H=1.20m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.20
t1 = 0.15 m B1 = 1.00
t2 = 0.15 m B2 = 0.30
H pantalla = 1.20
Hr = 0.20
0.51 t-m
Hz = t2 + 5cm = 20 cm hz = 0.2 m
hm = hp + hz = 1.40 Ht = hm + h' = 1.995 m
B2 = 0.30 m
Mínimo B2 = hz = 0.2
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 2.8664 / 1.45 x ( 1 +- 6 x 0.17 / 1.45 ) (+) 3.37 Tn/m2 ( Talón )
(-) 0.59 Tn/m2 (Punta)
hc = 0.011
Lc = 0.11 m
Lc = hc + d usar Lc = 0.6 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 15 = 2.7 cm2 / m
2/3 As 1/3As
1.8 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 5.3 x 0.3 ^2 / 2 = 0.2385 tn-m 3.37
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 20 = 3.6 f 1/2" @ 0.15 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
0.59
DISEÑO DE MUROS DE CONCRETO ARMADO
H=1.50m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.20
t1 = 0.15 m B1 = 1.20
t2 = 0.15 m B2 = 0.30
H pantalla = 1.50
Hr = 0.20
0.88 t-m
Hz = t2 + 5cm = 20 cm hz = 0.2 m
hm = hp + hz = 1.70 Ht = hm + h' = 2.295 m
B2 = 0.30 m
Mínimo B2 = hz = 0.2
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 4.0068 / 1.65 x ( 1 +- 6 x 0.19 / 1.65 ) (+) 4.11 Tn/m2 ( Talón )
(-) 0.75 Tn/m2 (Punta)
hc = 0.074
Lc = 0.18 m
Lc = hc + d usar Lc = 0.6 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 15 = 2.7 cm2 / m
2/3 As 1/3As
1.8 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 6.56 x 0.3 ^2 / 2 = 0.2952 tn-m 4.11
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 20 = 3.6 f 3/8" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
0.75
DISEÑO DE MUROS DE CONCRETO ARMADO
H=1.80m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.25
t1 = 0.20 m B1 = 1.25
t2 = 0.20 m B2 = 0.30
H pantalla = 1.80
Hr = 0.20
1.4 t-m
Hz = t2 + 5cm = 25 cm hz = 0.25 m
hm = hp + hz = 2.05 Ht = hm + h' = 2.645 m
B2 = 0.30 m
Mínimo B2 = hz = 0.25
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 5.07 / 1.75 x ( 1 +- 6 x 0.25 / 1.75 ) (+) 5.38 Tn/m2 ( Talón )
(-) 0.41 Tn/m2 (Punta)
hc = 0.136
Lc = 0.29 m
Lc = hc + d usar Lc = 0.6 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 20 = 3.6 cm2 / m
2/3 As 1/3As
2.4 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 8.61 x 0.3 ^2 / 2 = 0.38745 tn-m 5.38
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 25 = 4.5 f 1/2" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
0.41
DISEÑO DE MUROS DE CONCRETO ARMADO
H=2.80m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.40
t1 = 0.30 m B1 = 1.80
t2 = 0.30 m B2 = 0.40
H pantalla = 2.80
Hr = 0.20
4.51 t-m
Hz = t2 + 5cm = 35 cm hz = 0.4 m
hm = hp + hz = 3.20 Ht = hm + h' = 3.795 m
B2 = 0.40 m
Mínimo B2 = hz = 0.4
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
hc = 0.342
Lc = 0.6 m
Lc = hc + d usar Lc = 0.6 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 30 = 5.4 cm2 / m
2/3 As 1/3As
3.6 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 12.74 x 0.4 ^2 / 2 = 1.0192 tn-m 8
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 40 = 7.2 f 1/2" @ 0.15 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
1.05
DISEÑO DE MUROS DE CONCRETO ARMADO
H=3.00m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.40
t1 = 0.30 m B1 = 1.90
t2 = 0.30 m B2 = 0.40
H pantalla = 3.00
Hr = 0.20
5.45 t-m
Hz = t2 + 5cm = 35 cm hz = 0.4 m
hm = hp + hz = 3.40 Ht = hm + h' = 3.995 m
B2 = 0.40 m
Mínimo B2 = hz = 0.4
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 12.5684 / 2.6 x ( 1 +- 6 x 0.34 / 2.6 ) (+) 8.63 Tn/m2 ( Talón )
(-) 1.04 Tn/m2 (Punta)
hc = 0.382
Lc = 0.64 m
Lc = hc + d usar Lc = 0.7 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 30 = 5.4 cm2 / m
2/3 As 1/3As
3.6 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 13.81 x 0.4 ^2 / 2 = 1.1048 tn-m 8.63
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 40 = 7.2 f 1/2" @ 0.15 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
1.04
DISEÑO DE MUROS DE CONCRETO ARMADO
H=3.50m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.40
t1 = 0.30 m B1 = 2.30
t2 = 0.30 m B2 = 0.40
H pantalla = 3.50
Hr = 0.20
8.32 t-m
Hz = t2 + 5cm = 35 cm hz = 0.4 m
hm = hp + hz = 3.90 Ht = hm + h' = 4.495 m
B2 = 0.40 m
Mínimo B2 = hz = 0.4
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
hc = 0.485
Lc = 0.74 m
Lc = hc + d usar Lc = 0.75 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 30 = 5.4 cm2 / m
2/3 As 1/3As
3.6 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 15.71 x 0.4 ^2 / 2 = 1.2568 tn-m 9.75
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 40 = 7.2 f 1/2" @ 0.15 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
1.59
DISEÑO DE MUROS DE CONCRETO ARMADO
H=3.80m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.40
t1 = 0.30 m B1 = 2.30
t2 = 0.30 m B2 = 0.40
H pantalla = 3.80
Hr = 0.20
10.45 t-m
Hz = t2 + 5cm = 35 cm hz = 0.4 m
hm = hp + hz = 4.20 Ht = hm + h' = 4.795 m
B2 = 0.40 m
Mínimo B2 = hz = 0.4
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
hc = 0.547
Lc = 0.8 m
Lc = hc + d usar Lc = 0.8 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 30 = 5.4 cm2 / m
2/3 As 1/3As
3.6 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 18.14 x 0.4 ^2 / 2 = 1.4512 tn-m 11.18
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 40 = 7.2 f 5/8" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
0.97
DISEÑO DE MUROS DE CONCRETO ARMADO
H=4.00m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.40
t1 = 0.30 m B1 = 2.40
t2 = 0.30 m B2 = 0.40
H pantalla = 4.00
Hr = 0.20
12.05 t-m
Hz = t2 + 5cm = 35 cm hz = 0.4 m
hm = hp + hz = 4.40 Ht = hm + h' = 4.995 m
B2 = 0.40 m
Mínimo B2 = hz = 0.4
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 19.8164 / 3.1 x ( 1 +- 6 x 0.44 / 3.1 ) (+) 11.84 Tn/m2 ( Talón )
(-) 0.95 Tn/m2 (Punta)
hc = 0.589
Lc = 0.84 m
Lc = hc + d usar Lc = 0.9 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 30 = 5.4 cm2 / m
2/3 As 1/3As
3.6 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 19.26 x 0.4 ^2 / 2 = 1.5408 tn-m 11.84
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 40 = 7.2 f 5/8" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
0.95
DISEÑO DE MUROS DE CONCRETO ARMADO
H=4.20m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.40
t1 = 0.30 m B1 = 2.50
t2 = 0.30 m B2 = 0.40
H pantalla = 4.20
Hr = 0.20
13.81 t-m
Hz = t2 + 5cm = 35 cm hz = 0.4 m
hm = hp + hz = 4.60 Ht = hm + h' = 5.195 m
B2 = 0.40 m
Mínimo B2 = hz = 0.4
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 21.4616 / 3.2 x ( 1 +- 6 x 0.47 / 3.2 ) (+) 12.62 Tn/m2 ( Talón )
(-) 0.8 Tn/m2 (Punta)
hc = 0.631
Lc = 0.88 m
Lc = hc + d usar Lc = 0.9 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 30 = 5.4 cm2 / m
2/3 As 1/3As
3.6 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 20.59 x 0.4 ^2 / 2 = 1.6472 tn-m 12.62
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 40 = 7.2 f 5/8" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 m
f 3/8" @ 0.20 cm
f 3/8" @ 0.20 m
0.8
DISEÑO DE MUROS DE CONCRETO ARMADO
H=6.15m
Datos de Suelo
g1 = 1.80 tn/m3 g2 = 1.80
f1 = 32 ° f2 = 32
s suelo = 4.00
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 0.65
t1 = 0.30 m B1 = 3.10
t2 = 0.60 m B2 = 0.70
H pantalla = 6.15
Hr = 0.20
41.58 t-m
Hz = t2 + 5cm = 65 cm hz = 0.65 m
hm = hp + hz = 6.80 Ht = hm + h' = 7.356 m
B2 = 0.70 m
Mínimo B2 = hz = 0.65
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 40.499 / 4.4 x ( 1 +- 6 x 0.61 / 4.4 ) (+) 16.86 Tn/m2 ( Talón )
(-) 1.55 Tn/m2 (Punta)
hc = 1.048
Lc = 1.6 m
Lc = hc + d usar Lc = 1.6 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 30 = 5.4 cm2 / m
2/3 As 1/3As
3.6 f 3/8" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 27.26 x 0.7 ^2 / 2 = 6.6787 tn-m 16.86
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 65 = 11.7 f 5/8" @ 0.15 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 3/8" @ 0.20 m
f 1/2" @ 0.20 m
f 3/8" @ 0.20 m
f 1/2" @ 0.15 cm
f 1/2" @ 0.20 m
1.55
DISEÑO DE MUROS DE CONCRETO ARMADO
H=10.00m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 26 ° f2 = 26
s suelo = 1.42
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 1.40
t1 = 0.50 m B1 = 7.10
t2 = 1.35 m B2 = 1.40
H pantalla = 10.00
Hr = 0.20
202.7 t-m
B2 = 1.40 m
Mínimo B2 = hz = 1.4
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 147.8304 / 9.85 x ( 1 +- 6 x 0.69 / 9.85 ) (+) 21.32 Tn/m2 ( Talón )
(-) 8.7 Tn/m2 (Punta)
hc = 1.827
Lc = 3.13 m
Lc = hc + d usar Lc = 3.2 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 50 = 9 cm2 / m
2/3 As 1/3As
6 f 1/2" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
3 f 1/2" @ 0.20 m
conservadoramente:
Mu = 33.22 x 1.4 ^2 / 2 = 32.5556 tn-m 21.32
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 140 = 25.2 f 1" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 1/2" @ 0.20 m
f 5/8" @ 0.20 m
f 5/8" @ 0.20 m
f 3/4" @ 0.20 cm
f 3/4" @ 0.20 m
8.7
DISEÑO DE MUROS DE CONCRETO ARMADO
H=11.00m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 1.50
t1 = 0.50 m B1 = 7.65
t2 = 1.45 m B2 = 1.50
H pantalla = 11.00
Hr = 0.20
218.95 t-m
B2 = 1.50 m
Mínimo B2 = hz = 1.5
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante de
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 173.76 / 10.6 x ( 1 +- 6 x 0.51 / 10.6 ) (+) 21.12 Tn/m2 ( Talón )
(-) 11.66 Tn/m2 (Punta)
hc = 2.033
Lc = 3.43 m
Lc = hc + d usar Lc = 3.4 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 50 = 9 cm2 / m
2/3 As 1/3As
6 f 1/2" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
3 f 1/2" @ 0.20 m
conservadoramente:
Mu = 32.66 x 1.5 ^2 / 2 = 36.7425 tn-m 21.12
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 150 = 27 f 1" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 1/2" @ 0.20 m
f 5/8" @ 0.20 m
f 5/8" @ 0.20 m
f 3/4" @ 0.20 cm
f 3/4" @ 0.20 m
11.66
DISEÑO DE MUROS DE CONCRETO ARMADO
H=13.50m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 1.80
t1 = 0.50 m B1 = 6.30
t2 = 1.70 m B2 = 1.80
H pantalla = 13.00
Hr = 0.20
357.04 t-m
B2 = 1.80 m
Mínimo B2 = hz = 1.8
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante d
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 170.3788 / 9.8 x ( 1 +- 6 x 1.12 / 9.8 ) (+) 29.31 Tn/m2 ( Talón )
(-) 5.46 Tn/m2 (Punta)
hc = 2.446
Lc = 4.1 m
Lc = hc + d usar Lc = 4.1 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 50 = 9 cm2 / m
2/3 As 1/3As
6 f 1/2" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
3 f 1/2" @ 0.20 m
conservadoramente:
Mu = 45.94 x 1.8 ^2 / 2 = 74.4228 tn-m 29.31
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 180 = 32.4 f 1" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 1/2" @ 0.20 m
f 3/4" @ 0.20 m
f 5/8" @ 0.20 m
f 3/4" @ 0.15 cm
f 3/4" @ 0.20 m
5.46
DISEÑO DE MUROS DE CONCRETO ARMADO
H=13.50m
Datos de Suelo
g1 = 1.70 tn/m3 g2 = 1.70
f1 = 32 ° f2 = 32
s suelo = 1.50
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 1.75
t1 = 0.40 m B1 = 8.50
t2 = 1.70 m B2 = 1.80
H pantalla = 13.50
Hr = 3.80
388.11 t-m
B2 = 1.80 m
Mínimo B2 = hz = 1.75
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante d
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
hc = 2.552
Lc = 4.2 m
Lc = hc + d usar Lc = 4.2 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 40 = 7.2 cm2 / m
2/3 As 1/3As
4.8 f 1/2" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
conservadoramente:
Mu = 64.51 x 1.8 ^2 / 2 = 104.506 tn-m 40.17
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 175 = 31.5 f 1" @ 0.20 m
E MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 1/2" @ 0.20 m
f 3/4" @ 0.20 m
f 5/8" @ 0.20 m
f 3/4" @ 0.15 cm
f 3/4" @ 0.20 m
3.14
DISEÑO DE MUROS DE CONCRETO ARMADO
H=15.00m
Datos de Suelo
g1 = 1.68 tn/m3 g2 = 1.68
f1 = 31.1 ° f2 = 31.1
s suelo = 1.80
Pz = m profundidad de zapata
Hs= m altura de suelo
Datos de muro
hz = 2.40
t1 = 0.50 m B1 = 7.50
t2 = 2.30 m B2 = 2.40
H pantalla = 15.00
Hr = 0.20
543.57 t-m
B2 = 2.40 m
Mínimo B2 = hz = 2.4
* Para evitar la inclinación del muro por asentamiento diferencial de la cimentación, es deseable que la resultante d
las presiones en el suelo actúe en el nucleo central de la superficie resistente.
q talón punta = 239.2664 / 12.2 x ( 1 +- 6 x 1.12 / 12.2 ) (+) 30.41 Tn/m2 ( Talón )
(-) 8.81 Tn/m2 (Punta)
hc = 2.858
Lc = 5.11 m
Lc = hc + d usar Lc = 5.2 m
Refuerzo Horizontal As = rt bt d
Arriba: = 0.0018 x 100 x 50 = 9 cm2 / m
2/3 As 1/3As
6 f 1/2" @ 0.20 m
f3/8 1@0.05,15@0.20, Rto.@ 0.30
f1/2 1@0.05,10@0.19, Rto.@ 0.30
3 f 1/2" @ 0.20 m
conservadoramente:
Mu = 46.51 x 2.4 ^2 / 2 = 133.949 tn-m 30.41
t/m
Refuerzo transversal
As temp = 0.0018 x 100 x 240 = 43.2 f 1" @ 0.20 m
MUROS DE CONCRETO ARMADO
Datos de Suelo
tn/m3
°
kg/cm2
Datos de muro
m
m
m
m
m
tn/m3
………. (1)
Brazo Momento
Tn-m
f 1/2" @ 0.20 m
f 3/4" @ 0.15 m
f 5/8" @ 0.20 m
f 1" @ 0.175 cm
f 3/4" @ 0.20 m
8.81