Documente Academic
Documente Profesional
Documente Cultură
: PMT-MS-
FUSE CUT OUT 002.mga
TESTING METHODOLOGY
REV.NO.00
PROJECT:
Reviewed by:
Signed:
Date:
Rev.No.
A – No Comments
B – Comments as noted
C – Not to be used
METHOD STATEMENT
FOR
TESTING AND COMMISSIONING
Page 1 of 7
Doc. No.: PMT-MS-
FUSE CUT OUT 002.mga
TESTING METHODOLOGY
REV.NO.00
2. OBJECTIVE
The Fuse Cutout must be suitable for High Voltage Distribution lines and Transformer,
acting as an overload protector and a device for opening and closing load current. All the
metal parts of the fuse cutout are free from erosion and rust.
The purpose of this document is to present and describe the method of testing for Fuse
Cut out.
All installation and testing works must cover the general procedures for the testing of
Fuse Cutout. The testing will consist of two associated phases; the investigation (test
analysis) and the visual inspection (perceptual analysis). Electrical field tests will be
limited to those hereinafter specified for the Fuse Cutout. Visual examination shall be prior
to, during, and after the energization of the electrical installations. Visual inspection
includes:
Page 2 of 7
Doc. No.: PMT-MS-
FUSE CUT OUT 002.mga
TESTING METHODOLOGY
REV.NO.00
Prior to inspection Engineers must inspect the area to avoid unnecessary delay of
inspection
Engineers must prepare documents, brochure and shop drawings if it’s necessary
for easy checking and prepare test data.
Engineers must submit a list of remaining works with target completion date
Inspection will be visual, functional and actual running test with complete testing
instruments
After inspection prepare punch list report with target completion date
Client will confirm all completed punch list and/or prepare pictorial report especially
for the concealed items for necessary approval
As-Built Drawings
Page 3 of 7
Doc. No.: PMT-MS-
FUSE CUT OUT 002.mga
TESTING METHODOLOGY
REV.NO.00
To test the Fuse Cutout, test prod is pointed to line and load side terminal of each pole,
micro ohms reading of each pole must not exceed the recommended values of the
manufacturer.
7. FUSE CUTOUT
e) Inspect bolted electrical connections for high resistance using one of the
following methods:
Page 4 of 7
Doc. No.: PMT-MS-
FUSE CUT OUT 002.mga
TESTING METHODOLOGY
REV.NO.00
g) Verify that fuse size and types are in accordance with drawings, short-circuit
study, and coordination study
h) Verify that each fuse holder has adequate mechanical support and contact
integrity
ELECTRICAL TEST
TEST VALUES
Page 5 of 7
Doc. No.: PMT-MS-
FUSE CUT OUT 002.mga
TESTING METHODOLOGY
REV.NO.00
b) Microhm or millivolt drop values should not exceed the high levels of the normal
range as indicated in the manufacturer’s published data. If manufacturer’s data
is not available, investigate values which deviate from adjacent poles or similar
switches by more than 50 percent of the lowest value.
B) Discrepancies.
3. TEST PARAMETERS
Page 7 of 7