Documente Academic
Documente Profesional
Documente Cultură
Product Announcement
Fire
PA-FCP-013 April 2,2019
FleXNet
Version 12.1.39 Release Document
Now in production.
The V12.1.39 update applies to the FlexNet V12.1.XX Series Product line. The purpose of this update is to provide enhancements and
additional features to the V12.1.XX Series Product line. This document shall outline all enhancements and updates from FlexNet
Software V12.1.9.
This update is not intended for previous product series V11.XX.XX or V10.XX.XX
FleXNet V12.1.39 firmware is compatible with the configuration software MGC Fire Detection and Mass Notification
Configurator V12.1.39.
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Product Announcement
Fire
PA-FCP-013 April 2,2019
MODULES
MIX-M500DMAP(A) DUAL INPUT MONITOR CLIP, 2 ADDRESSES
MIX-M500MAP(A) MONITOR CLIP, AP
MIX-M501MAP(A) MIN-MONITOR CLIP, AP
MIX-M500RAP(A) RELAY CLIP, AP
MIX-M500SAP(A) SUPERVISED CONTROL CLIP, AP
MIX-M502MAP(A) ZONE INTERFACE CLIP, AP (NON-SUB)
MIX-M500FP(A) FIRE PHONE MODULE (NON-AP) CLIP
M500M-4-20 4-20mA MONITOR MODULE (NON-AP) CLIP
M500DMR1(A) TWO INPUT / TWO OUTPUT (NON-AP) CLIP, 4 ADDRESSES
M500X(A) ISOLATOR (NON-AP) N/A
MULTI-MODULES
IM-10(A) MULTI-MONITOR (NON-AP) CLIP w/ 10 ADDRESSES
CR-6(A) MULTI-RELAY (NON-AP) CLIP w/ 6 ADDRESSES
SC-6(A) MULTI-CONTROL (NON-AP) CLIP w/ 6 ADDRESSES
CZ-6(A) MULTI-ZONE INTERFACE (NON-AP) CLIP w/ 6 ADDRESSES
ISO-6 MULTI-ISOLATOR (NON-AP) N/A
* "NON-SUB" DENOTES THAT MUTIPLE PHYSICAL ADDRESSES ARE REQUIRED FOR MULTI-CRITERIA DEVICES/MODULES
(A) ULC
(U) UL
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Product Announcement
Fire
PA-FCP-013 April 2,2019
* "NON-SUB" DENOTES THAT MUTIPLE PHYSICAL ADDRESSES ARE REQUIRED FOR MULTI-CRITERIA DEVICES/MODULES
(A) ULC
(U) UL
(+)The new firmware is also compatible with clip devices
THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO DESCRIBE THE PRODUCTS TECHNICALLY.
For complete and accurate technical information relating to performance, installation, testing and certification, refer to technical literature. This
document contains intellectual property of Mircom. The information is subject to change by Mircom without notice.
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Product Announcement
Fire
PA-FCP-013 April 2,2019
Update Enhancements
Major Enhancements:
➢ Improved Signal Silence Inhibit for Water Flow Alarms (See Signal Silence Operation – refer to page 7 )
➢ S.A. Flag Implementation for Supervisory/Monitor Input Zones (see Addendum A)
➢ Analog Telephone/Paging Bus supervision (see Addendum B)
➢ Updated Ground Fault Reporting (see Addendum C)
➢ Expanded Internal Logic limits (see Addendum D)
➢ Expanded the Advanced Logic Editor to include HOA manual switches and output modules (see Addendum E & F)
Minor Enhancements:
➢ Added disable Waterflow Retard feature
➢ Added water Flow Alarm Zone
➢ Added silence Audible Only feature
➢ Single Trouble Bypass feature
➢ Manual Control switch limit per system increase
➢ AP polling sequence & SLC initialization process
➢ OpenGN control for large campus applications
➢ Addressable Sounder Base internal sync
➢ AP Broadcast Command
➢ Get Job feature
➢ Built-in manufacturer sync protocol
➢ Web Services feature
Additional Documentation:
➢ Signal Silence Operation
➢ Addendum A - S.A. Flag Implementation for Supervisory/Monitor Input Zones
➢ Addendum B - Updated Trouble Reporting for Analog Paging/Telephone Bus Faults
➢ Addendum C - Updated Ground Fault Reporting
➢ Addendum D - Advanced Logic Limitation Increases
➢ Addendum E - Advanced Logic Editor - HOA Manual Switches
➢ Addendum F - Advanced Logic Editor – Output Modules
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Product Announcement
Fire
PA-FCP-013 April 2,2019
As of APRIL 2019, production of the FlexNet product line and components will begin shipping with FlexNet firmware, V12.1.39. This
change is to ensure the most current updates and enhancements are provided to new and existing systems.
Ideally, this update is intended for new system installations where final testing and verification has not yet been completed. For
existing systems, the following recommendations should be considered.
This update is intended for systems currently operating older V12.1.XX FlexNet series software.
This update is intended for systems currently operating with V12.1.9 software (or newer) since the software changes can be properly
assessed and appropriate retesting/verification can be completed in accordance to local governing standards and codes.
This update is not recommended for systems currently operating older FlexNet series software such as v10 and v11.
If you have any questions or concerns, please visit the Mircom Technical Support Forum or contact the Technical Support
Department directly.
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
In previous firmware versions the ‘NS’ Flag had two intended purposes, to prevent the resounding of signals following a subsequent
activation and to make the corresponding zone non-silenceable. To have both subsequent activation and silenceable outputs on
Supervisory and Monitor input zones the implementation of the SA flag (subsequent activation) was necessary.
The V12.1.39 Configuration software will automatically remove the NS Flag & assign the SA Flag to all applicable Monitor and
Supervisory Input zones upon restoral. Though this process is automatic, it is the installer and/or operator’s responsibility to
confirm the correct assignments following the update. For more information please refer to the ‘Signal Silence Operation’ &
Addendums included within this document.
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Activation of the Signal Silence button when the Panel is in Alarm turns on the Signal Silence Indicator and deactivates any Silencable
NACs. Non-Silencable Circuits are unaffected. Signals will re-sound upon any subsequent Alarm. This button does not function during
any configured Signal Silence Inhibit Timer period. It also does not function if the NACs are active as the result of a Fire Drill.
The NS (Non-Silencable) Flag is intended as an inhibitor to the Signal Silence command in accordance to certain jurisdictions
whereby silencing of audible and/or visual notification appliance circuits during a water flow type alarm may not be permitted.
Where driven by the activation of an Input Zone with a defined ‘NS’ Flag, audible and/or visual notification circuits shall continue to
operate following the manual activation of the Signal Silence Switch. Only visual and audible notification circuits driven by Silencable
Input Zones (No NS Flag defined) shall be silenced.
It is advised that the NS Flag not be defined directly to the notification appliance circuit(s).
As a result of the changes to the operation of the NS (Non-Silencable) Flag following a FleXNet V12.1.39 update, the configuration
of the notification appliance circuits (NAC’S) must be programmed in accordance to the applicable signal silence operation
outlined below.
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include any of the following:
Non-verified alarm, verified alarm, water-flow alarm, and general alarm input circuits. Upon receipt of an initial alarm input, the
panel shall cause the following:
• The active alarm input is displayed within the Main Display Alarm Queue
• The internal piezo buzzer sounds steadily
• The Common Alarm Status is active
• The on-board Common Alarm Relay is closed (Active)
• Audible and/or Visual signals associated with the input are activated at the evacuation rate
While in alarm, and the 1-minute signal silence inhibit has expired (where applicable), pressing the Signal Silence Switch will cause
the following events to occur (Basic Signal Silence Operation):
Where Modified Signal Silence operation is required, activation of an alarm input shall operate in a similar manner as described
following the receipt of an initial alarm.
While in alarm, and the 1-minute signal silence inhibit has expired (where applicable), pressing the Signal Silence Switch will cause
the following events to occur (Modified Signal Silence Operation):
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Where Non-Silencable Water Flow operation is required, activation of a water flow alarm input shall operate in a similar manner as
described following the receipt of an initial alarm.
During an active water flow alarm, pressing the Signal Silence Switch will cause the following events to occur (Non-Silencable Water
Flow operation):
Where Modified Non-Silencable Water Flow Operation is required, activation of a water flow alarm or any alarm input shall operate
in a similar manner as described following the receipt of an initial alarm.
During an active alarm classified as a non-water flow, pressing the Signal Silence Switch will cause the following events to occur
(Modified Non-Silencable Water Flow Operation):
If water flow alarm receipt is received, pressing the Signal Silence Switch will cause the following events to occur (Non-Silencable
Water Flow operation):
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
In a two-stage system, all alarm inputs are treated in a similar manner. Alarm inputs include any of the following:
Non-verified alarm, verified alarm, water-flow alarm, and general alarm input circuits. Upon receipt of an initial alarm input, the
panel shall cause the following:
• The active alarm input is displayed within the Main Display Alarm Queue
• The internal piezo buzzer sounds steadily
• The Common Alarm Status is active
• The on-board Common Alarm Relay is closed (Active)
• Audible and/or Visual signals associated with the input are activated at the alert rate (unless specified with the GA flag)
• Auto GA timer becomes active (if required)
• Auto signal silence (if required)
All four signal silence operation in a two-stage system shall operate as described in the single stage operation
in regards to the Silencing and Subsequent alarm of Audible and/or Visual signals, unless otherwise specified
in the configuration.
10
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Signal Silence 9
Operation
Programming
&
Configuration
11
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
A Basic Signal Silence Operation is considered to be any system whereby activation of the Signal Silence switch following receipt of
an alarm is uninhibited.
To configure Basic Signal Silence Operation, driven by the FleXNet On-Board notification appliance circuits (NAC’S), ensure the
following:
• Do not define the NS flag (F1) to any of the FleXNet on board (NAC’S)
• Do not define the NS flag (F1) flag to any of the alarm zone
To configure Basic Signal Silence Operation driven by the INX-10A, ensure the following:
• Do not correlate the signal silence status to the designated internal signal silence relay output module of the INX-10A
Power Supply panel
• Do not define the NS flag (F1) to any of the designated internal Supervised Output module (NAC’S) of the INX-10A Power
Supply panel
• Do not define the NS flag (F1) to any of the alarm zone
12
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
A Modified Signal Silence Operation is considered to be any system whereby activation of the Signal Silence switch following receipt
of an alarm is partially inhibited whereas the Audible are inhibited and the Visual signal remain uninhibited.
A new check box, “Silence NAC Audible Only” has been added to the job details page. With this checkbox
enabled all Alarm, Supervisory Trouble, Monitor zones with the “NS” flag defined will only silence audibles signals
when signal silence is activated.
NB: NFPA 72 (2019) 10.12.2 “When a fire alarm notification deactivation means is actuated, both audible and visible
notification appliances shall be simultaneously deactivated” unless otherwise specified by Authority Having
Jurisdiction (AHJ).
To configure Modified Signal Silence Operation, driven by the FleXNet On-Board notification appliance circuits (NAC’S), ensure the
following:
• Enable the “Silence NAC Audible Only” check box in the job details page
• Define the NS flag (F1) to the alarm zone that requires the Modified Signal Silence operation
• Do not define the NS flag (F1) to any of the FleXNet on board (NAC’S)
To configure Modified Signal Silence Operation driven by the INX-10A, ensure the following:
• Enable the “Silence NAC Audible Only” check box in the job details page
• Correlate the signal silence status to the designated internal signal silence relay output module of the INX-10A Power
Supply panel
• Do not define the NS flag (F1) to any of the designated internal Supervised Output module (NAC’S) of the INX-10A Power
Supply panel
• Define the NS flag (F1) to the alarm zone that requires the Modified Signal Silence operation
13
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Non-Silencable Water Flow Operation is considered to be any system whereby activation of a water flow alarm shall inhibit the
signal silencing of Audible and/or Visual signals.
. A new “Water Flow ” zone type has been added to the configurator. Audible and/or visuals signal driven by the Water Flow
Zone will now be unhindered by the activation of the signal silence switch. This zone was created to accommodate the select
regions specific code requirement’s regarding water flow activation.
A new check box “Disable Water Flow Retard Timer” has also been added to the job details page. With the “disable water
flow retard timer” enabled the built in retard timer for designated water flow devices will be disabled. The purpose of this
checkbox is to accommodate sprinkler systems that already have a built in water flow retard timer.
To configure Non-Silencable Water Flow Alarm Operation, driven by the FleXNet On-Board notification appliance circuits (NAC’S),
ensure the following:
• Add all devices that are required to be Non-Silencable to the new “water flow” zone
• Do not define the NS flag (F1) to any of the FleXNet on board (NAC’S)
To configure Non-Silencable Water Flow Operation driven by the INX-10A, ensure the following:
• Add all devices that are required to be Non-Silencable to the “Water Flow” zone
• Do not correlate the signal silence status to the designated internal signal silence relay output module of the INX-10A
Power Supply panel
• Do not define the NS flag (F1) to any of the designated internal Supervised Output module (NAC’S) of the INX-10A Power
Supply panel
14
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
A Modified Non-Silencable Water Flow Operation is considered to be any system whereby activation of the Signal Silence switch
following receipt of a Non-Water Flow alarm is partially inhibited by which the Audible signals become inactive and the Visual signals
shall remain unimpeded the activation of a water flow alarm shall inhibit the signal silencing of Audible and/or Visual signals.
To configure Modified Non-Silencable Water Flow Operation, driven by the FleXNet On-Board notification appliance circuits (NAC’S),
ensure the following
• Add all devices that are required to be Non-Silencable to the new water flow zone
• Enable the silence to audible only check box in the job details page
• Define the NS flag (F1) to the alarm zone that requires the modified signal silence operation
• Do not define the NS flag (F1) to any of the FleXNet on board (NAC’S)
To configure Modified Non-Silencable Water Flow Operation driven by the INX-10A, ensure the following
• Add all devices that are required to be Non-Silencable to the “water flow zone”
• Enable the ‘Silence Audible Only’ check box in the job details page
• Do not define the NS flag (F1) to any of the designated internal Supervised Output module (NAC’S) of the INX-10A Power
Supply panel
• Define the NS flag (F1) to the alarm zone that requires the modified signal silence operation
• add the following logic statement to internal signal silence relay output module of the INX-10A Power Supply panel “Signal
Silence AND NOT Water Flow Zone: A”
Example (**-**-**-ST-012 AND NOT 01-00-**-IZ-005: A)
15
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Addendum A
S.A. Flag Implementation for Supervisory/Monitor Input Zones
Subsequent activation following or during an active Signal Silence status is only inherent to the Alarm Input Zone. For Applications
where a Supervisory or Monitor Input Zone(s) are used to drive audible and/or visual signaling devices, an ‘SA’ Flag must be defined
to support this operation.
Example,
The SA Flag implementation is intended to support applications whereby Smoke/CO detectors providing local alarms are used in lieu
of Smoke Alarms within dwelling units.
The SA Flag, when defined to a Supervisory or Monitor Input Zone, shall allow the zone to cancel an active Signal Silence status and
resound the notification appliance circuits. Therefore, it is advised that this flag be enabled on any Input Zone of Supervisory or
Monitor type which is used to drive activation of audible and/or visual signaling devices.
The ‘SA’ (Subsequent Activation) Flag is definable via the F5 column to Supervisory & Monitor Input Zones within the MGC Fire
Detection and Mass Notification Configurator v12.1.39, or later.
If upgrading an existing system to v12.1.39 or later, ensure the ‘SA’ (Subsequent Activation) Flag is set to any
Supervisory and/or Monitor zone(s) driving the activation of Audible/Visual Notification appliance circuits
16
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Addendum B
Trouble Reporting for Analog Paging/Telephone Bus Faults
Where analog communication is used for the Telephone/Paging bus, a trouble shall be reported when a fault is present on the
corresponding circuit(s).
In previous Firmware releases, a fault in the corresponding bus would report as:
LCD Display
Info
Where ‘NODE ID’ will display the numerical value assigned to that particular node
V12.1.39 or later shall now report a fault in the corresponding Bus as:
LCD Display
Info
17
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Addendum C
Ground Fault Reporting
When the FleXNet System is subjected to a Ground Fault condition, a trouble shall be reported on the corresponding Node and/or
system. Following v12.1.39, the system will identify the Node and CPU location of the ground fault condition. The system will no
longer identify the polarity of the ground fault.
LCD Display
Info
Where ‘NODE ID’ will display the numerical value assigned to that particular node
LCD Display
Info
Where ‘NODE ID’ will display the numerical value assigned to that particular node and CPU module
The CPU is only identified for ground faults occurring on the ALCN-792MISO board SLCs.
18
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Addendum D
Advanced Logic Limitation Increases
Advanced Logic Equations within The MGC Fire Detection and Mass Notification Configurator have certain internal limitations that
exist per Node, Equation and CPU. These Internal limitations have recently been expanded:
Example,
Equation:
Description:
(Input Zone 1 Active AND Input Zone 2 Active) OR Input Zone 3 Active
Comments:
When Input Zone 1 and Input Zone 2 become active drive signals. OR when Input Zone 3 becomes active drive signals
19
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Addendum E
Advanced Logic Editor - HOA Manual Switches
H.O.A. (Hand-Off-Auto) Manual Switches are definable within The Advanced Logic Editor and listed within the left-hand pane of the
Logic Editor Window under the abbreviation ‘HA’
ND-CPU-**-HA-ADR
Whereby:
ND – The physical address of the Node pertaining to the Fan-Damper Display Module
CPU – The address of the CPU responsible for driving the Fan-Damper Display module
ADR – Switch index number assigned a particular Fan-Damper switch.
The HOA Switch is to be defined within the Advanced Logic Editor by use of the System Define (Sys Def) terms “HOA_ON” and
“HOA_OFF”
Example 1
The logic equation is to be TRUE (Active) when HOA Switch #5 is manually set to the ‘ON’ position.
Example 2
The logic equation is to be TRUE (Active) when HOA Switch #3 is manually set to the ‘ON’ or ‘OFF’ position.
Note: Defining HOA switches as ‘Normally Off’ or ‘Normally On’ will not impact the processing of the logic statement.
20
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Addendum F
Advanced Logic Editor – Output Modules
Output modules are definable within The Advanced Logic Editor and listed within the left-hand pane of the Logic Editor Window
under the abbreviation ‘OU’.
ND-CPU-LP-OU-ADR
Whereby:
ND – The physical address of the Node pertaining to the Output Module
CPU – The designated address of the CPU responsible for driving the Output module
LP – The designated SLC number wired to the output module
ADR – The designated physical address assigned to the output module
The Output Module is to be defined within the Advanced Logic Editor by use of the Device Status Masks Active (:A), Bypass (:B), and
Fault (:F)
Example 1
The logic equation is to be TRUE (Active) when the output module ND-1 CPU-1 LP-2 ADR-M128 is active. (:A)
01-01-02-OU-M128:A
Example 2
The logic equation is to be TRUE (Active) when the output module ND-1 CPU-1 LP-2 ADR-M128 is faulted (i.e. Missing, Wiring Fault
etc.)
01-01-02-OU-M128:F
The Device Status Mask (:F) can be used to create an event when a device goes into a trouble state.
21
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113
Register an account with Mircom.com to access the latest news & software updates
https://mircom.com/technical-support/documents-firmware-software-downloads/
Email: OR Telephone:
TechSupport@mircom.com 1-888-MIRCOM5 (1-888-647-2665)
Mircom strives to offer the highest quality products and services, on occasion an issue may require field action and we regret when
these issues arise. As part of our commitment to quality we incorporate any findings into a continuous improvement process so as
to better serve our customers in the future. As part of our support offering please feel free to contact us with any inquiries or
assistance you may require.
We are always looking for your feedback on our Products and Solutions.
Regards
Lisa Turner
Sr. Product Manager Fire Products
Mircom Group of Companies
25 Interchange Way, Vaughan, Ontario, Canada, L4K 5W3
T: 905.660.4655 ext . 3100 | 1.888.660.4655
E: lturner@mircomgroup.com
22
25 INTERCHANGE WAY, VAUGHAN (TORONTO), ONTARIO, CANADA L4K 5W3 TOLL FREE (888) 660-4655 FAX (888) 660-4113