace the thermistor assembly. Secure 12. Remove and replace the motor.
it with the new speed nut supplied with the 13. Secure with mounting hardware.
thermistor assembly.
14. Reconnect the terminals.
11. Place filter inlet plate back on top of the scroll.
Secure the ten screws. 15. Secure wire harness to motor with a wire tie.
12. Replace the terminal block. Reconnect the 16. Reinstall the blower wheel, making sure
ground wire to the backing plate. Make sure there is 0.10" (2.5 mm) clearance between
the lock washer is reinstalled. the wheel and the blower inlet ring (see fig.
9). NOTE: the hex screw must be aligned
13. Plug the thermistor assembly into the control with the flat on the motor shaft.
board. Use the cable ties supplied with the
thermistor assembly to hold the thermistor 17. Place the filter inlet plate back on top of the
wires to the PC board wire harness and scroll. Secure the ten screws.
enclosure standoff. 18. Replace the terminal block. Reconnect the
14. Replace the HEPA filter. Secure it with the filter ground wire to the backing plate; make sure
retainer and nut. the lock washer is installed.
15. Perform the FUNCTIONAL CHECK AND SAFETY 19. Replace the HEPA filter. Secure it with the
INSPECTION (section 7, pp. 8-15). filter retainer and nut.
22
Section 10 - Repair Procedures (cont’d)
20. Perform the FUNCTIONAL CHECK AND 7. Connect brown and blue wires to the circuit
SAFETY INSPECTION (section 7, pp. 8-15). breaker (refer to label on inside of case).
8. Reconnect ground wire to filter inlet plate.
10.5 Replacing the I. V. Pole Mount 9. Secure wires with wire tie provided.
Bracket
10. Perform the FUNCTIONAL CHECK AND
To replace the I. V. pole mount bracket: SAFETY INSPECTION (section 7, pp. 8-15).
1. Unplug the Power Unit.
2. Remove the six screws securing the 10.7 Temperature Control PC Board
enclosure. Open the enclosure.
3. Remove the two screws securing the WARNING
terminal block from the backing plate.
The Temperature Control PC Board is
4. Remove the two screws and the lock washer pre-set at the factory. Do not attempt to
holding the I. V. pole mount bracket to the calibrate it. Adjustment of the Control
backing plate. PC Board in the field could result in
5. Remove the I. V. pole mount bracket from patient injury.
the rear half of the enclosure.
6. Insert new I. V. pole mounting bracket into To replace the P.C. board assembly
rear half of the enclosure. (item 11, fig. 10):
7. Replace the two screws and the lock washer 1. Unplug the Power Unit.
into the backing plate and I. V. pole mounting 2. Remove the six screws securing the
bracket. enclosure. Open the enclosure.
8. Replace the terminal block. 3. Cut the four cable ties which secure the PC
9. Perform the FUNCTIONAL CHECK AND board wires together.
SAFETY INSPECTION (section 7, pp. 8-15). 4. Unplug the following wires from the PC
board assembly at the terminal block (item
27, fig. 11):
10.6 Replacing the Power Cord
• Yellow wire from TB1-1C
To replace the power cord:
• Gray wire from TB1-2C
1. Unplug the Power Unit.
• Red wire from TB1-3C
2. Disconnect the blue and brown wires from
the circuit breaker and cut wire tie securing • White wire from TB1-4C
these wires. • Black wire from TB1-5C
3. Remove the top ground wire only (green with 5. Unplug the main harness (5-pin connector)
yellow stripe) from the filter inlet plate. from PC board.
4. Using a pair of pliers, from the outside, 6. Unplug the 2-pin harness from the PC board.
gently squeeze the strain relief and pull it out.
7. Remove the six screws securing the PC
5. Remove the power cord. board assembly.
6. Attach strain relief to new power cord and 8. Remove the old PC board assembly and
insert with pliers into case. install the new PC board assembly.
NOTE: Replace the power cord only with
the P/N listed on figure 11, page 26. 9. Reassemble in reverse order.
10. Perform the FUNCTIONAL CHECK AND
SAFETY INSPECTION (section 7, pp. 8-15).
23
Section 11 - Drawings/Parts Lists
Part
Item Description
Number
1 HEPA filter 78029-000
2 Filter retainer nut 91396-005
3 Heater 77947-000
4 RT1 Thermistor assembly 77942-000
5 Blower wheel 91369-000
6 a. Clip 90228-004
b. Rachet 91428-002
7 Label, Caution 08985-000
8 Bed rail hook 77943-000
6b
6a
4 7
3
8
5
0.10"
2.5 mm
24
Section 11 - Drawings/Parts Lists (cont’d)
78436-000
78437-000
12
09297-001
TEST PLUG
11
13
HOUR TIMER
14
10
S2 S3
Figure 10 - THERMOSTAT
BYPASS
HEAT
25
Section 11 - Drawings/Parts Lists (cont’d)
22 23
24
21
25
26
20
19
27
S3
S2
To release wires from
terminal block, insert
a small screwdriver in
slot nearest wire and
18 28 pull towards center.
29
17 S4
16
30
31
wire tie
32
26
Section 11 - Drawings/Parts Lists (cont’d)
16 S t ra in re lie f b u s h ing 9 0 4 2 6 -0 01 25 C a rd , c o n t ra in d ic a t io n, 0 9 8 7 3 -0 0 0
S p a n is h / P o r t u g u e s e
17 M o t o r k it 7 7 9 4 9 -0 00 26 C a rd , c o n t ra in d ic a t io n, 0 9 8 7 2 -0 0 0
E n g lis h / F r e n c h
18 P a t ie n t lim it t h e rm o s t a ts 9 1 3 2 3 -0 0 5 27 Te rm in a l b lo ck 9 1 3 4 6 -0 00
(S 2 , S 3 )
19 H o s e a s s e m b ly 78423-000 228 C o r d s t r a p a s s e m b ly 0 3 7 9 1 -0 00
20 K it , c a rd / la b el 7 8 1 0 9 -0 0 0 29 H e a t e r t h e rm o s t a t (S 4) 7 8 0 2 5 -0 00
r e p la c e m e n t
21 R e a r h o u s in g k it 30 P o w e r c o rd a s s e m b ly 0 8 3 7 4 -0 00
78438-000
( in c lu d e s la b e lin g )
22 I . V . p o le c la m p 0 8 6 1 4 -0 0 0 31 I n t e rlo c k s w it ch 9 1 3 7 5 -0 0 0
a s s e m b ly
23 To g g le s h oe 9 1 4 3 9 -0 00 32 S le e v in g , 4 1 / 2 " LG 8 1 0 5 4 -0 00
ATTENTION
Static-Sensitive
Devices
ATTENTION
Static-Sensitive
Devices
28
Section 13 - Wiring Diagram (cont’d)
29
®
Phone:
1 800 828-7341
(716) 662-2551
FAX:
1 800 993-7890
THERMACARE PRODUCTS
®
(716) 662-0748
ARE MADE IN THE USA