Sunteți pe pagina 1din 1

1756-IF16 (Single Ended Voltage) with 1492-AIFM16-F-3

1756-IF16
1492-AIFM16-F-3 1492-ACABLE 1 UA TC-IAH161
3-Wire Transmitter 1492-HWACAB 1 UA
0 B2 3 Red 2
IN-0
Transmitter 1 B3 2 Brown 4
IN-1
2 B4 1 Black 6
IN-2
3 B5 14 White 8
IN-3
4 B6 15 White/Black 12
IN-4
5 B7 16 White/Brown 14
IN-5
6 B8 17 White/Red 16
IN-6
7 B9 18 White/Orange 18
IN-7
4 4 Orange 10
RTN
6 Yellow 9
RTN
RTN B18 8 Green 27 6
RTN
10 Blue 28
RTN
19

8 B10 12 Violet 20
IN-8
9 B11 13 Gray 22
IN-9
10 B12 25 White/Black/Brown 24
IN-10
11 B13 24 White/Gray 26
IN-11
12 B14 23 White/Violet 30
IN-12
13 B15 22 White/Blue 32
IN-13
14 B16 20 White/Yellow 34
IN-14
15 B17 21 White/Green 36
IN-15
- + +V B1
Power Supply +V0F C1

+V1F C2 2
+V2F C3

+V3F C4
+V4F C5

+V5F C6
+V6F C7

+V7F C8
+V8F C9

+V9F C10
+V10F C11

+V11F C12
+V12F C13

+V13F C14
+V14F C15

+V15F C16
SHIELD A1 SH
5
SHIELD A2
1 Cables are available in 0.5m, 1.0m, 2.5m, and 5.0m
standard lengths (005=0.5m, 010=1.0m, 025=2.5m, SHIELD A17
050=5.0m). Custom length cables are also available. SHIELD A18
2 LED provides blown fuse indication. When the
fuse is blown the leakage current through the LED is 3
2mA nominal. One analog power source must be
used with this module combination as the fuses are
commoned on the AIFM.
3 Terminals starting with A are the lower row of
terminals, B terminals are the middle row, C
terminals are the upper row.
4 Function of DIP switch required by some PLC
analog modules to short unused channels to
common when closed. Factory Position: Open.
(Refer to your PLC manual for details).
5 Follow your PLC Analog User Manual for proper
shield grounding instructions.
6 RTN terminals are internally connected on the
1756-IF16.

41170-163 (3)