PVSYST V6.

86 29/01/20 Page 1/4


A1 Building

Grid-Connected System: Simulation parameters


Project : AHB
Geographical Site Hanoi Country Vietnam
Situation Latitude 21.02° N Longitude 105.84° E
Time defined as Legal Time Time zone UT+7 Altitude 30 m
Albedo 0.20
Meteo data: Hanoi Meteonorm 7.2 (1993-2000), Sat=100% - Synthetic

PVsyst TRIAL
Simulation variant :

Simulation parameters
Collector Plane Orientation
A1_Bldg
Simulation date

System type
Tilt
29/01/20 09h42

No 3D scene defined, no shadings


16° Azimuth 0°
Models used Transposition Perez Diffuse Perez, Meteonorm
Horizon Free Horizon
Near Shadings No Shadings
User's needs : Unlimited load (grid)

PVsyst TRIAL
PV Array Characteristics
PV module Si-mono Model LR6-72 HPH 400 M
Original PVsyst database Manufacturer Longi Solar
Number of PV modules In series 14 modules In parallel 60 strings
Total number of PV modules Nb. modules 840 Unit Nom. Power 400 Wp
Array global power Nominal (STC) 336 kWp At operating cond. 305 kWp (50°C)
Array operating characteristics (50°C) U mpp 518 V I mpp 589 A
Total area Module area 1662 m² Cell area 1482 m²

Inverter Model SUN2000-60KTL-HV-D1-001


Custom parameters definition Manufacturer Huawei Technologies
Characteristics Operating Voltage 200-1000 V Unit Nom. Power 60.0 kWac
Max. power (=>30°C) 66.0 kWac

PVsyst TRIAL
Inverter pack Nb. of inverters 30 * MPPT 17 % Total Power 300 kWac
Pnom ratio 1.12

PV Array loss factors


Thermal Loss factor Uc (const) 20.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 15 mOhm Loss Fraction 1.5 % at STC
Module Quality Loss Loss Fraction -0.5 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
Incidence effect (IAM): User defined profile
0° 25° 45° 60° 65° 70° 75° 80° 90°
1.000 1.000 0.995 0.962 0.936 0.903 0.851 0.754 0.000

PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.86 29/01/20 Page 2/4

Grid-Connected System: Main results


Project : AHB
Simulation variant : A1_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 840 Pnom total 336 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 5.0 Pnom total 300 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 406.9 MWh/year Specific prod. 1211 kWh/kWp/year
Performance Ratio PR 86.80 %

Normalized productions (per installed kWp): Nominal power 336 kWp Performance Ratio PR

6 1.0
Lc : Collection Loss (PV-array losses) 0.46 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.868
0.9
Ls : System Loss (inverter, ...) 0.04 kWh/kWp/day
5 Yf : Produced useful energy (inverter output) 3.32 kWh/kWp/day
0.8
[kWh/kWp/day]

0.7
Performance Ratio PR

PVsyst TRIAL
0.6
Energy

3 0.5

0.4
Normalized

2
0.3

0.2
1

0.1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

A1_Bldg
Balances and main results

PVsyst TRIAL January


February
March
April
GlobHor
kWh/m²
67.3
69.2
86.6
104.9
DiffHor
kWh/m²
48.71
53.08
65.75
70.55
T_Amb
°C
15.45
17.33
20.62
24.44
GlobInc
kWh/m²
73.3
72.7
87.8
104.2
GlobEff
kWh/m²
71.3
70.6
85.3
101.2
EArray
MWh
22.75
22.35
26.42
30.74
E_Grid
MWh
22.46
22.07
26.08
30.35
PR

0.911
0.904
0.884
0.867
May 144.1 86.20 27.81 138.1 134.3 39.98 39.49 0.851
June 153.3 92.30 29.36 145.3 141.3 41.96 41.45 0.849
July 159.9 90.93 29.39 152.0 147.8 43.79 43.26 0.847
August 155.1 92.68 28.46 152.8 148.8 44.24 43.72 0.851
September 131.2 81.43 26.84 134.5 130.9 39.24 38.77 0.858
October 129.8 80.52 25.02 140.0 136.5 41.29 40.81 0.868
November 92.9 59.49 20.72 103.9 101.3 31.36 30.98 0.887

PVsyst TRIAL December


Year

Legends: GlobHor
DiffHor
T_Amb
80.4
1374.6
55.84
877.49

Horizontal global irradiation


Horizontal diffuse irradiation
T amb.
17.24
23.59
90.4
1395.1
87.9
1357.4

GlobEff
EArray
E_Grid
27.79
411.91
27.45
406.88
0.904
0.868

Effective Global, corr. for IAM and shadings


Effective energy at the output of the array
Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio

PVsyst Evaluation mode


PVSYST V6.86 29/01/20 Page 3/4

Grid-Connected System: Special graphs


Project : AHB
Simulation variant : A1_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 840 Pnom total 336 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 5.0 Pnom total 300 kW ac
User's needs Unlimited load (grid)

Daily Input/Output diagram

2500
Values from 01/01 to 31/12

2000
Energy injected into grid [kWh/day]

1500

PVsyst TRIAL 1000

500

0
0 1 2 3 4 5 6 7 8
Global incident in coll. plane [kWh/m².day]

PVsyst TRIAL
System Output Power Distribution

8000
Values from 01/01 to 31/12
7000
Energy injected into grid [kWh / Bin]

6000

5000

4000

3000

PVsyst TRIAL 2000

1000

0
0 50 100 150 200 250 300
Power injected into grid [kW]

PVsyst Evaluation mode


PVSYST V6.86 29/01/20 Page 4/4

Grid-Connected System: Loss diagram


Project : AHB
Simulation variant : A1_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 840 Pnom total 336 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 5.0 Pnom total 300 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1375 kWh/m² Horizontal global irradiation


+1.5% Global incident in coll. plane

-2.70% IAM factor on global

1357 kWh/m² * 1662 m² coll. Effective irradiation on collectors


efficiency at STC = 20.24% PV conversion

PVsyst TRIAL 456.6 MWh Array nominal energy (at STC effic.)
-0.43% PV loss due to irradiance level

-8.06% PV loss due to temperature

+0.50%

-1.10%
Module quality loss

Mismatch loss, modules and strings


-0.86% Ohmic wiring loss
411.9 MWh Array virtual energy at MPP

-1.21% Inverter Loss during operation (efficiency)


0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage

PVsyst TRIAL
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
-0.01% Night consumption
406.9 MWh Available Energy at Inverter Output
406.9 MWh Energy injected into grid

PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.86 29/01/20 Page 1/4
TH2 Building

Grid-Connected System: Simulation parameters


Project : AHB
Geographical Site Hanoi Country Vietnam
Situation Latitude 21.02° N Longitude 105.84° E
Time defined as Legal Time Time zone UT+7 Altitude 30 m
Albedo 0.20
Meteo data: Hanoi Meteonorm 7.2 (1993-2000), Sat=100% - Synthetic

PVsyst TRIAL
Simulation variant :

Simulation parameters
Collector Plane Orientation
TH2_Bldg
Simulation date

System type
Tilt
29/01/20 09h48

No 3D scene defined, no shadings


16° Azimuth 0°
Models used Transposition Perez Diffuse Perez, Meteonorm
Horizon Free Horizon
Near Shadings No Shadings
User's needs : Unlimited load (grid)

PVsyst TRIAL
PV Array Characteristics
PV module Si-mono Model LR6-72 HPH 400 M
Original PVsyst database Manufacturer Longi Solar
Number of PV modules In series 14 modules In parallel 48 strings
Total number of PV modules Nb. modules 672 Unit Nom. Power 400 Wp
Array global power Nominal (STC) 269 kWp At operating cond. 244 kWp (50°C)
Array operating characteristics (50°C) U mpp 518 V I mpp 471 A
Total area Module area 1329 m² Cell area 1185 m²

Inverter Model SUN2000-60KTL-HV-D1-001


Custom parameters definition Manufacturer Huawei Technologies
Characteristics Operating Voltage 200-1000 V Unit Nom. Power 60.0 kWac
Max. power (=>30°C) 66.0 kWac

PVsyst TRIAL
Inverter pack Nb. of inverters 24 * MPPT 17 % Total Power 240 kWac
Pnom ratio 1.12

PV Array loss factors


Thermal Loss factor Uc (const) 20.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 18 mOhm Loss Fraction 1.5 % at STC
Module Quality Loss Loss Fraction -0.5 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
Incidence effect (IAM): User defined profile
0° 25° 45° 60° 65° 70° 75° 80° 90°
1.000 1.000 0.995 0.962 0.936 0.903 0.851 0.754 0.000

PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.86 29/01/20 Page 2/4

Grid-Connected System: Main results


Project : AHB
Simulation variant : TH2_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 672 Pnom total 269 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 4.0 Pnom total 240 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 325.5 MWh/year Specific prod. 1211 kWh/kWp/year
Performance Ratio PR 86.80 %

Normalized productions (per installed kWp): Nominal power 269 kWp Performance Ratio PR

6 1.0
Lc : Collection Loss (PV-array losses) 0.46 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.868
0.9
Ls : System Loss (inverter, ...) 0.04 kWh/kWp/day
5 Yf : Produced useful energy (inverter output) 3.32 kWh/kWp/day
0.8
[kWh/kWp/day]

0.7
Performance Ratio PR

PVsyst TRIAL
0.6
Energy

3 0.5

0.4
Normalized

2
0.3

0.2
1

0.1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

TH2_Bldg
Balances and main results

PVsyst TRIAL January


February
March
April
GlobHor
kWh/m²
67.3
69.2
86.6
104.9
DiffHor
kWh/m²
48.71
53.08
65.75
70.55
T_Amb
°C
15.45
17.33
20.62
24.44
GlobInc
kWh/m²
73.3
72.7
87.8
104.2
GlobEff
kWh/m²
71.3
70.6
85.3
101.2
EArray
MWh
18.20
17.88
21.14
24.59
E_Grid
MWh
17.96
17.66
20.87
24.28
PR

0.911
0.904
0.884
0.867
May 144.1 86.20 27.81 138.1 134.3 31.98 31.59 0.851
June 153.3 92.30 29.36 145.3 141.3 33.57 33.16 0.849
July 159.9 90.93 29.39 152.0 147.8 35.03 34.61 0.847
August 155.1 92.68 28.46 152.8 148.8 35.39 34.97 0.851
September 131.2 81.43 26.84 134.5 130.9 31.39 31.01 0.858
October 129.8 80.52 25.02 140.0 136.5 33.04 32.64 0.868
November 92.9 59.49 20.72 103.9 101.3 25.09 24.78 0.887

PVsyst TRIAL December


Year

Legends: GlobHor
DiffHor
T_Amb
80.4
1374.6
55.84
877.49

Horizontal global irradiation


Horizontal diffuse irradiation
T amb.
17.24
23.59
90.4
1395.1
87.9
1357.4

GlobEff
EArray
E_Grid
22.23
329.53
21.96
325.51
0.904
0.868

Effective Global, corr. for IAM and shadings


Effective energy at the output of the array
Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio

PVsyst Evaluation mode


PVSYST V6.86 29/01/20 Page 3/4

Grid-Connected System: Special graphs


Project : AHB
Simulation variant : TH2_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 672 Pnom total 269 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 4.0 Pnom total 240 kW ac
User's needs Unlimited load (grid)

Daily Input/Output diagram

1800
Values from 01/01 to 31/12
1600
Energy injected into grid [kWh/day]

1400

1200

PVsyst TRIAL
1000

800

600

400

200

0
0 1 2 3 4 5 6 7 8
Global incident in coll. plane [kWh/m².day]

PVsyst TRIAL
System Output Power Distribution

7000
Values from 01/01 to 31/12
6000
Energy injected into grid [kWh / Bin]

5000

4000

3000

PVsyst TRIAL 2000

1000

0
0 50 100 150 200 250
Power injected into grid [kW]

PVsyst Evaluation mode


PVSYST V6.86 29/01/20 Page 4/4

Grid-Connected System: Loss diagram


Project : AHB
Simulation variant : TH2_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 672 Pnom total 269 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 4.0 Pnom total 240 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1375 kWh/m² Horizontal global irradiation


+1.5% Global incident in coll. plane

-2.70% IAM factor on global

1357 kWh/m² * 1329 m² coll. Effective irradiation on collectors


efficiency at STC = 20.24% PV conversion

PVsyst TRIAL 365.3 MWh Array nominal energy (at STC effic.)
-0.43% PV loss due to irradiance level

-8.06% PV loss due to temperature

+0.50%

-1.10%
Module quality loss

Mismatch loss, modules and strings


-0.86% Ohmic wiring loss
329.5 MWh Array virtual energy at MPP

-1.21% Inverter Loss during operation (efficiency)


0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage

PVsyst TRIAL
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
-0.01% Night consumption
325.5 MWh Available Energy at Inverter Output
325.5 MWh Energy injected into grid

PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.86 A2 Building 29/01/20 Page 1/4

Grid-Connected System: Simulation parameters


Project : AHB
Geographical Site Hanoi Country Vietnam
Situation Latitude 21.02° N Longitude 105.84° E
Time defined as Legal Time Time zone UT+7 Altitude 30 m
Albedo 0.20
Meteo data: Hanoi Meteonorm 7.2 (1993-2000), Sat=100% - Synthetic

PVsyst TRIAL
Simulation variant :

Simulation parameters
Collector Plane Orientation
A2_Bldg
Simulation date

System type
Tilt
29/01/20 09h36

No 3D scene defined, no shadings


16° Azimuth 0°
Models used Transposition Perez Diffuse Perez, Meteonorm
Horizon Free Horizon
Near Shadings No Shadings
User's needs : Unlimited load (grid)

PVsyst TRIAL
PV Array Characteristics
PV module Si-mono Model LR6-72 HPH 400 M
Original PVsyst database Manufacturer Longi Solar
Number of PV modules In series 14 modules In parallel 12 strings
Total number of PV modules Nb. modules 168 Unit Nom. Power 400 Wp
Array global power Nominal (STC) 67.2 kWp At operating cond. 61.0 kWp (50°C)
Array operating characteristics (50°C) U mpp 518 V I mpp 118 A
Total area Module area 332 m² Cell area 296 m²

Inverter Model SUN2000-60KTL-HV-D1-001


Custom parameters definition Manufacturer Huawei Technologies
Characteristics Operating Voltage 200-1000 V Unit Nom. Power 60.0 kWac
Max. power (=>30°C) 66.0 kWac

PVsyst TRIAL
Inverter pack Nb. of inverters 6 * MPPT 17 % Total Power 60 kWac
Pnom ratio 1.12

PV Array loss factors


Thermal Loss factor Uc (const) 20.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 74 mOhm Loss Fraction 1.5 % at STC
Module Quality Loss Loss Fraction -0.5 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
Incidence effect (IAM): User defined profile
0° 25° 45° 60° 65° 70° 75° 80° 90°
1.000 1.000 0.995 0.962 0.936 0.903 0.851 0.754 0.000

PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.86 29/01/20 Page 2/4

Grid-Connected System: Main results


Project : AHB
Simulation variant : A2_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 168 Pnom total 67.2 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 81.38 MWh/year Specific prod. 1211 kWh/kWp/year
Performance Ratio PR 86.80 %

Normalized productions (per installed kWp): Nominal power 67.2 kWp Performance Ratio PR

6 1.0
Lc : Collection Loss (PV-array losses) 0.46 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.868
0.9
Ls : System Loss (inverter, ...) 0.04 kWh/kWp/day
5 Yf : Produced useful energy (inverter output) 3.32 kWh/kWp/day
0.8
[kWh/kWp/day]

0.7
Performance Ratio PR

4
0.6

PVsyst TRIAL
Energy

3 0.5

0.4
Normalized

2
0.3

0.2
1

0.1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

A2_Bldg
Balances and main results

PVsyst TRIAL
GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR
kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh
January 67.3 48.71 15.45 73.3 71.3 4.550 4.491 0.911
February 69.2 53.08 17.33 72.7 70.6 4.471 4.415 0.904
March 86.6 65.75 20.62 87.8 85.3 5.284 5.217 0.884
April 104.9 70.55 24.44 104.2 101.2 6.147 6.070 0.867
May 144.1 86.20 27.81 138.1 134.3 7.996 7.899 0.851
June 153.3 92.30 29.36 145.3 141.3 8.392 8.290 0.849
July 159.9 90.93 29.39 152.0 147.8 8.758 8.652 0.847
August 155.1 92.68 28.46 152.8 148.8 8.849 8.743 0.851
September 131.2 81.43 26.84 134.5 130.9 7.848 7.753 0.858
October 129.8 80.52 25.02 140.0 136.5 8.259 8.161 0.868
November 92.9 59.49 20.72 103.9 101.3 6.271 6.195 0.887
December 80.4 55.84 17.24 90.4 87.9 5.557 5.490 0.904

PVsyst TRIAL Year

Legends: GlobHor
DiffHor
T_Amb
GlobInc
1374.6 877.49

Horizontal global irradiation


Horizontal diffuse irradiation
T amb.
Global incident in coll. plane
23.59 1395.1 1357.4

GlobEff
EArray
E_Grid
PR
82.382 81.377 0.868

Effective Global, corr. for IAM and shadings


Effective energy at the output of the array
Energy injected into grid
Performance Ratio

PVsyst Evaluation mode


PVSYST V6.86 29/01/20 Page 3/4

Grid-Connected System: Special graphs


Project : AHB
Simulation variant : A2_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 168 Pnom total 67.2 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
User's needs Unlimited load (grid)

Daily Input/Output diagram

500
Values from 01/01 to 31/12

400
Energy injected into grid [kWh/day]

300

PVsyst TRIAL 200

100

0
0 1 2 3 4 5 6 7 8
Global incident in coll. plane [kWh/m².day]

System Output Power Distribution

PVsyst TRIAL 1600

1400
Values from 01/01 to 31/12
Energy injected into grid [kWh / Bin]

1200

1000

800

600

PVsyst TRIAL 400

200

0
0 10 20 30 40 50 60
Power injected into grid [kW]

PVsyst Evaluation mode


PVSYST V6.86 29/01/20 Page 4/4

Grid-Connected System: Loss diagram


Project : AHB
Simulation variant : A2_Bldg
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 16° azimuth 0°
PV modules Model LR6-72 HPH 400 M Pnom 400 Wp
PV Array Nb. of modules 168 Pnom total 67.2 kWp
Inverter Model SUN2000-60KTL-HV-D1-001 Pnom 60.0 kW ac

PVsyst TRIAL
User's needs Unlimited load (grid)

Loss diagram over the whole year

1375 kWh/m² Horizontal global irradiation


+1.5% Global incident in coll. plane

-2.70% IAM factor on global

1357 kWh/m² * 332 m² coll. Effective irradiation on collectors

efficiency at STC = 20.24% PV conversion

PVsyst TRIAL
91.3 MWh Array nominal energy (at STC effic.)
-0.43% PV loss due to irradiance level

-8.06% PV loss due to temperature

+0.50% Module quality loss

-1.10% Mismatch loss, modules and strings


-0.86% Ohmic wiring loss
82.4 MWh Array virtual energy at MPP

-1.21% Inverter Loss during operation (efficiency)


0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold

PVsyst TRIAL
0.00% Inverter Loss due to voltage threshold
-0.01% Night consumption
81.4 MWh Available Energy at Inverter Output
81.4 MWh Energy injected into grid

PVsyst TRIAL
PVsyst Evaluation mode