Sunteți pe pagina 1din 7

AN INDUSTRIAL POWER DISTRIBUTION SYSTEM

FEATURING UPS PROPERTIES

B.K. Johnson,Member R.H. Lasseter, Fellow


University of Idaho University of Wisconsin-Madison

Abstract: A high power quality dc power distri- the dc side. The ring bus supplies a number of invert-
bution system for industrial applications is de- ers or dc/dc converters, each supplying separate loads.
scribed. The distribution system incorporates The dc system helps to isolate individual loads from
UPS properties and can supply larger loads than non-linear interactions with neighboring loads, as well
conventional UPS’S. Certain high power appli- as providing isolation from ac system disturbances. The
cations are very sensitive to power quality prob- dc system can also support energy storage in the form
lems. These applications are beyond the power of either battery storage or a superconducting magnetic
capabilities of current UPS systems. Customers energy storage (SMES) coil, each connected via dc/dc
in such a situation would be willing to pay a converters. A back-up generator can be interfaced to
higher premium on the electricity supply to im- the system through an additional rectifier.
prove the quality of the power. The scheme de- This paper starts with a brief discussion of dc power
scribed here has two rectifier terminals supply- distribution systems. This discussion is followed by a
ing a dc ring bus system capable supplying a description of the proposed distribution system config-
large number of parallel inverters. The dc sys- uration. Control aspects of this scheme will also be dis-
tem incorporates energy storage systems to ride cussed. A sample system is introduced followed by the
through an ac system outage until a backup gen- results of computer simulation on this system. This pa-
erator is brought on-line. The scheme described per uses a superconducting distribution system for the
here utilizes superconductors on the dc bus, but simulations shown here but the scheme presented here
the same basic scheme will work with ordinary will soon be extended to systems with normal conduc-
conductors following some modification of the tors as well.
converter control.

DC POWER SYSTEMS
IN TRODU CTI0 N
Direct current systems see limited use as high power,
Many customers supplied by electric utilities have high voltage dc (HVDC) transmission systems. These
loads that are extremely sensitive to the quality of the HVDC systems operate at high voltage, low current
electricity supplied. Voltage dips and sags are especially levels to reduce resistive losses. The systems use line
troublesome. Harmonic distortion and power outages commutated, thyristor based converters, and have fairly
are also major sources of problems. Brief voltage sags simple point to point layouts with a single rectifier and
could result in defective parts for some highly auto- one inverter. More complicated multiterminal systems
mated robotic assembly lines. Such customers would have been considered, but the complexity of a reliable
be willing to pay a higher premium for a high quality control scheme allowing operation without communica-
power supply. Some of these types of loads are presently tion during a disturbance severely limits the number
supplied by uninterruptible power supplies (UPS), but of converters in the system. The advent of high tem-
UPS’S are generally limited to lower power levels, and perature superconductors [l]allows a low voltage, high
are rarely seen used for larger industrial systems. current dc transmission system capable of supporting a
An entire power distribution system with UPS capa- large number of “off the shelf” inverters [2].
bilities is desired. Such a system would supply a vari- Implementing a low voltage dc system with a large
ety of loads, from motors to computers. The scheme number of parallel connected terminals requires solving
described here takes the dc link present in the motor the problem of fast control without reliance on commu-
drives and builds it into a power distribution system. nication. This problem can be solved with a distributed
The dc link is supplied by one or preferably two rec- voltage control scheme based on the concept of voltage
tifiers, each fed by a separate, dedicated ac line. The droop, [3]. The voltage droop scheme uses changes in
added redundancy of two rectifiers helps make the sys- dc voltage as a communication signal in the same way
tem more reliable. The dc system is configured as a ring that frequency variations are used in ac power systems.
bus, with both of the rectifiers connected in parallel on The control scheme is able to react quickly to changes

Q 1993 IEEE
0-7803-1243-0~3$03.00
759

-7- 11
Each lOkW -1.5 MW
in loads and disturbances on the ac and dc systems.
The same concepts used in the low voltage dc
r
(LVDC) transmission system can also be applied to in-
dustrial distribution systems. Some of the limitations
faced by long distance transmission systems disappear,
making this a more appealing application in some cases. Main AC r
The short distances between converters will allow very
fast communication between the converters, making it -
Infeedsl0MW w@ Dc
Ring Bus
easier to extend the control concepts for the supercon-
ducting system for use with normal conductors. The
distribution system will utilize a distributed voltage
control scheme that shares the voltage control respon- 0
sibilities between the energy sources supplying the sys- Back-up
0
tem. The load converters will operate in a power or Generator 0
current control mode. zr
0

-
GENERAL SYSTEM LAYOUT

There are several key features that the distribution


system must possess to be able to provide high quality Battery
T
power to the loads. The system should try to emulate
the desirable features of a UPS. Key features to include Fig. 1: DC Ring Bus System with Parallel Converters
are: isolation from ac supply system voltage fluctua-
tions, limiting non-linear interactions with other loads system through a dc/dc converter. The converter will
and sources on the system, and ride-through capabili- be controlled to keep the storage element charged dur-
ties for ac faults and outages. Disturbances on the dc ing normal operation, and then support the dc voltage
system itself should have minimum impact on the volt- at a minimum level during a disturbance.
age waveforms seen by the loads. The energy storage element can only supply the full
The dc distribution system can meet these needs loads for a short time. It will then be necessary to
given a proper topology and control scheme. The dc start some form of backup generator to supply the loads
system should incorporate a ring bus structure to en- during longer outages of the ac system. The storage
sure a parallel path for power flow. A general system element should be sized to keep the loads in operation
configuration is shown in Figure 1. The dc system is long enough to either provide a graceful shutdown or
supplied by several rectifiers, each connected in parallel allow the backup generator time to start.
on the dc side. One or two of these rectifiers are con- This system takes the dc link normally present in
nected to the ac power system via dedicated lines. The motor drives and many UPS designs and expands it into
dedicated lines help to isolate the dc ring bus from the a complete distribution system. Each load is isolated
affects of other loads on the ac system. Each rectifier from the other loads by its converter and by the dc line
should be supplied by its own line to reduce the in- connected it to the other loads. Some added damping
teractions between the subsystems and to increase the may be necessary to reduce interactions between the
reliability. Two rectifiers, each capable of supplying the voltage source inverters [5]. Increasing the load at one
full system rated load, are preferred. This allows the inverter will depress the local voltage, and will require
system to operate despite the loss of either rectifier. neighboring inverters to also draw energy from their
The system should also have the ability to ride capacitors until the rectifiers respond. This can result
though brief voltage sags on the ac system. A small, in current oscillations between neighboring inverters.
sub-cycle sag can be corrected for by the converter con- Damping can be provided by feeding the derivative of
trols and the energy stored in the passive elements in the capacitor voltage into the phase control loop.
the system. But a longer lasting sag, or an outright
interruption requires the presence of some form of en-
ergy storage on the dc system. Energy storage can be SYSTEM CONTROL
provided either through the use of a storage battery or
by a superconducting magnetic energy storage (SMES) The overall control scheme must coordinate the reg-
coil. Small scale SMES coils for energy backup appli- ulatory actions of each converter on the dc system in
cations are presently available using low temperature concert. The system must be able to respond quickly
superconductors, and development continues on high and cleanly to disturbances on the supply system, dis-
temperature coils [4]. The storage element, whether its turbances on any of the load systems, and problems
a battery or a SMES coil will be interfaced to the dc within the dc mesh itself.

760

I1
a) Three Rectifiers Feeding DC System b) Droop Characteristics

Fig. 2: Example of the D C Droop Scheme f o r a System with Three Rectifiers

Dastributed Voltage Control the rectified ac voltage for a 0' firing angle. The equa-
tions shown assume a controlled three phase rectifier,
The distributed voltage control scheme for the dc sys- with a firing angle a , and a commutating resistance R,.
tem is based on using a change in voltage as a commu- The variable K c represents the controlled slope of the
nication signal. A change in load changes the power droop characteristic. This is varied by changing the fir-
drawn from the dc system, causing an initial decrease ing angle to mimic a sloping characteristic. Equation 2
in the dc voltage when the power is increased. This shows an expression for calculating this firing angle. A
change in voltage normally causes a single rectifier op- central control loop determines the current setpoint of
erating in a voltage control mode to increase or decrease the converter, and computes the expected dc terminal
its current to maintain the proper voltage level. Sev- voltage Vdes.
eral converters connected in parallel can be operated in
a joint voltage control mode, where they distribute the
change in current among themselves. This is based on a
sloping voltage droop characteristic. Figure 2b) shows Vdes -k Rc * Idc
cos(ff) = (2)
the basic characteristic for three three voltage sources vdo
connected in parallel as shown in Figure 2a). The sys-
This basic scheme works well for a superconducting
tem starts out with each rectifier supplying equal cur-
transmission system where there is no steady-state volt-
rents. The load is then decreased, causing the system
age drop between converters. Systems with current de-
to move t o operating point B. The third rectifier then
pendent resistive voltage drops complicate this basic
shuts down, and its load is picked up by the other two
scheme. Knowledge of the system topology and line re-
rectifiers, moving the system to operating point C.
sistances makes it possible to incorporate the line volt-
Each naturally commutated rectifier has a built- age drops into control calculations at each converter, al-
in droop component due to the commutation overlap lowing for compensation. The short distances involved
within the converter. However, this could result in a in dc distribution systems make it possible to use cur-
very shallow droop characteristic, and there may be rent measurements from each converter on the dc sys-
circumstances where it is beneficial to have a steeper tem for control purposes. Therefore the slopes of the
characteristic. droop characteristics can be varied to control current
The current dependent slope of the voltage droop sharing and overcome the affects of line resistances.
characteristic is a controllable quantity. The slope is The rectifier control characteristics can also be ad-
represented by Rc and K , in Equation 2. Where v d o is justed to increase the slope when the converter ap-

761
proaches its current limits. This control action causes vac
the dc terminal voltage to fall more rapidly as the con-
verter nears its limit. The other converters increase
their current share if they have lower droops.
The chopper connecting the storage element to the
dc system will be set to keep the dc voltage within a
preset range. The battery will not supply current to
1
...............
Vmid

the system if the voltage is above this range. The stor-


age element will be charged if needed when the system Idcl
voltage is within normal levels. This converter will still
need a droop component to share load with the main Fig. 3: Inverter Control Characteristics for High and
rectifiers if they are still capable of supplying power to Low Priority Loads. The High Priority Load (on the
the system. Sharing load with rectifiers will extend the left) is also Regenerative
useful operating time of the storage element.
The backup generator will have a steep droop char- plied to the dc system, the voltage droop characteristic
acteristic. It will not supply any current when the main for this converter should have a very small slope on its
rectifiers are in operation. The generator will start if the droop. This will cause the other sources to decrease the
voltage falls causing the storage element to discharge for power they supply to the system. One of the converters
an extended time. The generator, which will be sized shown in Figure 3 demonstrates a regenerative control
to supply the rated system load, will start after a preset characteristic as well.
time. The backup generator will maintain the voltage
at a slightly lower level than the main rectifiers would. STUDY SYSTEM
Therefore, the voltage will rise when the main rectifiers
come back on line. The steep droop characteristic on The dc distribution system concept is demonstrated
the back-up generatorlrectifier will cause its current to for a system incorporating two rectifiers and three in-
go to zero when the main rectifiers are on line. After a verters. The studies presented here utilize a supercon-
time delay to make sure the system is back in a normal ducting dc ring bus to demonstrate the concept. Later
state the generator will shut down. work will utilize normal conductors. The system also
contains a battery connected to the ring bus through a
Control of Loads chopper. The ring bus operates with a nominal voltage
of 750 Vde. Each of the thyristor based, line commu-
The dc system can supply many different types of tated rectifiers is rated at 750 kW and is capable of
loads. But each load will draw a controlled level of supplying the full rated system load. The dc system
power, largely independent of the conditions on the dc supplies three pulse width modulated voltage source
system, unless the dc voltage level falls below the nor- inverters. The initial studies here model the loads as
mal operating range of the converter. Therefore each of impedances, with each load rated at 250 kVA. A backup
the converters can be seen as a power controlled load. generator is also connected to the dc bus through a rec-
The dc system described here will keep the dc voltage tifier. The generator is rated to supply 750 kW and will
level at acceptable levels for the inverters through most startup if the ac infeeds have been off line for a period
possible operating conditions. However there could be of one-half second. The backup generator in an actual
circumstances where the voltage will fall below accept- distribution system would have a longer delay before it
able levels, for example during a dc fault. is started, but a short period was chosen here to sim-
It would be better if only pre-selected converters trip plify the simulations. The system layout is shown in
off-line initially when the dc voltage falls, leaving high Figure 4.
priority converters in operation. This action is useful
if a decrease in load can keep the voltage from falling
below acceptable levels. This can be done by setting SIMULATION RESULTS
the voltage at which a given converter will shut-down.
The distribution system was modeled with a digital
Figure 3 compares the control characteristic for a low
computer simulation to study its response to distur-
priority load to a high priority load. Both converters
bances. These studies demonstrate the ability to supply
operate in a constant power mode until the dc voltage
quality power to loads.
falls below the appropriate Vmin.
This overall control scheme can accommodate regen-
Voltage Dip on A C Infeed
erative loads. The load converter will act as an ad-
ditional voltage source feeding the dc system when it The first case looks at the affect of a distant fault on
enters a regenerative mode. However, since this control the ac system. This fault causes the magnitude of the
mode allows little room for control of the power sup- ac voltage supplying both of the main rectifiers to dip

762
I- 800.0
d

Main AC

mb
600.0

5: DC
5 Ringbus 5 250kVA

t
200.0

Generator 3 250kVA
0.0
0.0
I 0.2 0.4 0.6

4
@ 400.0
(a) DC Voltage Level

Battery

Fig. 4: 750 kVA Sample System

to 80% of the rated values for twelve 60 He cycles. This


voltage sag causes the battery to support the dc volt-
age. Figure 5(a) shows the dc voltage level. The mesh
voltage level falls due to the fall in ac voltage, and then
returns to its initial level following the disturbance. The
key result is shown in Figure 5(b). The magnitude of
the ac voltage only experiences slight variations from
this disturbance. This response could be further en- 300.0 I
0.0 0.2 0.4 0.8
hanced through better converter control. Figure 5(b) Time (Seconds)

shows the load voltage following a transformation to


the synchronous reference frame. The load is regulated Fig. 5: Case 1: AC supply voltage falls t o 0.8 per unit
at 480 Vac. for 12 cycles

A similar disturbance would force an system fed di- Loss of AC Infeed


rectly from the ac lines to shut-down. The storage bat- The final case looks at the loss of both of the ac in-
tery maintains the dc voltage at a level of 712 V during feeds due to an outage on the ac system. The storage
the duration of the voltage sag, and the rectifiers re- battery initially supplies the load, but the back-up gen-
sume normal operation following the disturbance. erator starts after the outage has lasted longer than one-
half second. Figure 7(a) shows the dc voltage response.
The dc voltage has an initial large decrease down to
Large Power Change at an Inverter the level supplied by the battery. The final change in
voltage is due to the startup of the backup generator.
The second case looks at the impact of a large change The generator increases the voltage level slightly. Fig-
in power at one of the inverters. Figure 6 shows a case ure 7(b) shows that the ac voltage magnitude seen by
where the power demanded by one of the inverters is the loads is again largely isolated from the problems on
doubled. Figure 6(a) shows the dc voltage at the in- the ac system.
verter terminal. The dc voltage level experiences a dip The results here examine extreme disturbances. The
when the power is first increased, and then returns to a system provides very good regulation of the load voltage
level slightly below the original steady-state level. This and power during smaller disturbances. The dc distri-
decrease is due to the slope of the droop characteristic. bution system shows its ability to provide load voltage
Figure 6(b) shows the power set-point and the mea- regulation in the face of extreme disturbances. The
sured power. The power control used for the converter same basic concepts demonstrated here can also be im-
has relatively slow response] taking about six cycles to plemented in systems with normal conductors, substan-
reach the desired level. Figure 6(c) shows that the ac tially lower the cost of the installation.
voltage magnitude at the other inverters shows very lit-
tle change as a result of this operation.
763
(a) DC Voltage Level

2.0

n
.=
c
(a) DC Voltage Level
,2
2 1.0

400.0

375.0

0.0
0.0 0.2 0.4
3
(b) Output Power and Power Order at In- 3
verter 1 360.0

400.0

Y
326.0

33 376.0

E
13 300.0 I
0.0 0.2 0.4 0.8 0.8
Time (Seconds)
360.0
s (b) AC Voltage
%
22
8
y 326.0

Fig. 7: Case 9: Complete loss of QC supply system

300.0
0.2 0.4
Time (Seconds)
(c) AC Voltage at Inverter 2

Fig. 6: Case 2: 100% load change at one of the in-


verters

764
CONCLUSION

A dc distribution system capable of supplying high


quality power for commercial and industrial applica-
tions has been introduced. The system utilizes a dc
ring bus supplied by one of more dedicated ac infeeds
to supply multiple converter fed loads. The dc bus is
also connected to an energy storage element and a back-
up generator to provide ability to ride though larger
voltage dips and outages. The dc system exhibits UPS
qualities for each of the loads it supplies. Future work
will look at applying this to ‘non-superconducting sys-
tems,’ and control difficulties that arise with this. More
detailed load and inverter models will also be studied.
Interactions between loads through the converters and
the dc systems must be studied in further detail to im-
prove the control response to changes in system oper-
ating states.

REFERENCES
[I] J.G. Bednorz and K.A. Muller, Possible High T, Super-
conductivity in the Ba-La-Cu-0 System. Zeits. Physik,
B64, 189, 1986.
[a] B.K. Johnson, R.H. Lasseter and R. Adapa, ‘Power
Control Applications on a Superconducting LVDC
Mesh,’ IEEE Transactions on Power Delivery. Vol. 6,
NO. 3, pp. 1282-1288, July 1991.
[3] B.K. Johnson, R.H. Lasseter, F.L. Alvarado, and R.
Adapa, ‘Expandable Multiterminal DC Systems Based
on Voltage Droop,’ Submitted to IEEE PES Society
Winter Power Meeting, February 1993.
[4] Energy Applications of High-Temperature Superconduc-
tors: A Progress Report. EPRI, TR-101635, July, 1992.
[5] J. Holtz, W. Lotzkat, and K-H Werner, ‘A High-Power
Multitransistor-Inverter Uninterruptable Power Sup-
ply System,’ IEEE Transactions on Power Electronics.
Vol. 3, NO. 3, pp. 278-285, July 1988.
[6] W. McMurray, Feasibility of Gate- Turnoff Thyristors
in a High- Voltage Direct Current Transmission System.
EPRI Report EL-5332, Project 2443-5 Final Report,
August 1987.
[7] D.W. Novotny, Equivalent Circuit Steady State Anal-
ysis of Inverter Driven Electric Machines. WEMPEC
Tutorial Report 81-6. 1981.

765

S-ar putea să vă placă și