Sunteți pe pagina 1din 1

PLOT LIMIT

21.348M

22.474M

20.771M

SE
TB
AC 22.313M
K 55
00M
M

21.10M
21.458M 22.474M

22.149M
INTERLOCK PAVING
SRI >29

LOADING AND UNLOAD AREA

SETBACK 5500MM
22.313M

21.379M

21.986M

22.149M

SLOPE 1:10
RAMP UP
21.392M
22.474M UP
21.572M
21.823M
22.448M

COVERED PLATFORM
+ 23.648M LVL

21.359M
PLOT LIMIT

TELE

TE
RM

GA

L
E

VE
WID

LE
9M

TE
GA
GUARD
OPEN OFFICE ROOM
450.00 SQM
+ 22.123M LVL

TE

L
VE
GA

LE
22.474M

E
21.774M

WID

TE
GA
6M
+23.648M LVL + 23.648M LVL 21.823M

21.36M

WORKERS FACILITY
219.15 SQM
+ 22.123M LVL

21.442M

L.V ROOM
+ 0.15M LVL
PUMP RM

22.474M SETBACK 5500MM 22.313M 22.149M


SUB
21.986M
STATION
+ 0.15M LVL

21.435M 21.353M 21.472M 21.63M 21.489M 21.530M

PLOT LIMIT PLOT LIMIT

KEY PLAN
LEGEND :

DESCRIPTION SYMBOL

UNDER GROUND HDPE PIPES


SPRINKLER PIPE - MAIN HEADER
SPRINKLER PIPE - BRANCH LINE
WET RISER PIPE
UPRIGHT SPRINKLER HEAD
ZONE - 1 ZONE - 2
RECESSED PENDENT SPRINKLER HEAD
AREA = 2740 SQ.MTR. AREA = 1373 SQ.MTR.
ZONE CONTROL VALVE
ASSEMBLY (ZCV)
1) BUTTERFLY VALVE WITH
SUPERVISORY SWITCH ZCV
2) FLOW SWITCH -
3) TEST AND DRAIN VALVE
ALARM CHECK VALVE
FH 6 KGS. DCP FIRE EXTINGUISHER
5 KGS. CO2 FIRE EXTINGUISHER
4-WAY BREECHING INLET
NON RETURN VALVE / CHECK VALVE

FIRE HYDRANT WITH NRS GATE VALVE FH

SURFACE TYPE FIRE HOSE CABINET


( SURFACE MOUNTED )
1"x30 m LONG AUTO. FIRE HOSE REEL FHC
1" LOCK SHIELD VALVE
1" PRESSURE REDUCING VALVE

RECESSED TYPE FIRE HOSE REEL


CABINET

1" LOCK SHIELD VALVE FHR


1" PRESSURE RELEASE VALVE

FOR APPROVAL

00 ISSUED FOR APPROVAL PRG KD 06.12.15


REV DESCRIPTION DWN CHK'D DATE
GENERAL NOTES : PROJECT :
1) All dimensions are in mm, unless otherwise specified. PROPOSED WAREHOUSE AND OFFICE AREA
2) Fire sprinkler system design as per UAE Fire & Life Safety Code (2011 Edition). ON PLOT NO. TP030603
3)
4)
Wet Riser system design as per UAE Fire & Life Safety Code (2011 Edition).
Fire Pumps design as per UAE Fire & Life Safety Code (2011 Edition).
FIRE FIGHTING SYSTEM DRAWINGS REFERENCE : AT TECHNO PARK, DUBAI
5) Drain pipe shall be terminated to nearest drain point. SR. DRAWING TITLE DRAWING NO. REV. CLIENT :
6) For maximum distance between pipe supports for Sch. 40 pipes as per 01 DESIGN BASIS CEN-590XX-FF-00 00
NFPA 13 (Edition 2013) refer table no. 9.2.2.1 02 SITE SETTING OUT PLAN CEN-590XX-FF-01 00
SKYWAY INTERNATIONAL INDUSTRIES FZE
25 32 40 50 65 80 100 150 200 WAREHOUSE GROUND FLOOR PLAN
03 CEN-590XX-FF-02 00 CONSULTANT :
SPRINKLER LAYOUT
Max. Distance (m) 3.66 3.66 4.57 4.57 4.57 4.57 4.57 4.57 4.57 04
WAREHOUSE GROUND FLOOR PLAN
CEN-590XX-FF-03 00 ENGiNEERiNG CONSULTANTS
WET RISER LAYOUT
OFFICE GROUND FLOOR PLAN
7) PIPES - 05 CEN-590XX-FF-04 00
SPRINKLER & FIRE HOSE REEL LAYOUT
Above ground pipe shall be Factory Galvanized Steel ERW in Accordance with
06 SECTION DRAWING CEN-590XX-FF-05 00 P O Box 34714
ASTM A53 Grade B or ASTM A795 Grade B, SCH40 or Manufactured as per Dubai, United Arab Emirates

BS1387 Class 'C' Heavy Grade, as per UAE Fire & Life Safety Code (2011 Edition) 07 SCHEMATIC RISER DIAGRAM CEN-590XX-FF-06 00 T - 04 343 8404
F - 04 343 4524
feconsul@eim.ae http://www.freelineeng.ae
Section No. 16.1 08 TYPICAL INSTALLATION DETAILS (2 SHEETS) CEN-590XX-FF-07 00
Under ground HDPE PIPE, SDR9, PE100, PN20. 09 FIRE PUMP ROOM DETAILS CEN-590XX-FF-08 00
DISCIPLINE :
8) FITTINGS - FIRE - PROTECTION
- Threaded type
- Grooved type Drawn by : PRG Chkd.by : KD Appd. by : KD
Scale : NTS Sheet : A1 Date : 06.12.15
Project job No. : C - 590XX Rev. No. : 00
Cad file ref : CEN-590XX-FF-06 Sheet. : 1 OF 1
Drawing Title :
FIRE FIGHTING SYSTEM
SCHEMATIC RISER DIAGRAM

Dwg No. CEN-590XX-FF-06 Rev. 00