Install the CompactLogix 5370 L1 Controller Chapter 1

IMPORTANT You must install bumpers on the back of your CompactLogix 5370 L1
controller before mounting it on the EN 50022 - 35 x 15 mm
(1.38 x 0.59 in.) DIN rail.
Bumper Selection:
• For more information on Bumper Selection, see Rockwell
Automation Knowledgebase article #591565, 5370 L16ER/L18ER
recommended Bumpers for use with 1.38 x 0.59 in. DIN rail. You
can access the article at: (Login required)
https://rockwellautomation.custhelp.com/

Minimum Spacing

Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow
50 mm (2 in.) of space on all sides, as shown. This spacing provides ventilation
and electrical isolation.

50 mm
Top (2 in.)

50 mm 50 mm
1734 POINT I/O Module
1734 POINT I/O Module

1734 POINT I/O Module


Supply and I/O Module
CompactLogix 5370 L1

(2 in.) (2 in.)
Embedded Power
Controller with

End Cap
Side Side

Bottom 50 mm
(2 in.)

Rockwell Automation Publication 1769-UM021F-EN-P - April 2015 25