Sunteți pe pagina 1din 23

Bay Controller

BC 1703 ACP
Energy Automation

© Siemens AG 2009
Energy Sector
Applications

Bay control unit, optionally with integrated


overcurrent protection
Signal voltage
 110/220 VDC or
 48/60VDC
For direct installation into the bay or
into a control cubicle

From medium up to high and extra high voltage

Also applicable for applications with


 large no. of binary I/Os
 special communication protocols
 integrated control tasks (voltage, tap changer, …)
 diagnostics for HV GIS equipment
© Siemens AG 2009
Page 2 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Highlights

Control and protection in one device


 Realised by additional protection module
with own binary I/O for protection
Seamless communication based on IEC
60870-5-101/103/104 and IEC 61850
 Up to 3 serial interfaces possible
One tool for control and protection
 Separate engineering of control and
protection is possible (password)
 Object oriented data engineering
 Programming of process control and
interlocking functions via CAEx plus
(IEC 61131-3)
Plug & play for spare parts by flash card

© Siemens AG 2009
Page 3 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Control and Protection in 1 Device

IEC 60870-5-101/103/104
Realised by an architecture IEC 61850
with an separate
protection module BC 1703 ACP

No alternating

Supply
Power
Protection Module
impacts of

Control CPU + I/O


Communication
control and protection

Additional I/O's
(CPU + I/O)

Additional I/O's

Supply
Power
Option

Process
© Siemens AG 2009
Page 4 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Seamless Communication

Control Centre System

IEC 60870-5-104

Router
IEC 60870-5-104

IEC 60870-5-101

Router
SAT 200

IEC 60870-5-104 / IEC 61850


IEC 60870-5-101 IEC 60870-5-103 IEC 60870-5-103

BC 1703 ACP BC 1703 ACP BC 1703 ACP Reyrolle SIPROTEC BC 1703 ACP ELIN DRS
© Siemens AG 2009
Page 5 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
One Tool for Protection and Control

Control Centre System TOOLBOX II

IEC 60870-5-104

Router
IEC 60870-5-104

IEC 60870-5-101

Router
SICAM 230

IEC 60870-5-104 / IEC 61850


IEC 60870-5-101 IEC 60870-5-103 IEC 60870-5-103

BC 1703 ACP BC 1703 ACP BC 1703 ACP Reyrolle SIPROTEC BC 1703 ACP ELIN DRS
© Siemens AG 2009
Page 6 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Plug & Play for Spare Parts

Parameters and firmware stored


on flash card

No PC with tool box for device


exchange necessary due SD Card

Flash card also can be written by


Toolbox II offline in advance


© Siemens AG 2009
Page 7 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Control and Display Panel

Illuminated LCD display


 Readability from -10 ... +70°C
Single LED's
 Ready status
 Free definable status information for
protection and control
 3 colored LEDs
 Labelling via insert able strips
Control elements
 Key switch (Local/Remote/Test,
interlocked/unlocked)
 Numeric keypad
 Various push-buttons

© Siemens AG 2009
Page 8 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Mechanical Design

Rear, panel or 19" installation


 The control and display panel can
be located
remote up to 3m (optionally)
Process interface via screw terminal
 Wire cross-section up to 2,5mm²
 Wire cross-section for CTs up to
6mm²
EMC compatibility
 5kV isolation…
Temperature range
 -25 …+70°C

© Siemens AG 2009
Page 9 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
BC 1703 ACP Models

Compact Modular
 Medium and High Voltage  High Voltage (back-up protection)
 Up to 10 controlled equipment  10 controlled equipment and more
 Up to 73 I/O signals  Up to 500 I/O signals

BC 1703 ACP/C BC 1703 ACP/M


© Siemens AG 2009
Page 10 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Architecture BC 1703 ACP/C
IEC 60870-5-103 Slave 2x communication (serial, LAN, 61850)

CM-5882
Protection
Protection CPU
CPU with
with own
own peripherals,
peripherals,
AI-5399
AI-5399 for
for VT
VT

PS-562x
AI-5399
CP-5002(3)/PIP5x

DO-5212/PCCO55
CP-5014/CPCX55

DI-5111(0)/BISI55
Master
Master control
control CPU,
CPU,
SM-25xx
with
with local
local peripherals
peripherals andand
11 opt.
opt. local
local serial
serial interface
interface (103
(103 Slave)
Slave)

REDUNDANT
PS-562x
Power
Power supply,
supply, optional
optional redundant
redundant
DI-5199(8) /
DO-5298

ItIt can
can be
be equipped
equipped up
up toto 22
peripheral
peripheral elements
elements (PE)
(PE)
(without
(without protection-CPU
protection-CPU up
up toto 33 PE)
PE)
Display
Display can
can be
be located
located remote
remote (3m)
(3m) (220mm
(220mm xx 266mm)
266mm)
© Siemens AG 2009
Page 11 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Architecture BC 1703 ACP/M
IEC 60870-5-103 Slave 2x communication (serial, LAN, 61850)

CM-5888

PS-562x
AI-5399
CP-5002(3)/PIP5x

DO-5212/PCCO55
CP-5014/CPCX55

DI-5111(0)/BISI55

DI-5111(0)/BISI55
DO-5203/BISO55
AI-5303/TIPS05

AI-5303/TIPS05
SM-25xx

REDUNDANT
PS-562x
11 xx optical
optical interface
interface
for
for Ax
Ax 1703
1703 peripheral
peripheral bus,
bus,

Total
Total number
number ofof peripheral
peripheral elements
elements
(internal
(internal ++ external)
external) ≤≤ 16
16
© Siemens AG 2009
Page 12 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Architecture BC 1703 ACP/M
IEC 60870-5-103 Slave 2x communication (serial, LAN, 61850)

CM-5888

PS-562x
AI-5399
CP-5002(3)/PIP5x

DO-5212/PCCO55
CP-5014/CPCX55

DI-5111(0)/BISI55

DI-5111(0)/BISI55
DO-5203/BISO55
AI-5303/TIPS05

AI-5303/TIPS05
SM-25xx

REDUNDANT
PS-562x
ItIt can
can be
be equipped
equipped up
up to
to 66
peripheral
peripheral elements
elements (PE)
(PE)
(without
(without protection-CPU
protection-CPU up
up to
to 88 PE)
PE)
(315mm
(315mm xx 266mm)
266mm)
© Siemens AG 2009
Page 13 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Architecture BC 1703 ACP/M
IEC 60870-5-103 Slave 2x communication (serial, LAN)

CM-5884

PS-562x
AI-5399
CP-5002(3)/PIP5x

DO-5212/PCCO55
CP-5014/CPCX55

DI-5111(0)/BISI55
DO-5203/BISO55
AI-5303/TIPS05

AI-5303/TIPS05
SM-25xx

REDUNDANT
PS-562x
ItIt can
can be
be equipped
equipped up up to
to 13
13
peripheral
peripheral elements
elements (PE)
(PE)
(without
(without protection-CPU
protection-CPU up up to
to 15
15 PE)
PE)
(483mm
(483mm (=19")
(=19") xx 266mm)
266mm)
© Siemens AG 2009
Page 14 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Module Overview

Protection
Protection(Optionally)
(Optionally)
CP-5002/CP-5003
CP-5002/CP-5003 Protection
ProtectionModule
Module(CPU,
(CPU,Input
Input(8x),
(8x),Output
Output(5x2pole),
(5x2pole),
Analog
AnalogInput
Input(Transf.
(Transf.4xI)
4xI)
Submodules
Submodulesfor
forCP-5002/3
CP-5002/3
AI-5399
AI-5399 Analog
AnalogInput
Input(Transformer
(Transformer4xU)
4xU)
Control
Control
CP-5014
CP-5014 Control
ControlCPU,
CPU,Command
CommandOutput
Output(4(4xx2pole,
2pole,33groups)
groups)
Submodules for CP-5014 (for CM-5882
Submodules for CP-5014 (for CM-5882 only) only)
DI-519x,
DI-519x,oder
oder Binary
BinaryInput
Input(14,
(14,48-60VDC,110-220VDC),
48-60VDC,110-220VDC),Binary
BinaryOutput
Output(2)
(2)
DO-5298
DO-5298 Command Output (6 x 2pole, 3
Command Output (6 x 2pole, 3 groups)groups)
further
further peripheralsfor
peripherals forprocess
processcontrolcontrol
DI-511x
DI-511x Binary
Binary Input (28,48-60VDC,110-220VDC)
Input (28, 48-60VDC,110-220VDC)
DO-5212
DO-5212 Command
Command Output(14x2-pole,
Output (14x2-pole,44groups,
groups,direct
directmotor
motordrive(30A))
drive(30A))
DO-5203
DO-5203 Binary Output (16 x 1pole relais 24-220VDC/230VAC)
Binary Output (16 x 1pole relais 24-220VDC/230VAC)
AI-5300
AI-5300 Analog
AnalogInput
Input8x20mA
8x20mA
AI-5303
AI-5303 Analog Input (Transformer,4xU,3xI)
Analog Input (Transformer,4xU,3xI)
Power
Powersupply
supply
PS-560x
PS-560x 24-60VDC,
24-60VDC,110-220VDC,
110-220VDC,115-230VAC,
115-230VAC,22W
22W
PS-562x
PS-562x 24-60VDC,
24-60VDC,110-220VDC,
110-220VDC,115-230VAC,
115-230VAC,80W
80W
© Siemens AG 2009
Page 15 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Peripheral Element TM 1703 ACP
Available I/O Modules
= 1 periphe ral
el.
Power supply
PS-6630 24-60VDC EMC+ 1-2
PS-6632 110-220VDC EMC+
Peripheral Control Modules
1
PE-6411 Ax-PE Bus coupler (1x optical PCF, 200m)
Binary I/O-modules
DI-6100 Binary Input 2x8, 24-60VDC, resolution 10ms
DI-6101 Binary Input 2x8, 110/220VDC, resolution 10ms
DI-6102 Binary Input 2x8, 24-60VDC, resolution 1ms
DI-6103 Binary Input 2x8, 110/220VDC, resolution 1ms
DI-6104 Binary Input 2x8, 220VDC, resolution 10ms
DO-6200 Binary Output Transistor 2x8, 24-60VDC
DO-6212 Binary Output Relays 8x 24-220VDC/230VAC
DO-6220 Command Output Basic Module 24-125VDC
DO-6221 Command Output Basic Module with measure 24-125VDC 1-8
DO-6230 Command Output Relay Module Relays 2x8 24-125VDC
Analog I/O-modules
AI-6300 Analog Input 2x2 ±20mA/±10V
AI-6307 Analog Input 2x2 ± 5mA
AI-6310 Analog Input 2x2 Pt100/Ni100
AO-6380 Analog Output 4x ±20mA/±10mA/±10V
TE-6420 Speed Measurement 2x2 24VDC/5VDC/NAMUR © Siemens AG 2009
TE-6450
Page 16 PositionNov-09
Acquisition 2x2 SSI/RS422
Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Peripheral Element TM 1703 ACP
Special Case: CT/VT Inputs

Power Supply
PS-66xx + AI-6303
4 VT-Inputs
= 1 perip
heral ele
ment

Output Relay for


Synchrocheck/ 3 CT-Inputs
Synchronizing

Ax-Bus interface (optical & electrical)


no additional Ax Bus coupler necessary © Siemens AG 2009
Page 17 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
Extract of Protection Functions

Over current protection Cold load pickup


Earth fault overcurrent protection Circuit breaker fail
Negative phase sequence protection Auto-reclose
Directional phase-fault detection Switch on to fault
Directional earth-fault detection Trip circuit supervision
Fault locator Thermal overload
Phase under- and overvoltage Fault, Event, Disturbance Records
Residual overvoltage Synchro check
Inrush restraint Parameter sets
Dynamic parameter switching

© Siemens AG 2009
Page 18 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
KEMA Certification

Complete functionality of protection is


tested by an independent external test
laboratory.

© Siemens AG 2009
Page 19 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
KEMA Certification– IEC 61850

© Siemens AG 2009
Page 20 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
References of BC 1703 ACP (Excerpt)

KWO (Innertkirchen, CH)


 12 devices, directional DTL
 Communication via LAN (IEC 104)
Olympic Village (GR)
 23 devices, undirectional DTL
Deutsche Bahn (GER)
 13 devices, directional DTL
TenneT (NL)
 7 devices for 380kV
bay control & back up protection
 2 x IEC 101 to a redundant control
centre system (no station controller)
Monk-Fryston (UK)
 7 devices for 400kV
bay control & back up protection
© Siemens AG 2009
Page 21 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
ACP 1703 Features

Parameters stored on Flash Card

Plug & Play for Spare Parts

Engineering with TOOLBOX II

Programming language according to


IEC 61131-3

Remote Maintenance with TOOLBOX II


© Siemens AG 2009
Page 22 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector
BC 1703 ACP Further Highlights

Combination of
 measuring (high accuracy) &
 protection
in one device

Programming language according to


IEC 61131-3,
 integrated
 voltage controller
 tap change controller
in one device

Versatile communication
 IEC 61850, IEC 60870-5-101/3/4
 Further protection devices can be
connected (e.g. via 103)
© Siemens AG 2009
Page 23 Nov-09 Energy Automation M. Haslinger E D EA PRO LM2 Energy Sector

S-ar putea să vă placă și