Documente Academic
Documente Profesional
Documente Cultură
Figure 1
Cost/SF Comparison of Studied Buildings
had the sixth lowest life cycle cost; the DX RTU elementary the replacement cost to be 50% of the original construction
school was in seventh place. In last place was an elementary cost (e.g., $31 x 50% = $15.50/SF). However, a 3% escalation
school that was retrofitted with VRF heat pumps. As shown factor was used to adjust this cost for the future: $24.15/SF in
in Figure 1, replacement allocations had a significant impact 15 years. For equipment lasting 24 and 25 years, applying this
on the life cycle cost analysis (see yellow bars) and drastically full replacement cost at the time of replacement would give
reduced the cost effectiveness of equipment with 15-year life a distorted view for these units in the 30-year life cycle cost
expectancies. analysis, so this was prorated to represent the replacement
cost during the remaining years of the life cycle cost analysis
Other studies have shown the ability of ground source heat only. The age of equipment can vary drastically, and ASHRAE
pumps to use much less energy than variable refrigerant flow has created an online database to provide service life of
heat pumps (see 2013 study by Oklahoma State University and typical HVAC equipment as a part of ASHRAE Research Project
Oak Ridge National Laboratory of the ASHRAE Headquarters 1237-TRP along with information in the ASHRAE Handbook —
Building). However, in this study, the school that used ground HVAC Applications.
source heat pumps had thermally contaminated wells that
likely contributed to excessive energy use. Some additional factors are likely at play within this data set
considering it is compiled from various sources (e.g., lighting
Equipment replacement allocations were applied to each technology, outside air delivery, etc.). However, HVAC systems
system with the following equipment life assumptions: DX can make up 50% of the overall energy use of K-12 buildings,
RTU and VRF (15 years), WSHP and GSHP (24 years), WC and according to data from ENERGY STAR.
ACC (25 years). This allocation was reached by estimating
Figure 2
10-Year Life Cycle Cost Analysis
Figure 3
15-Year Life Cycle Cost Analysis
2
Figure 4
20-Year Life Cycle Cost Analysis
Figure 5
25-Year Life Cycle Cost Analysis
Graphical results for 10-,15-, 20- and 25-year life cycles can The installed cost of the mechanical system is estimated to be
be seen in Figures 2-5. Please note: A negative replacement around $42/SF in 2019 dollars, according to a cost consultant
cost corresponds to the value associated with the remaining in the area. Upfront cost of DOAS units were reduced as a
equipment life. result of using the IAQ method instead of the ventilation rate
procedure (VRP) as outlined in ASHRAE 62.1. When the amount
VRF middle school of outside air needed is reduced, there is a commensurate
reduction in the amount of energy use and costs. The
This new construction school is primarily served by a VRF
ventilation air load requirements can vary significantly, but the
multizone system with heat recovery. Dedicated outdoor air
latent load is considerable for this facility’s location in Climate
system (DOAS) units separately supply necessary ventilation
Zone 3A (see Atlanta in Figure 6). There is a twofold benefit to
air for occupants and building pressure. Bipolar ionization air
applying the IAQ method for this building: a reduction in first
cleaning allows for reduced outside air delivery through these
cost and also ongoing annual energy cost. However, changes
DOAS units in accordance with the indoor air quality (IAQ)
to the IAQ method are currently being evaluated that would
method as outlined in ASHRAE 62.1. Some nonclassroom
require CO2 less than or equal to 1,100 ppm in the space.
portions of the building, such as the administrative offices,
gymnasium and cafeteria, are served by traditional DX RTUs
without DOAS units.
3
Albuquerque Latent ton-hours per scfm per year
Boston
Sensible ton-hours per scfm per year
Detroit
Minneapolis
Pittsburgh
New York
Chicago
Las Vegas
Indianapolis
Lexington
Colorado Springs
Omaha
Phoenix
St. Louis
Oklahoma City
Richmond
Raleigh
Atlanta
Nashville
Little Rock
Charleston
San Antonio
New Orleans
Miami
5 10 15 20 25
Figure 6
Cumulative Dehumidification and Cooling Loads
from Ventilation Air
Latent and Sensible Ton-Hours Per scfm per year
5
Maintenance of the multizone VRF system is more complex
than a traditional DX system, so some maintenance has
been contracted to outside sources. This obviously comes
at an increased cost but ensures efficient, reliable operation
of equipment. The district maintenance cost for the HVAC
systems at this school averaged $14,337/year, but contract
maintenance totaled approximately $5,000/year, which
equates to $0.2111/SF annually. As a comparison, the average
maintenance cost in schools is $0.112/SF, according to an
ASHRAE Research Project 1237-TRP.
Figure 12
30-Year Life Cycle Cost for VRF Elementary School
(5% Escalation on Energy and 3% on Maint/Replace)
6
DX RTU Elementary School
This elementary school is primarily served by direct expansion
(DX) Rooftop Units (RTU) feeding VAV boxes with hot water
heat from natural gas boilers.
7
The maintenance cost for the HVAC systems at this school
averaged $8,887/year, which equates to $0.0993/SF annually.
As a comparison, the average maintenance cost in schools
is $0.112/SF, according to an ASHRAE Research Project
1237-TRP.
Figure 20
30-Year Life Cycle Cost for ACC Elementary School
(5% Escalation on Energy and 3% on Maint/Replace)