Documente Academic
Documente Profesional
Documente Cultură
The content of this Instruction Book is provided for informational use only and is subject to change
without notice. Beckwith Electric Co., Inc. has approved only the English version of this document.
SYNCHRONIZING
Standard Features
Automatic Transfer: The digital Motor Bus Transfer Manual Transfer: When a Manual Transfer is initiated
System (MBTS) provides the following Automatic the digital MBTS provides the following:
Transfer logic and features: • Sync check functions with adjustable
• Transfer initiated by protective relay external parameters
to the MBTS • Hot Parallel Transfer if enabled (make-before-
• Automatic Transfer after a loss of the motor bus break)
supply voltage based on the programmable • Fast Transfer, In-Phase Transfer and Residual
undervoltage element. This provides a Voltage Transfer (if the Hot Parallel Transfer is
selectable backup feature if a protective relay disabled)
transfer is not initiated.
• Programmable load shedding prior to initiating
• Fast Transfer with adjustable phase angle limit, Residual Voltage Transfer
delta voltage limit and delta frequency limit
• Verify the new source (the source to which the
• In-Phase Transfer at the first phase coincidence bus is being transferred) is healthy and within
if Fast Transfer is not possible. acceptable upper and lower voltage limits
• Residual Voltage Transfer at an adjustable
low residual voltage limit if Fast Transfer is not
Circuit Breaker Control: The digital Motor Bus
possible
Transfer System includes the following Circuit Breaker
• Fixed Time Transfer after an adjustable time Control features:
delay
• Control of two circuit breakers with two
• Programmable load shedding prior to initiating individual programmable breaker closing times
In‑Phase Residual Voltage Transfer and Fixed
• Three-breaker configuration can be provided
Time Transfer
by two M‑4172 devices
• Verify the new source (the source to which the
• Breaker status supervision
bus is being transferred) is healthy and within
acceptable upper and lower voltage limits • Breaker failure monitoring
–2–
M‑4172 Digital Motor Bus Transfer System – Specification
–3–
M‑4172 Digital Motor Bus Transfer System – Specification
The M‑4172 Digital Motor Bus Transfer System provides Automatic and Manual Transfers. The Fast Transfer,
In-Phase Transfer, and Residual Voltage Transfer methods are activated at the same time, if enabled. If the
conditions for the Fast Transfer are not met, then the In-Phase Transfer or the Residual Voltage Transfer will be
attempted. The Fixed Time Transfer is also provided if during a transfer operation, it is not possible to monitor
the motor bus voltage (due to Bus VT fuse loss, for example). The Residual Voltage Transfer, and Fixed Time
Transfer methods can be selectively disabled. The Automatic or Manual Transfer operation can be blocked by
control/status input or remote serial communications. See Figure 2 for Typical Application of Motor Bus Transfer
Systems and Figure 3 for Open Transition Transfer methods.
Automatic Transfer
Automatic Transfer can be initiated by an external protection trip signal (86P) or an external undervoltage function
(27) using control/status input to the Motor Bus Transfer System (MBTS) device or triggered by a sudden loss
of motor bus supply voltage using the internal bus undervoltage relay (27B Function). Automatic Transfer allows
transfer operation in both directions: from Source 1 to Source 2, and vice versa. The Automatic Transfer provides
Fast Transfer, In-Phase Transfer, Residual Voltage Transfer and Fixed Time Transfer. The Automatic Transfer is
blocked when any lockout/blocking condition occurs. The MBTS will not respond to any transfer command and
will not send the trip command while in the lockout/blocking condition.
Manual Transfer
Manual transfer can be initiated by using the local Human-Machine Interface (HMI), from a control/status input
or through remote serial communications. The Manual Transfer allows transfer operation in either direction: from
Source 1 to Source 2, and vice versa. Manual Transfer provides Hot Parallel Transfer or a combination of Fast
Transfer, In-Phase Transfer, and Residual Voltage Transfer. The Manual Transfer is blocked when any lockout/
blocking condition occurs. The MBTS will not respond to any transfer command and will not send the trip command
while in the lockout/blocking condition.
Transfer Modes
There are two transfer modes, Sequential and Simultaneous, in the open transition transfer operation.
* NOTE: The 'new source' is defined as the source to which the bus is being transferred.
–4–
M‑4172 Digital Motor Bus Transfer System – Specification
Auto Trip
If an external operation closes the second breaker while leaving the first one closed, and if the Auto Trip feature
is enabled, there is a breaker trip option: the MBTS will trip the breaker that was originally closed or the breaker
that has just been closed within an adjustable time delay (0 to 50 Cycles in increments of 0.5 Cycle) after the
second breaker is closed. This Auto Trip operates to transfer in either direction. The purpose is to allow external
parallel transfer but prohibits inadvertent parallel operation. It must be noted that the external operation that
closed the second breaker must be supervised by means external to the motor bust transfer system.
Auto Close
If an external operation opens the second breaker while leaving the first one open, and if the Auto Close feature
is selected, the MBTS will close the breaker that was originally opened. The originally opened breaker will be
closed using the Fast Transfer, Residual Voltage Transfer or Fixed Time Transfer method depending upon the
bus voltage decayed condition. This Auto Close operates to transfer in either direction. The purpose is to permit
a transfer when the normally-closed breaker is accidentally/inadvertently tripped resulting in two open breakers.
This operation is very similar to the regular transfer process except it does not send out the trip command, since
the second breaker is already opened.
* NOTE: The 'new source' is defined as the source to which the bus is being transferred.
–5–
M‑4172 Digital Motor Bus Transfer System – Specification
Lockout/Blocking
A transfer is blocked when any lockout/blocking condition described below is active:
• Voltage Blocking – If prior to a transfer, the new source* voltage exceeds the Upper or Lower voltage
limits, all transfers are blocked as long as the voltage remains outside these limits.
• External Blocking – When this control input contact is closed, all transfers are blocked.
• Incomplete Transfer Lockout – Blocks any transfer initiated by a protective relay initiate or an automatic
initiated transfer or manual transfer if the last transfer has not been completed within the time delay. A
time delay can be set from 50 to 3000 Cycles. The MBTS remains in the lockout condition until manually
reset.
• Bus VT Fuse Loss Blocking – Transfer is blocked if the Bus VT fuse loss is detected and the customer
has selected to block transfers when this occurs.
• "Both Breakers Same State" Blocking – If both breaker status contacts are in the open state, due to
an external operation that opens the second breaker while leaving the first one open, and if the Auto
Close feature is not selected, no transfer sequence is initiated. Furthermore, any subsequent initiation
of a transfer sequence while the breakers are in this state is inhibited. Also, if both breaker status
contacts are closed due to an external operation that closes the second breaker while leaving the first
one closed, and if the auto trip feature is disabled, no transfer sequence is initiated.
• Transfer in Process Blocking – Once a transfer is in process, any other transfer initiate inputs will be
ignored until the original transfer is complete.
• Blocking After Transfer – After a transfer has been completed, any additional transfers are blocked for
0 to 8160 cycles, as selected by the user.
The Output 8 Lockout/Blocking Output is energized when any Lockout/Blocking condition as mentioned above
is active except Transfer In Process Blocking and Blocking After Transfer.
* NOTE: The 'new source' is defined as the source to which the bus is being transferred.
–6–
M‑4172 Digital Motor Bus Transfer System – Specification
TRANSFER SETTINGS
Setpoint
Ranges Increment Accuracy†
Automatic Transfer
Fast Transfer
Delta Phase Angle Limit* 0.0 to 90.0 Degrees 0.1 Degree ±0.5 Degree
Delta Voltage Limit 0 to 60 V 1 V ±0.5 V or ±2%
Delta Frequency Limit 0.02 to 2.00 Hz 0.01 Hz ±0.01 Hz or 5%
Time Window** 1 to 10 Cycles 0.5 Cycle ±1 Cycle
Closing Command
Time Delay*** 0 to 10 Cycles 0.5 Cycle 1 Cycle
* Accuracy defined at a constant frequency with a delta frequency of zero (0).
** This timer is used to limit the time window during which a Fast Transfer may be initiated.
*** This time delay is only used for Fast Transfer in Simultaneous. The trip and close commands are normally issued
at the same time. This time delay allows the flexibility to delay the closing command to accomplish the break-before-
make mode of operation (open transition).
In-Phase Transfer
†
Select the greater of these accuracy values. Accuracy applies to sinusoidal voltage with constant amplitude and frequency.
–7–
M‑4172 Digital Motor Bus Transfer System – Specification
Manual Transfer
Fast Transfer
Delta Phase Angle Limit* 0.0 to 90.0 Degrees 0.1 Degree ±0.5 Degree
Delta Voltage Limit 0 to 60 V 1 V ±0.5 V or ±2%
Delta Frequency Limit 0.02 to 2.00 Hz 0.01 Hz ±0.01 Hz or ±5%
Time Window** 1 to 10 Cycles 0.5 Cycle ± 1 Cycle
Closing Command
Time Delay*** 0 to 10 Cycles 0.5 Cycle 1 Cycle
* Accuracy defined at a constant frequency with a delta frequency of zero (0).
** This timer is used to limit the time window during which a Fast Transfer may be initiated.
*** This time delay is only used for Fast Transfer in Simultaneous mode. The trip and close commands are normally
issued at the same time. This time delay allows the flexibility to delay the closing command to accomplish the break-
before-make mode of operation (open transition).
In-Phase Transfer
†
Select the greater of these accuracy values. Accuracy applies to sinusoidal voltage with constant amplitude and frequency.
–8–
M‑4172 Digital Motor Bus Transfer System – Specification
Auto Trip
contact closes. The selectable adaptive breaker closing time is also provided.
(2)
An alarm is activated if the actual Breaker Closing Time exceeds the programmed closing time by ± this value.
Incomplete Transfer
Lockout Time(3) 50 to 3000 Cycles 1 Cycle ±1 Cycle or ±1%
Local Manual Transfer
Initiate Time Delay(4) 0 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Remote Manual Transfer
Initiate Time Delay(6) 0 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Blocking After
Transfer Time(5) 0 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Trip Command
Pulse Length 15 to 30 Cycles 1 Cycle ±1 Cycle
Close Command
Pulse Length 15 to 30 Cycles 1 Cycle ±1 Cycle
This timer is used for situations where the transfer was not completed. Response to a breaker failure is
(3)
Com1 port.
(5)
This timer is used to block any additional transfer after a transfer has been completed.
This time delay is only applicable when manual transfer is initiated from the Control/Status input, Com2 Port,
(6)
†
Select the greater of these accuracy values. Accuracy applies to sinusoidal voltage with constant amplitude and frequency.
–9–
M‑4172 Digital Motor Bus Transfer System – Specification
FUNCTIONS
Setpoint
Ranges Increment Accuracy†
†
Select the greater of these accuracy values. Accuracy applies to sinusoidal voltage with constant amplitude and frequency.
Values in parentheses apply to 1 A CT secondary rating.
–10–
M‑4172 Digital Motor Bus Transfer System – Specification
FUNCTIONS (Cont.)
Setpoint
Ranges Increment Accuracy†
81 Bus Frequency
Pickup #1, #2 0.10 to 20.00 Hz/Sec. 0.01 Hz/Sec. ±0.05 Hz/Sec. or ±5%
81R Time Delay #1, #2 3 to 8160 Cycles 1 Cycle +20 Cycles
Negative Sequence
Voltage Inhibit 0 to 99% 1% ±0.5%
Increasing ROCOF Enable/Disable
The 81R #1 Function can be used to initiate Load Shedding. 81R function can only be used when the bus voltage
input is three-phase, and for load shedding.
If the bus VT fuse-loss is detected, the user must either select block transfer or initiate the Fixed Time Transfer.
Bus VT fuse-loss output is initiated from internally generated logic.
ISSLogic®
ISSLogic uses control/status input status, system status, function status, output contact close signals
ISSL to develop 6 programmable logic schemes.
Time Delay #1-#6 0 to 65500 Cycles 1 Cycle 1 Cycle or 1%
Dropout/Reset Time Delay
#1-#6 0 to 65500 Cycles 1 Cycle 1 Cycle or 1%
†
Select the greater of these accuracy values. Accuracy applies to sinusoidal voltage with constant amplitude and frequency.
–11–
M‑4172 Digital Motor Bus Transfer System – Specification
Metering
The Digital Fast Transfer System provides metering of voltage and current of the Source 1 and Source 2, and
Voltage and Frequency of the Motor Bus.
Metering accuracies are:
Voltage: ±0.5 V or ±0.5%, whichever is greater (from 57 to 63 Hz for 60 Hz models; from 47 to 53 Hz for
50 Hz models)
±1.0 V or ±0.75%, whichever is greater (below 57 Hz or beyond 63 Hz for 60 Hz models; below
47 Hz or beyond 53 Hz for 50 Hz models)
Current: 5 A rating, ±0.1 A or ±3%, whichever is greater
1 A rating, ±0.02 A or ±3%, whichever is greater
Frequency: ±0.02 Hz (from 57 to 63 Hz for 60 Hz models; from 47 to 53 Hz for 50 Hz models)
±0.1 Hz (below 57 Hz or beyond 63 Hz for 60 Hz models; below 47 Hz or beyond 53 Hz for 50
Hz models)
Phase Angle: ±0.5 degree or ±0.5%, whichever is greater
Oscillographic Recorder
The oscillographic recorder provides comprehensive data recording of all monitored waveforms, and status
inputs storing up to 248 cycles of data. The total record length is user-configurable from 1 to 16 partitions. The
number of samples per cycle used to store the data is user selectable. The number of samples per cycle that
can be selected is 16 or 32 (50 or 60 Hz). The number of samples selected effects the length of the data that can
be saved and its resolution. The lower the number of samples, the longer the record length that can be stored
(but at a lower resolution).
The oscillographic recorder is triggered by a designated control/status input (usually a protective relay initiate
input), an automatically initiated signal, a trip output, a manual transfer signal or from serial communications.
When untriggered, the recorder continuously stores waveform data, thereby keeping the most recent data
in memory. When triggered, the recorder stores pre-trigger data, then continues to store data in memory for
a user‑defined, post-trigger delay period. The records may be analyzed using Beckwith Electric ISScom®
Communications and Oscillographic Analysis Software, and are also available in COMTRADE file format.
Depending on transfer type, up to four transfers will be stored. When 16 events are stored, any subsequent
event will cause the oldest event to be lost. Each Transfer Event Log parameter is time stamped with the date
and time in 1 ms increments.
The trigger and complete events are used to define the time frame during which the transfer event log is storing
information. A reset feature is provided to clear this log through the serial communications. The Transfer Event
Log is available for viewing utilizing the M-3871 ISScom Communications Software.
*NOTE: The 'new source' is defined as the source to which the bus is being transferred.
–12–
M‑4172 Digital Motor Bus Transfer System – Specification
Calculations
Current and Voltage Values: The Digital Fast Transfer System uses Discrete Fourier Transform (DFT) and
RMS calculation algorithm on sampled voltage and current signals to extract fundamental amplitude, phase and
frequency for the M‑4172.
Sensing Inputs
Nine Voltage Inputs – Rated for a nominal voltage of 60 Vac to 140 Vac (user configurable) at 60 Hz or 50 Hz.
Will withstand 240 V continuous voltage and 360 V for 10 seconds. Voltage transformer burden is less than 0.2
VA at 120 V. Source voltage may be phase-to ground or phase-to-phase connected. For proper operation of
M‑4172 MBTS, the connections for the Source 1, Source 2 and Bus voltages must match each other. The unit
may have up to three voltage inputs for each of the Source 1, Source 2, and Bus Voltages.
One Source 1 Current Input – Rated for a current (IR) of 5.0 A or 1.0 A (optional) at 60 Hz or 50 Hz. Will withstand
4 IR continuous current and 100 IR for 1 second. Current transformer burden is less than 0.5 VA at 5 A (5 A
option), or 0.3 VA at 1 A (1 A option).
One Source 2 Current Input – Rated for a current (IR) of 5.0 A or 1.0 A (optional) at 60 Hz or 50 Hz. Will withstand
4 IR continuous current and 100 IR for 1 second. Current transformer burden is less than 0.5 VA at 5 A (5 A
option), or 0.3 VA at 1 A (1 A option).
Control/Status Inputs
To provide proper operation and breaker status LED indication on the front panel, the 52a or 52b breaker contacts
must be connected to inputs 1 and 4. The default programming of INPUT1 is S1 52a. The default programming of
INPUT4 is S2 52a. The remaining inputs are left unprogrammed and can be programmed to initiate the transfer
or block the transfer operation, trigger the Oscillograph recorder, or to operate one or more outputs.
The four inputs, INPUT2, INPUT3, INPUT5 and INPUT6 are fully programmable to any of the following functions:
• None • 86P-S2 Initiate (S2 to S1) • Transfer Block #3
• S1 52 SP (service position) • 27-S1 Initiate (S1 to S2) • External Status Reset
• S2 52 SP (service position) • 27-S2 Initiate (S2 to S1) • Manual Transfer Initiate
• Automatic Transfer Block • Transfer Block #1 • Manual Transfer Block
• 86P-S1 Initiate (S1 to S2) • Transfer Block #2
The control/status inputs are designed to be connected to dry contacts and are internally wetted with a 24 Vdc
power supply. The minimum current value to initiate/pickup an input is ≥ 25 mA.
Output Contacts
Output contacts OUTPUT1 through OUTPUT4 are available to Trip and Close the Source 1 and Source 2 breakers
and are closed for a defined pulse length (pulse length can be programmed from 15 to 30 Cycles). The power
supply alarm output contact (form 'b') and the self-test alarm output contact (form 'c'), and one output contact
for lockout or blocking status (form 'c'). These outputs are predefined.
The three programmable output contacts OUTPUT5 through OUTPUT7 (two form 'a' and one form 'c'), the Lockout/
Block alarm output contact OUTPUT8 (form 'c'), the power supply alarm output contact (form 'b') and the self-test
alarm output contact (form 'c'), are all rated as per IEEE C37.90 (see Tests and Standards section for details).
Any of the MBTS functions can be individually programmed to activate any one or more of the programmable
output contacts (Outputs 5 to 7). Any output contact can also be selected as pulsed or latched. ISSLogic can
also be used to activate an output contact.
–13–
M‑4172 Digital Motor Bus Transfer System – Specification
Communication
Communication ports include rear RS-232 and RS-485 ports, a front RS-232 port, a rear IRIG-B port, and
an Ethernet port (optional). The communications protocol implements serial, byte-oriented, asynchronous
communication, providing the following functions when used with the Windows®-compatible M-3871 ISScom®
Communications and Oscillographic Analysis Software. MODBUS protocol is supported, providing:
• Interrogation and modification of setpoints and configuration
• Time-stamped status information for the 4 most recent Transfer Event logs
• Time-stamped status information for the 512 most recent events in the Sequence of Events log
• Real-time metering of all measured quantities, control status inputs, and outputs
• Downloading of recorded oscillographic data and Sequence of Events recorder data
• Initiate manual transfer and Sequence of Events recorder
*NOTE: The 'new source' is defined as the source to which the bus is being transferred.
–14–
M‑4172 Digital Motor Bus Transfer System – Specification
The M‑3871 ISScom Communications and Oscillographic Analysis Software enables the plotting and printing
of M‑4172 waveform data downloaded from the unit to any Windows® compatible computer. The ISScom
Communications and Oscillograph Analysis Software can also be used to analyze the operation of the system,
determine timing of the trip and close commands, breaker times and to evaluate "bus ringdown" test data.
The evaluation of "bus ringdown" data eliminates the requirement for separate recording equipment during
commissioning.
IRIG-B
The M‑4172 accepts either modulated (B‑122) using the BNC Port, or demodulated (B‑002) using the RS-232
Port, IRIG-B time clock synchronization signals. The IRIG-B time synchronization information is used to correct
the local calendar/clock and provide greater system wide synchronization for status and oscillograph time tagging.
HMI Module
Local access to the M‑4172 is provided through the M-3931 Human-Machine Interface (HMI) Module, allowing
for easy-to-use, menu-driven access to all functions using a 6-pushbutton keyboard and a 2-line by 24 character
alphanumeric display. The M-3931 module includes the following features:
• User-definable access codes providing three levels of security
• Real-time metering of all measured quantities, control status inputs, and outputs
• Initiate Manual Transfer
• Remote/Local control
• Device On/Off control
Status Module
An M-3976 Status Module provides 24 status and 8 output LEDs. Appropriate status LEDs illuminate when the
corresponding M‑4172 conditions, event or function activates. The status indicators can be reset with the STATUS
RESET pushbutton if the activated conditions have been removed. The OUTPUT LEDs indicate the status of
the programmable output contacts.
ISSLogic®
This feature can be programmed utilizing the M-3871 ISScom Communications Software. ISScom takes the
control/status input status, system status and function status, and by employing (OR, AND, NOR and NAND)
boolean logic and timers, can activate an output, change active setting profiles, initiate transfer, or block transfer.
There are six ISSLogic Functions. The ISSLogic Function Diagram is illustrated in Figure 1.
–15–
M‑4172 Digital Motor Bus Transfer System – Specification
Voltage Withstand
Dielectric Withstand
IEC 60255-5 2,000 Vac / 3,500 Vdc for 1 minute applied to each independent circuit to earth
2,000 Vac / 3,500 Vdc for 1 minute applied between each independent circuit
1,500 Vdc for 1 minute applied to IRIG-B circuit to earth
1,500 Vdc for 1 minute applied between IRIG-B to each independent circuit
1,500 Vdc for 1 minute applied between RS-485 to each independent circuit
Impulse Voltage
IEC 60255-5 5,000 V pk, +/- polarity applied to each independent circuit to earth
5,000 V pk, +/- polarity applied between each independent circuit
1.2 by 50 µs, 500 ohms impedance, three surges at 1 every 5 seconds
Insulation Resistance
IEC 60255-5 > 100 Megaohms
Electrical Environment
Emissions
EN 55022 Class A Limits
Conducted Emissions 150 kHz-30 MHz
Radiated Emissions 30 MHz-1000 MHz
–16–
M‑4172 Digital Motor Bus Transfer System – Specification
Radiated Immunity
IEEE C37.90.2 80-1000 Mhz @ 35 V/m
EN 60255-22-3
Conducted Immunity
EN 60255-22-6 10 Vemf 150 kHz-80 MHz
Output Contacts
IEEE C37.90 30 A make for 0.2 seconds at 250 Vdc Resistive
Atmospheric Environment
Temperature
IEC 60068-2-1 Cold, -20° C (-4° F) Operating
IEC 60068-2-2 Dry Heat, +70° C (+158° F) Operating
IEC 60068-2-78 Damp Heat, +40° C @ 95%RH Operating
IEC 60068-2-30 Damp High Heat Condensation Cycles +25° C, +55° C (131° F) @ 95%RH Operating
Mechanical Environment
Vibration
IEC 60255-21-1 Vibration response Class 1, 0.5 g
Vibration endurance Class 1, 1.0 g
IEC 60255-21-2 Shock Response Class 1, 5.0 g
Shock Withstand Class 1, 15.0 g
Bump Response Class 1, 10.0 g
Compliance
cULus-Listed per 508 – Industrial Control Equipment
– Industrial Control Equipment Certified for Canada CAN/CSA C22.2 No. 14-M91
cULus-Listed Component per 508A Table SA1.1 Industrial Control Panels
European Safety - EN 61010-1:2001, CAT II, Pollution Degree 2
Physical
Size: 19.00" wide x 5.21" high x 10.20" deep (48.3 cm x 13.2 cm x 25.9 cm)
Mounting: The unit is a standard 19", semi flush, 3-unit high, rack-mount panel design, conforming to ANSI/
EIA RS-310C and DIN 41494 Part 5 specifications. Optional mounting is available.
Environmental: For flat surface mounting on a Type 1 enclosure, UL rated to 70°C surrounding air ambient.
Approximate Weight: 17 lbs (7.7 kg)
Approximate Shipping Weight: 25 lbs (11.3 kg)
–17–
M‑4172 Digital Motor Bus Transfer System – Specification
External Connections
M‑4172 external connection points are illustrated in Figure 6 & Figure 7, External Connections.
TRADEMARKS
All brand or product names referenced in this document may be trademarks or registered trademarks of their
respective holders.
Specification subject to change without notice. Beckwith Electric Co., Inc. has approved only the English version
of this document.
–18–
ISSLogic Functions
Initiating Outputs This section of ISSLogic
used to activate the desired Output
This section of ISSLogic initiates
the Function Operation
Outputs
Initiating Function
Programmable
function(s) Initiate
(Incl. ISSLogic Selectable And/Or
Transfer
and System
Status) Programmed
Time Delay
Selectable And/Or/Nor/Nand
ISSLogic # N
–19–
Activated
Initiating Inputs
Programmable
Inputs and AUX
Input
Selectable And/Or
Blocking Inputs
This section of ISSLogic is used
to Block the Function Operation
Programmable
Inputs and AUX
Input
Selectable And/Or
Block Via
Communication
Point
M‑4172 Digital Motor Bus Transfer System – Specification
M‑4172 Digital Motor Bus Transfer System – Specification
VT-M VT-SU
VS1 VS2
M-4172
CT-M IS1 VBus IS2 CT-SU
52 N.O. 52
M N.C. SU
VT-B
M M
TWO-BREAKER CONFIGURATION
TWO-BREAKER CONFIGURATION
VS1 VS1
VT-S1 VT-S2
IS1 M-4172 M-4172 IS1
IS2 IS2
VBus VS2 VS2 VBus
CT-S1 CT-S2
52 N.C. N.C. 52
S1 S2
VT-B1 VT-B2
BUS-TIE
STATION BUS SYSTEM BUS 1 BUS 2
52T
CT-B1 N.O. CT-B2
M M M M
THREE-BREAKER CONFIGURATION
NOTE: Current Transformers are used for the M‑4172's 50BF Function metering and oscillography, they are
not required for transfer operation.
–20–
M‑4172 Digital Motor Bus Transfer System – Specification
Fast
0 1 pu
Phase (Degrees)
Voltage
Residual and
180
Fixed Time
In-Phase
0 pu
360
Time
Figure 3 Open Transition Transfer Methods
–21–
M‑4172 Digital Motor Bus Transfer System – Specification
–22–
M‑4172 Digital Motor Bus Transfer System – Specification
IN-PHASE TRANSFER
ENABLE
–23–
M‑4172 Digital Motor Bus Transfer System – Specification
–24–
M‑4172 Digital Motor Bus Transfer System – Specification
B EC K W IT H E L ECT R IC C O . INC .
VA
6 19 0 118 t h AV E NO .
L A RG O , F L 3 3 7 7 3
39
VAB S contact can be connected to Input 1 52/S1
O
U
R
and Input 4 52/S2. The M‑4172 must be
40
VB C 1
programmed to agree with the 52a or 52b
VBC E
41 1 2 contact connections respectively.
3
42
-
727- 5 4 4 - 23 26
VC RS 4 8 5
COM 3
VCA 4
3.
+
43
R
6
0 44
IN6
5
terminal must be connected to an earthed
A
ground any time external connections
-
T 1 IN5 6
E 4
D 0
V VA
52/S2
a/b IN4
7 have been made to the unit.
V
O VAB
S IN3 8
L 5 O
T 0 U
A
G
/
6
R IN2 9
NOTE: All relays are shown in the de-
E 45 C
1
0
E 52/S1
a/b IN1 energized state, and without power
Danger! Contact avec les terminaux peut causer un choc electrique
10
H
z 2 &
46
VB 2 applied to the relay.
(
N
O 47
VBC
INPUTS !
M
I
IN
N
A
48
VC RT N 11 NOTE: The self-test relay is energized when
L
49
VCA
the relay has performed all self-tests
(
12
50
P/S
13
successfully.
VA
SELF TEST
VAB 14
51
L B 17
condition occurs. See Lockout/Blocking
54
OL
CO section for details.
VC KC 8 18
OK
VCA U I
55
TN 19
G
1A 56
S
O 20
QQ NOTE: The power supply relay (P/S) is
R
C
U
I S1
U
R
C
7 21
energized when the power supply is
(
MODEL: M-4172
RN
functioning properly.
A 57 E
1
T RO
E E M
5 0 Hz
22
D
(
N S
58 O
T U
I S2 R 23
C
5A 59 E
2
6
6 0 Hz
24
OUT-
60 PUTS
+
25
18- 5 6
85-265 PS 2 5
FIRMWARE: D-0229
61 - 26
62 27
+
18- 5 6
PS 1 4
S E RIA L NO .
85-265 CLOSE
63 - S2
28
29
3
TRIP
30
S2
F3 F1
31
2
PS 2 CLOSE
32
S1
3 A MP,
F4 33
250V, F2
(3A B) 1
TRIP
34
S1
PS 1
–25–
M‑4172 Digital Motor Bus Transfer System – Specification
17.50 ± .12
.00
[44.5 +.30 - .00]
9.97
[25.32]
19.00
[48.26]
18.31 0.35
[46.51] [0.89]
2.25 5.21
M-4172 DIGITAL MOTOR [13.23]
BUS TRANSFER SYSTEM [5.72]
1
2
3
4
5
6
7
8
1.48
[3.76]
0.40 [1.02] X 0.27
NOTE: Dimensions in brackets are in centimeters. [0.68] Slot (4X)
–26–
M‑4172 Digital Motor Bus Transfer System – Specification
5.65
[14.40]
5.59
[14.20] 0.03
Actual [0.076]
2.25 1.67
0.35 [5.72] [4.24] 2.25 1.67
[0.89] [5.72] [4.24]
0.28 [0.71]
Dia. (4X)
STATUS
19.00
[48.26]
OUTPUTS
OUT 1 OUT 3 OUT 5 OUT 7
18.31
OUT 2 OUT 4 OUT 6 OUT 8
[46.51]
17.5
[44.45]
ACTUAL
17.68
[44.91]
EXIT ENTER
STATU S
R ES ET
PS 2 PS 1
B R KR BRK R
O PE N O PE N
S O URC E SO URC E
1 2
BRKR BRK R
C LO S E D C LO S E D
SY S D IA G /
OK T IM E
SY NC
CO M 1
M-4172 M-4205
DIGITAL MOTOR
BUS
FASTTRANSFER SYSTEM
TRANSFER SYSTEM
RR
Integrated Synchronizing Systems
BEECC K W IIT
TH
CO
O.. I NC .
E
ELL EC T R
RIIC
Ma d e in U .S .A .
9.97 10.20
[25.32] [25.91]
19.00
[48.26]
–27–
18.31
[46.51]
0.32
[0.81]
M‑4172 Digital Motor Bus Transfer System – Specification
–28–
[0.71]
NOTE: Dimensions in brackets are in centimeters.
M-4172 (HORIZONTAL)
– This sign warns that the area is connected to a dangerous high voltage, and you
must never touch it.
– This sign means that you should refer to the corresponding section of the operation
manual for important information before proceeding.
TABLE OF CONTENTS
M-4172 Digital Motor Bus Transfer System
Instruction Book
i
M-4172 Instruction Book
ii
Table of Contents
iii
M-4172 Instruction Book
iv
Table of Contents
v
M-4172 Instruction Book
vi
Table of Contents
vii
M-4172 Instruction Book
viii
Table of Contents
ix
M-4172 Instruction Book
x
Table of Contents
xi
M-4172 Instruction Book
xii
Table of Contents
xiii
M-4172 Instruction Book
xv
M-4172 Instruction Book
xvi
Introduction – 1
1 Introduction
1.1 Instruction Book Contents........................................................ 1–1
This instruction book includes six Chapters and Chapter 4: System Setup and Setpoints
nine Appendices. Chapter Four is designed for the person(s)
responsible for the direct setting and configuration
Chapter 1: Introduction of the system. It describes the procedures for
Chapter One summarizes the devices’ capabilities, entering all required data into the MBTS. Included
introduces the instruction book contents and in this chapter are functional and connection
describes the application of an MBTS. diagrams for a typical application for the system;
and describes the configuration process for the
unit (choosing active functions), output contact
Chapter 2: Operation assignment and input blocking designation. It also
Chapter Two provides the necessary instructions illustrates the definition of system quantities and
regarding manual operation of the MBTS. equipment characteristics required by the MBTS,
Manual operation of the MBTS is accomplished and describes the individual function settings.
by utilizing either the unit’s front panel controls
and indicators, which include the M‑3931 Human Chapter 5: Installation
Machine Interface (HMI) and M‑3976 Status Module
or through the M-3871 ISScom® Communications The person or group responsible for the installation of
and Oscillographic Analysis Software. the MTBS will find herein all mechanical information
required for physical installation, equipment ratings,
and all external connections in this chapter. For
Chapter 3: ISScom reference, the Three‑Line Connection Diagram
Chapter 3 provides a description of each element is repeated from Chapter 4, System Setup and
of the M‑3871 ISScom Communications and Setpoints. Further, a commissioning checkout
Oscillographic Analysis Software. The ISScom menu procedure is outlined to check the external CT and
structure and commands are described in detail for VT connections. Additional tests which may be
each feature and function. desirable at the time of installation are described in
Chapter 6, Testing.
1–1
M‑4172 Instruction Book
Chapter 6: Testing
1.2 M‑4172 Motor Bus Transfer
This chapter provides step-by-step test procedures
System
for each function, as well as diagnostic mode and
auto-calibration procedures.
The M‑4172 Motor Bus Transfer System (MBTS) is
a microprocessor-based unit that uses digital signal
Appendix A: Configuration Record Forms processing technology to provide automatic and
This Appendix supplies a set of forms to record manual transfer modes.
and document the settings required for the proper
operation of the MBTS. The available internal functions of the system are
listed in Table 1‑1. The nomenclature follows the
standards of ANSI/IEEE Std. C37.2, Standard
Appendix B: Communications Electric Power Systems Device Function Numbers
This Appendix describes communication port where applicable. The available MBTS Transfer
signals and various topologies and equipment Functions are listed in Table 1-2.
required for remote communication.
Mode Transfer Function
Appendix C: Self‑Test Error Codes AUTO MANUAL
This Appendix lists all the error codes and their X X Fast Transfer
definitions.
X X In-Phase Transfer
Appendix D: Transfer Event Log Sample X X Residual Voltage Transfer
Printout X Fixed Time Transfer
This Appendix provides a sample Transfer Event X Hot Parallel
Log printout.
Table 1-1 M‑4172 Transfer Functions
Appendix E: Sequence of Events Sample
Printout The control/status inputs can be programmed to
This Appendix provides a sample Sequence of block and/or to trigger the oscillograph recorder. Any
Events printout. of the functions or the control/status inputs can be
individually programmed to activate any one or more
Appendix F: Transfer Logic Time Sequence of the programmable outputs, each with a contact.
This Appendix includes the Transfer Logic Time QQ NOTE: See Section 1.3, Application for Transfer
Sequence for each transfer. Function descriptions.
Appendix G: Layup and Storage The M‑3931 Human Machine Interface (HMI)
This Appendix includes the recommended storage Module allows the user to access the following
parameters, periodic surveillance activities and features and functions from the M‑4172 front
layup configuration for the M‑4172 Motor Bus panel using a menu-driven, 2 line by 24 character
Transfer System. alphanumeric display:
Settings
Appendix H: Index
• Enable and Disable Manual Transfer
This Appendix includes the Index for the M-4172
Instruction Book. • Enable and Disable Auto Transfer
• Set MBTS to either Local or Remote
Appendix I: Declaration of Conformity • Enter Comm settings
This Appendix includes the Declaration of • Set Access Codes
Conformity in accordance to ISO/IEC 17050-1:2004. • Set User Control Number
• Set display User Lines 1 and 2
• Set Date/Time
1–2
Introduction – 1
Table 1-2 M‑4172 Device Functions QQ NOTE: COM1, COM2 and COM3 can be
disabled for security purposes from the
The MBTS stores time-tagged transfer information Communications HMI menu. A Level 2
for the four most recent transfers. The M‑3976 Status Access Code is required.
Module LEDs are used to provide a detailed visual
indication of function operation for the most recent The system may be remotely set and interrogated
event. utilizing either a hard-wired RS‑232 serial
connection or modem (COM2 when activated as
The MBTS retains up to 248 cycles of oscillograph RS‑232, or COM3), or when purchased, the ethernet
waveform data. This data can be downloaded connection (RJ45 activated).
and analyzed using the M‑3871 ISScom ®
Communications and Oscillograph Analysis
Software.
The unit is powered from one wide input range
switch mode power supply. There is an option for a
redundant power supply.
The MBTS includes self-test, auto calibration, and
diagnostic capabilities, in addition to IRIG-B time-
sync capability for accurate time-tagging of events.
1–3
M‑4172 Instruction Book
STATUS
27B BUS UNDERVOLTAGE DELTA PHASE ANGLE OK
FAST TRANS OP DELTA VOLTAGE OK
IN-PHASE TRANS OP DELTA FREQUENCY OK
RES V/FIXED– TIME TRANS OP FAST/PARAL TRANS READY
PARAL TRANS/AUTO TRIP OP NEW SOURCE VOLT BLOCK
50BF–1/SOURCE 1 BRKR FAIL BUS VT LOSS BLOCK EXIT ENTER
50BF–2/SOURCE 2 BRKR FAIL INCOMP TRANS BLOCK
81/81R BUS FREQ/ROCOF ALARM OUTPUT BLOCK
TRIP SOURCE 1 BRKR TRIP SOURCE 2 BRKR
CLOSE SOURCE 1 BRKR CLOSE SOURCE 2 BRKR
INPUT 2
INPUT 3
INPUT 5
INPUT 6
Figure 1-2 M‑3931 Human-Machine Interface
(HMI) Module
OUTPUTS
OUT 1 OUT 3 OUT 5 OUT 7
OUT 2 OUT 4 OUT 6 OUT 8
1–4
Introduction – 1
1.3 Application
1–5
M‑4172 Instruction Book
VT-M VT-SU
VS1 VS2
M-4172
CT-M IS1 VBus IS2 CT-SU
52 N.O. 52
M N.C. SU
VT-B
M M
TWO-BREAKER CONFIGURATION
QQ NOTE: Current transformers are used for the M-4172 50BF function, they are not required for transfer
operation.
Figure 1-3 Typical Two Breaker Configuration
TRANSMISSION SYSTEM
GENERATOR STEP-UP
TRANSFORMER
52
52
S2
STARTUP SOURCE
S1
GENERATOR BREAKER
AUXILIARY MOTOR BUS
M M M
1–6
Introduction – 1
Figure 1-5 illustrates a typical industrial plant one- A three phase fault in the Unit Auxiliary Generator
line diagram. This application has two independent Step-up transformer or on the high voltage bus near
sources, with each half of the processing plant the plant may completely deenergize the motor fields
operated by each source. There is normally an and the resultant voltage will be minimal. However,
open tie breaker between the two motor buses. for all other cases a significant voltage will be
In this application two M-4172 MBTS are used. induced on the motor bus. The induced voltage will
Each system controls a source breaker and the have a dynamic amplitude and phase charateristic
tie breaker. Whichever source fails has its breaker that will depend on the inertia of the motor loads
tripped and the tie breaker is closed, this transfers and the field energy stored in the motors.
the motor bus load to the remaining source which
now supplies power to the entire plant. The charactersistics for synchronous and induction
motors are shown in Figure 1-6 and Figure 1-7
In general, the voltage characteristic of a motor bus respectively. Figure 1-6 represents a 6000 hp I.D. fan
during a transfer is governed by the motor loads motor operating at 25% load proior to transfer. This
operating at the time of transfer. The majority of is an example of a characteristic for a large motor
auxiliary system motors are induction motors with driving a high inertia load. The voltage magnitude
few synchronous motors used in isolated cases. requires 42 cycles to drop 50% of it’s initial value and
The types of motors in use will, to a great degree, the angle takes more than 60 cycles to complete a
determine the voltage characteristics of the auxiliary 360 degree rotation. The 960 hp boiler circulating
system buses. When the bus is disconnected from pump motor used for Figure 1-7 data shows a
the source, the motors will maintain a voltage due dramatic variation in characteristics. The voltage
to the energy stored in the motor fields. The intital magnitude drops to 50% within 10 cycles and the
magnitude of the voltage depends on the integrity phase completes a 360 degree rotation in less than
of the power source prior to being disconnected. eight cycles.
VS1 VS1
VT-S1 VT-S2
IS1 M-4172 M-4172 IS1
IS2 IS2
VBus VS2 VS2 VBus
CT-S1 CT-S2
52 N.C. N.C. 52
S1 S2
VT-B1 VT-B2
BUS-TIE
STATION BUS SYSTEM BUS 1 BUS 2
52T
CT-B1 N.O. CT-B2
M M M M
QQ NOTE: Current transformers are used for the M-4172 50BF function, they are not required for transfer
operation.
Figure 1-5 Industrial Processing Plant Bus Transfer One-line
1–7
M‑4172 Instruction Book
Referring to Figure 1-6 and Figure 1-7, a few These parameters are key to analyzing the motor
generalizations can be made regarding the inertia of bus transfer issue and developing schemes
motor loads, motor size, and the mix of synchronous to accomplish transfers that promote process
and induction motors. continuity while causing no damage to the motors
or the loads.
• Inertia – The higher the inertia of the
aggregate motor loads on the motor bus, An important value to decide the viability of MBT
the more slowly the motor bus frequency is the resultant volts per hertz (V/Hz) across the
will decay during the disconnected breaker. The resultant V/Hz is derived from the V/
coastdown period. That has a direct impact Hz vectors of the motor bus and the new source
on how fast the phase angle changes. Low at the instant just prior to connection and must not
inertia loads will cause the phase angle to exceed 1.33 V/Hz [1]. Pursuant to phase angle and
change quickly, as the frequency of the voltage, and their effect on resultant V/Hz, some
motor bus decays quickly, and the slip generalizations can be made:
frequency between the motor bus and the
new source quickly increases. • Phase Angle – As the phase angle
increases between the two sources,
• Motor Size – The larger the motor size, assuming the two source voltages are the
the longer the time the voltage will take to same, the V/Hz will increase.
decay on an induction motor.
• Voltage – As the voltage difference
• Mix of Synchronous and Induction between the two sources increases,
Motors – Voltage will tend to decay assuming the phase angle between the
much more rapidly on a motor bus with all sources remains the same, the V/Hz will
induction motors. On a motor bus with a increase.
mix of synchronous and induction motors,
the synchronous motors will attempt to
hold up the voltage during the transfer
interval.
• Loading – The higher the load on the
motors, the faster the motor bus frequency
will decay.
Phase (Degrees)
60 -144 60 -144
Voltage
40 Magnitude -216 40 -216
Voltage
20 -288 20 -288
0 -360 0 -360
0 10 20 30 40 50 60 0 10 20 30 40 50 60
Figure 1-6 Coastdown of High Inertia Load On Figure 1-7 Coastdown of Low Inertia Load On
a Large Induction Motor a Small Induction Motor
1–8
Introduction – 1
The resultant V/Hz issue is exacerbated when the Hot Parallel, Fast, In-Phase, Residual and
phase angle difference increases and the voltage Fixed Time Transfer Methods
difference increases as shown in Figure 1-8. The MBTs can be categorized as closed or open
following relationship in equation 1 defines this transition [2]. The closed transition involves brief
condition: paralleling of the sources. The closed transition
transfer is commonly referred to as a hot parallel
ER =
2 2
E S + E M − 2 ES EM cos θ transfer. Open transition transfers do not parallel
[1] the sources, and include fast, in-phase, residual and
fixed time. The fast transfer can be subcategorized
where as simultaneous or sequential. All other transfers
ES System equivalent V/Hz are sequential.
1–9
M‑4172 Instruction Book
1–10
Introduction – 1
Residual Voltage Transfer fixed time transfer would be initiated. Obviously, the
In a residual voltage transfer, the motor bus is fast transfer offers the greatest chance of process
connected to the new source after the voltage on continuity, as the interruption period to the motors
the coasting motor bus falls to less than 0.33 pu. In is short. The in-phase transfer provides one more
this manner, no matter what the phase angle, the opportunity to transfer with a good possibilty to
resultant V/Hz will not exceed 1.33 V/Hz. This is the keep process continuity. By the time a residual or
third type of transfer type that does not parallel the fixed time transfer is initiated, the motors may have
sources. This type of transfer, however, typically is stopped against low inertia loads, such as positive
not fast enough to maintain process continuity, as displacement pumps or conveyors, and a process
certain motor loads that cause rapid stalling may interruption may occur. In addition, if many motors
necessitate a restart of the motors on the bus. must be started to restart the process, load shedding
and staggered starting of the motors may have to
be undertaken so as not to overload the capacity
Fixed Time Transfer of the new source and cause unacceptable voltage
In a fixed time transfer, the motor bus is connected to sags during the restarting procedure.
the new source after a time delay that would reflect
that the voltage on the coasting motor bus has fallen
References
to less than 0.33 pu. In this manner, no matter what
the phase angle, the resultant V/Hz will not exceed [1] ANSI C50.41-2000, American Nation
1.33 V/Hz. This is the fourth type of transfer type Standard for Polyphase Induction Motors
that does not parallel the sources. This type transfer, for Power generating Stations.
however, will not be able maintain process continuity, [2] A.P. Gabba and D.S. Hill, “Make Automatic
as certain motor loads that cause rapid stalling may Power Source Transfers a Success
necessitate a restart of the motors on the bus. for Your Plants,” IEEE Transactions on
Industry Applications, Vol. 37, No. 2, Mar/
These open transition transfers would be attempted Apr 2001.
in the order they are presented, as shown in Figure
1-9. The first possible transfer would be the fast [3] W.G. Hartmann, “Automatic Synchronizing
transfer which would be made if the phase angle for Generation and Tie Lines,” 18 th
between the motor bus and the new source is met. If Annual Georgia Tech Protective MBTSing
that transfer was not made, an in-phase, residual or Conference, Atlanta, GA, May 1999.
Fast
0 1 pu
Phase (Degrees)
Voltage
Residual and
180
Fixed Time
In-Phase
0 pu
360
Time
1–11
M‑4172 Instruction Book
1–12
Operation – 2
2 Operation
2–1
M‑4172 Instruction Book
2–2
Operation – 2
STATUS
BECKWITH ELECTRIC CO. 27B BUS UNDERVOLTAGE DELTA PHASE ANGLE OK
r
BUS TRANSFER SYSTEM CLOSE SOURCE 1 BRKR
INPUT 2
CLOSE SOURCE 2 BRKR
INPUT 5
INPUT 3 INPUT 6
r OUTPUTS
EXIT ENTER OUT 1 OUT 3 OUT 5 OUT 7
OUT 2 OUT 4 OUT 6 OUT 8
LED Test
AUTO FAST TRANSFER
OPERATE ELEMENTS
Model Number
AUTO FAST TRANSFER
OUTPUTS
Beckwith Electric Co.
M-4172
User Logo
INIT TRANSFER
Beckwith Electric Co. INIT rmte_lcal auto_xfer man-xfer stat comm setup
Substation Name
2–3
M‑4172 Instruction Book
• Software Version
REMOTE/LOCAL CONTROL
• Serial Number
init RMTE_LCAL • Alter Access Codes
• User Control Number
AUTO TRANSFER • User Logo Line 1
• User Logo Line 2
AUTO_XFER man_xfer
• Clear Alarm Counter
• Date & Time
MANUAL TRANSFER • Clear Error Codes
auto_xfer MAN_XFER • Eth Firmware Version
• Diagnostic Mode
STATUS
DIAGNOSTIC
STAT comm setup
MODE
• Voltage Status
• Current Status • Output Test (Relay)
• Frequency Status • Input Test (Status)
• Phase Angle Status • Status Led Test
• In/Out Status • Module Led Test
• Alarm Counter • Button Test
• Time of Last Power up • Display Test
• Error Codes • Com1 Loopback Test
• Checksums • Com2 Loopback Test
• Com3 Echo Test 2 Wire
• Clock Test
COMMUNICATION
• Flash Sys Ok Led
stat COMM setup • Auto Calibration
• Factory Use Only
• Com1 Setup
• Com2 Setup
• Com3 Setup DEVICE ON/OFF
• Communication Address ON_OFF exit
• Comm Access Code
• Ethernet Setup EXIT LOCAL MODE
• Ethernet IP Address
on_off EXIT
2–4
Operation – 2
LEVEL #(1,2 or 3)
A
ccess Granted!
I
NIT TRANSFER
INIT rmte_lcal
c. Go to step 4.
I
NIT TRANSFER
INIT rmte_lcal
C
ommunication
stat COMM setup
2–5
M‑4172 Instruction Book
2–6
Operation – 2
2–7
M‑4172 Instruction Book
LEVEL #(1,2 or 3)
A
ccess Granted!
2–8
Operation – 2
3. If Level Access is not active, then the HMI will display (scroll) the following
following is displayed: screens:
I
NIT TRANSFER MANUAL FAST TRANSFER
INIT rmte_lcal
30-JUN-2015 10:11:49.948
I
NIT TRANSFER MANUAL FAST TRANSFER
INIT rmte_lcal -
-PICKUP ELEMENTS--
2–9
M‑4172 Instruction Book
R
EMOTE/LOCAL CONTORL
i
nit RMTE_LCAL
C
ONTROL METHOD
Figure 2-6 Remote/Local Mode Dialog Screen L
OCAL remote
2. Select the desired control mode, then
6. Press the Left or Right arrow pushbutton
select Save.
as necessary to select the desired Control
3. Verify that the MBTS is in the desired Mode (upper case).
mode by observing the Remote Mode/
7. Press ENTER. The following will be
Local Mode status indicator on the
displayed:
Secondary Metering and Status screen
(System Status).
R
EMOTE/LOCAL CONTROL
i
nit RMTE_LCAL
Remote/Local Control (MBTS Front Panel)
To switch Control Method from the MBTS Front Panel 8. The MBTS is now in the selected Control
perform the following: Method. Press EXIT as necessary to
return to the Main Menu.
1. Press the ENTER pushbutton.
2. If Level Access is active, the following is
displayed: Device ON/OFF
The Device ON/OFF feature allows the operator
ENTER ACCESS CODE
to place the MBTS in a lockout condition. When
"Device OFF" is selected, no automatic or manual
0 transfers can be executed either through Local
mode or Remote mode and all output relays are
a. Input the required Access Code, then deactivated. The "Device ON" selection returns
press ENTER. the MBTS back to normal operation.
b. If the proper Access Code has been
entered, the HMI will return: When selecting Device ON/OFF feature through
Local mode (COM1 or HMI) the MBTS Local mode
LEVEL #(1,2 or 3)
must be selected. Any Remote attempt is blocked.
A
ccess Granted! When selecting Device ON/OFF feature through
Remote mode (COM2, RS485 or Ethernet), the
I
NIT TRANSFER MBTS Remote mode must be selected. Any Local
attempt is blocked.
INIT rmte_lcal
Upon saving the "Device OFF" selection, the Self-Test
c. Go to Step 4. relay contact terminals 15 & 16 close, the front panel
System OK and Fast/Paral Trans Ready Status LED
3. If Level Access is not active, then the indicators extinguish. All output relays are deactivated.
following is displayed:
Upon saving the "Device ON" selection, the Self-Test
relay contact terminals 15 & 16 open, front panel
I
NIT TRANSFER
System OK and Fast/Paral Trans Ready Status LED
INIT rmte_lcal indicators illuminate for normal operation. All output
relays return to activated states.
2–10
Operation – 2
D
EVICE ON/OFF
O
N_OFF exit
D
EVICE MODE
O
N off
Figure 2-7 Device On/Off Dialog Box 6. Press the Left or Right arrow pushbutton
as necessary to select the desired Device
2. Select either Device ON or Device OFF, Mode (upper case).
then select Save. 7. Press ENTER. The following will be
3. Verify that the MBTS is in the desired displayed:
mode by observing the Device On/Off
Mode status indicator on the Secondary D
EVICE ON/OFF
Metering and Status screen (System O
N_OFF exit
Status).
8. The MBTS is now in the selected Device
Device ON/OFF (MBTS Front Panel) Mode. Press EXIT as necessary to return
to the Main Menu.
To switch the MBTS On or OFF from the Front Panel
perform the following:
1. Press the ENTER pushbutton.
2. If Level Access is active, the following is
displayed:
LEVEL #(1,2 or 3)
A
ccess Granted!
I
NIT TRANSFER
INIT rmte_lcal
2–11
M‑4172 Instruction Book
System Error Codes and Output Counters Clear Alarm Counters (MBTS Front Panel)
The System Error Codes and Output Counters To reset Alarm Counters from the Front Panel
feature provides the user with the ability to view and perform the following:
clear system Error Codes, Processor Resets, Alarm
Counters, Power Loss Counter and Output Counters. 1. Press the ENTER pushbutton.
Also, Checksums can be viewed for Calibration and 2. If Level Access is active, the following is
Setpoints. displayed:
Figure 2-8 System Error Codes and Output Counters Dialog Screen
2–12
Operation – 2
3. If Level Access is not active, then the Clear Error Codes (MBTS Front Panel)
following is displayed: To clear Error Codes from the Front Panel perform
the following:
I
NIT TRANSFER
1. Press the ENTER pushbutton.
INIT rmte_lcal
2. If Level Access is active, the following is
4. Press the Right arrow pushbutton until displayed:
the following is displayed:
ENTER ACCESS CODE
S
ETUP UNIT 0
stat comm SETUP
a. Input the required Access Code, then
5. Press ENTER, the following will be press ENTER.
displayed: b. If the proper Access Code has been
entered, the HMI will return:
S
OFTWARE VERSION
VERS sn access number
LEVEL #(1,2 or 3)
A
ccess Granted!
6. Press the Right arrow pushbutton until
the following is displayed:
I
NIT TRANSFER
CLEAR ALARM COUNTER
INIT rmte_lcal
logo1 logo2 ALARM
c. Go to Step 4.
7. Press ENTER, the following will be
3. If Level Access is not active, then the
displayed:
following is displayed:
CLEAR ALARM COUNTER
I
NIT TRANSFER
PRESS ENTER KEY TO CLEAR
INIT rmte_lcal
8. Press ENTER, the following will be
4. Press the Right arrow pushbutton until
displayed:
the following is displayed:
CLEAR ALARM COUNTER
S
ETUP UNIT
-ALARM COUNTER CLEARED-
stat comm SETUP
9. Press EXIT as necessary to return to the
5. Press ENTER, the following will be
Main Menu.
displayed:
S
OFTWARE VERSION
VERS sn access number
2–13
M‑4172 Instruction Book
7. Press ENTER, the following will be Switching The Active Setpoint Profile
displayed: The Active Profile may be chosen utilizing ISScom®
through remote communications or through the
CLEAR ERROR CODES
ISSLogic elements. See Chapter 3, ISScom for
PRESS ENTER KEY TO CLEAR
additional information.
To manually select the Active Setpoint Profile
8. Press ENTER, the following will be
proceed as follows:
displayed:
1. Open the M-3871 ISScom Communications
CLEAR ERROR CODES
and Analysis software.
-ERROR CODES CLEARED-
2. Establish communications with the target
All Error codes have been cleared. M-4172.
3. Select System/Profile/Active Profile.
9. Press EXIT as necessary to return to the ISScom will display the "Select Active
Main Menu. Profile" dialog screen Figure 2-9.
2–14
Operation – 2
2–15
M‑4172 Instruction Book
2–16
Operation – 2
The Function Status window displays the status of To access the STATUS menu and begin monitoring,
various functions, with "T" representing the function proceed as follows:
which has timed out, and "P" representing the
function which has picked up and is timing. 1. Press the ENTER, the following will be
displayed:
▲ CAUTION: Do not use the Manual Initiate of 3. Press the ENTER, the following will be
ISScom when Delta Phase Angle and Delta Voltage displayed:
are constantly changing. Use the Manual Initiate of
the MBTS Front Panel. V
OLTAGE STATUS
The Phasor Diagram (Figure 3-18) provides selected VOLT curr freq phang
reference Phase Angle to Phase Angle data from
other sources. The Phasor Diagram also includes a 4. Press the Right or Left arrow pushbutton
Freeze capability to freeze the data displayed on the until the desired parameter is selected
Phasor Diagram. (upper case), then press ENTER. The
MBTS will display the selected parameter.
The Sync Scope screen (Figure 3-19) provides the
Delta Frequency relationship between the Bus and 5. Press the ENTER pushbutton to move
down within the STATUS menu to the
the New Source, illustrated in a Fast or Slow direction
desired category. To exit a specific
based on Delta Frequency.
category and continue to the next menu
category, press the EXIT pushbutton.
MBTS Front Panel
Transfer Event Log
Monitor Status/Metering
The initiating event that starts the Transfer Event Log
The HMI menu categories for monitored values are: is the "Start" signal for any transfer. A Transfer Event
• Voltage Status – S1, S2 and Bus phase Log is considered complete when one of following
voltages, Bus positive sequence voltage, occurs:
Bus negative sequence voltage, delta
voltage (referenced to new source) • When the breaker from the Old Source trips
and the breaker to the New Source closes.
• Current Status – S1 and S2 phase
currents (single-phase A, B or C / a, b or c)
• When a breaker failure occurs.
• Frequency Status – Bus Frequency • When the incomplete transfer timer times out.
and Delta Frequency (referenced to new
source) The trigger and complete events are used to define
the time frame during which the transfer event log
• Phase Angle Status
is storing information. One transfer can have up to
• I/O Status – Status of input and output 4 records. After 16 records have been stored, any
contacts new record will cause the oldest existing record to
• Alarm Counter be lost. Each Transfer Event Log parameter is time
stamped with the date and time in 1 ms increments.
• Time of Last Power up
• Error Codes A reset feature is provided to clear this log through
the serial communications. See Chapter 3, ISScom®,
• Checksums – setpoints, calibration, ROM
subsection System/Transfer Event Log for Transfer
Event Log Download, View, Clear Status and Clear
History selections.
2–17
M‑4172 Instruction Book
Oscillograph
The Oscillographic Recorder provides comprehensive
data recording of all monitored waveforms, and
status inputs storing up to 248 cycles of data.
The Oscillographic Recorder is triggered by a
designated control/status input (usually a MBTS
initiate input), an automatically initiated signal, a
trip output, a manual transfer signal or from serial
communications. The Oscillograph Recorder settings
are not considered to be part of the Setpoint Profile
and should be recorded manually. Recorder settings
are common to all profiles.
See Chapter 3, ISScom®, subsection System/
Oscillograph for Oscillograph Recorder Retrieve,
Trigger and Clear selections.
2–18
ISScom – 3
3 ISScom®
This chapter is designed for the person or group Shortcut Command Buttons
responsible for the operation and setup of the When the ISScom software opens, there are also
MBTS. The M‑3871 ISScom Communications and 8 shortcut command buttons for the most common
Oscillographic Analysis Software is required to operations performed by ISScom. The three buttons,
successfully communicate system settings and Monitor, Setup System and System Setpoints
operational commands to the MBTS as well as are also found under the System drop down menu.
access the extensive monitoring and status reporting
features. Figure 3-3, represents the ISScom Main Initiate and Reset Buttons
Screen menu structure. This chapter provides a The Initiate and Reset buttons are used to control the
general description of each ISScom menu selection MBTS. The Initiate button is used to initiate a Manual
and command in the same order as they are Transfer and the Reset Button Resets the Output
displayed in the software program. Those ISScom Status of Latched Outputs, Timed Out Function
features and functions that are covered in other Statuses that are Latched, the System Status and
sections of this Instruction Book will be noted and Latched Lockout indicators (if the condition is no
referenced. longer present).
Remote/Local Button
3.1 ISScom Functional Description The Remote/Local button opens a dialog screen
(Figure 3-2), that provides a selection between
The ISScom installation and establishing initial local Remote and Local control of the MBTS. If Local
communications are covered in Section 5.5, ISScom is selected only locally initiated transfers will be
Communications and Oscillographic Analysis performed, then Remote Control (manual initiate
Software Installation, and Section 5.6, Activating transfer) of the MBTS is blocked. Local mode also
Initial Local Communications. blocks remote setpoint changes. Remote Control
is defined as those manual transfers that initiate
Selecting the ISScom Program from the Becoware through any serial port (except for the RS-232 port
Folder or selecting the ISScom Program Icon (Figure on the front panel) and any externally connected
3-1), from the Desktop will open the program and manual initiate command through inputs; blocking
display the ISScom Main Screen (Figure 3-5). inputs are still allowed.
3–1
M‑4172 Instruction Book
3–2
ISScom – 3
3–3
M‑4172 Instruction Book
3–4
ISScom – 3
Figure 3-7 ISScom® Serial Communication Figure 3-8 ISScom TCP/IP Ethernet
Dialog Screen Communication Dialog Screen
3–5
M‑4172 Instruction Book
3–6
ISScom – 3
System/Setup/Setpoints/Display All
Selecting the Display All button displays the All
Setpoints Table dialog screen (Figure 3-13). This
dialog screen contains the settings for each MBTS
function within a single window to allow scrolling
through all MBTS setpoint and configuration values.
Both dialog screens (All Setpoint Table and
Configure), feature Jump Command Buttons which
allow the user to jump from a scrolling dialog screen
to an individual MBTS function dialog screen and
return to the scrolling dialog screen. All available
parameters can be reviewed or changed when
jumping to an MBTS configuration dialog screen
from either scrolling dialog screen.
3–7
M‑4172 Instruction Book
Path: System / Setup / System Setpoints / ATS command button OR ATS jump hotspot within All Setpoints Table
3–8
ISScom – 3
Path: System menu / Setup submenu / Setpoints screen/ Display All button
3–9
M‑4172 Instruction Book
3–10
ISScom – 3
3–11
M‑4172 Instruction Book
3–12
ISScom – 3
3–13
M‑4172 Instruction Book
▲ CAUTION: Do not use the Delta Phase Angle, The M-4172 MBT System portion of the screen also
Delta Voltage, Delta Frequency or Sync Scope displays the Manual Transfer Ready status, Lockout/
Pointer of the ISScom® Sync Scope screen to Blocking status, the Remote/Local control status and
determine when to manually initiate a transfer. There the Device ON/Device OFF status.
is sufficient delay in the communications between the
The Manual Transfer Ready indicator displays
MBTS and the ISScom such that these indications
GREEN color when the Manual Fast Transfer Ready
do not provide "live" information.
or Manual Hot Parallel Transfer Ready condition is
met.
System/Monitor/Single Line Diagram
The Single Line Diagram screen (Figure 3-20) is The Manual Transfer Ready indicator is not
a mimic display that allows the user to observe illuminated when the Manual Fast Transfer Ready
the Source 1 (S1) and Source 2 (S2)’s Secondary or Manual Hot Parallel Transfer Ready condition is
Voltage, Current and Bus Secondary Voltage. All of not met.
these metering values can be selected to be primary The Lockout/Blocking indicator displays RED color
or secondary values. when the Lockout/Blocking condition occurs. The
The screen displays the Phase Voltages for the Lockout/Blocking indicator is not illuminated when
three voltage inputs to the M-4172 MBT System. no Lockout/Blocking condition occurs.
The voltages of S1, S2 and Bus for the selected The Remote indicator displays GREEN color and
single phase will be displayed. The screen displays Local indicator is not illuminated when the Remote/
the single phase currents flowing through the Source Local control is selected to the Remote position.
1 and Source 2 breakers. The current is used for
the Breaker Failure (50BF) feature only. If the S1/ The Remote indicator is not illuminated and Local
S2 CT Configuration is set to "No" (S1 & S2 CT indicator displays GREEN color when the Remote/
not connected to the rear terminals) (Figure 4-22), Local control is selected to Local position.
then the Single Line Diagram will not display current
values. The Device ON indicator displays GREEN color
and Device OFF indicator is not illuminated when
The Single Line Diagram screen also displays Delta the Device On/Off control is selected to Device On
Phase Angle, Delta Frequency and Delta Voltage position.
between the motor bus and the new source (the new
source is defined as the source to which the bus is The Device ON indicator is not illuminated and
being transferred). Device OFF indicator displays RED color when
the Device On/Off control is selected to Device Off
position.
3–14
ISScom – 3
3–15
M‑4172 Instruction Book
NOTES:
1. If the S1/S2 CT Configuration is set to "No" (S1 & S2 not connected to the rear terminals)
(Figure 4-22), then the Single Line Diagram will not display current values.
2. The user may select either the primary or secondary values on the Single Line Diagram.
Path: System / Monitor / Single Line Diagram
Figure 3-20 Single Line Diagram (Primary Metering) or (Secondary Metering) Screen
3–16
ISScom – 3
System/Transfer Event Log • Open transition time (the time period from
The Transfer Event Log feature captures the following when the old source breaker status contact
parameters: opens to when the new source breaker
status contact closes)
• Start signal. The signals that trigger a • Close transition time in Hot Parallel Transfer
transfer are an external protective relay only (the time period from when the new
initiate, external undervoltage relay initiate, source breaker status contact closes to
internal automatic bus undervoltage relay when the old source breaker status contact
initiate, and manual initiate (either local, opens)
remote or through serial communications).
• Transfer completed: Fast, In-Phase,
• Source 1 voltage and current at time of trip Residual Voltage, Fixed Time or Hot
(or close) Parallel
• Source 2 voltage and current at time of
close (or trip)
A transfer can have up to four records. After 16
• Bus voltage at time of close (or trip) records have been stored, any new record will cause
• Delta Voltage between bus and new the oldest existing record to be lost. Each Transfer
source at time of close command (or trip Event Log parameter is time stamped with the date
command) and time in 1 ms increments.
• Delta Voltage between bus and new source The initiating event that starts the Transfer Event Log is
at the time of actual breaker close (or the "Start" signal for any transfer. A Transfer Event Log
breaker open) is considered complete when one of following occurs:
• Bus frequency, at time of close (or trip)
• When the breaker from the Old Source trips
• Bus rate of change of frequency at time of and the breaker to the New Source closes.
close (or trip)
• When a breaker failure occurs.
• Resultant Volts/Hertz at time of actual
• When the incomplete transfer timer times
breaker close
out.
• Element(s) Timed Out, for example: 27B,
81, 81R and 50BF Functions
The trigger and complete events are used to define
• Element(s) picked up, for example: 27B, the time frame during which the transfer event log is
81, 81R and 50BF Functions storing information. The Secondary Metering and
• Input/output contact status changes Status Screen (Figure 3-17) will display a status
when a complete Transfer Event Log has been
• Trip and close commands
stored. A reset feature is provided to clear this log
• Delta phase angle between bus and new through the serial communications. The Transfer
source at time of close command (or trip Event Log is available for viewing utilizing the M-3871
command) ISScom® Communications and Oscillograph Analysis
• Delta phase angle between bus and new Software.
source at time of actual breaker close (or
The Transfer Event Log menu selection opens a
breaker open)
submenu that includes the Download, View, Clear
• Delta frequency between bus and new Status and Clear History selections.
source at time of close command (or trip
command)
• Delta frequency between bus and new
source at time of actual breaker close (or
breaker open)
• Breaker closing time (the time period from
when the close command is issued to when
the new source’s breaker status contact
closes
• Breaker Opening Time
3–17
M‑4172 Instruction Book
2. Select Download. The Transfer Event Log Figure 3-22 Transfer Event Log Viewer
Record Download screen will display a
bar indicating the status of the download. 6. To print the Transfer Event Log Summary
When the download is complete the Save information select Print Summary.
As screen will be displayed with a default ISScom will print the Summary information
".log" file extension. to the default printer connected to the
3. Select the destination folder and name the computer. See Appendix D, Transfer
file, then select Save to save the Transfer Event Log Printout Sample.
Event Log Record or Cancel. 7. To print the Transfer Event Log Detail
information select Print Detail. ISScom
will print both the Summary and Detail
System/Transfer Event Log/View
information to the default printer
To view available Transfer Event Log Records connected to the computer. See Appendix
perform the following: D, Transfer Event Log Printout Sample.
1. From the ISScom Main Screen menu 8. To view the System Status and Transfer
select System/Transfer Event Log/ Start Signal information select System
View. ISScom will display the Transfer Status and Transfer Start Signal.
Event Log Viewer screen (Figure 3-22). ISScom will display the System Status
and Transfer Start Signal Status screen
2. Select Open. ISScom will display the (Figure 3-25).
Open screen with a default ".log" file
extension. 9. To view the Transfer Event Log Pickup
Input and Output information, select
3. Select the location of the ".log" files, then Pickup I/Os. ISScom® will display the
select the file to be viewed. Pickup I/Os Status screen (Figure 3-26).
4. Select Open. ISScom will Open the target
file in the Transfer Event Log Viewer
Summary screen (Figure 3-23).
3–18
ISScom – 3
Figure 3-24 Transfer Event Log File Summary and Details Screen
3–19
M‑4172 Instruction Book
Figure 3-25 System Status and Transfer Start Signal Status Screen
3–20
ISScom – 3
3–21
M‑4172 Instruction Book
3–22
ISScom – 3
3–23
M‑4172 Instruction Book
3–24
ISScom – 3
7. To print the Sequence of Events 10. To view the System Status and Transfer
Detail information select Print Detail. Start Signal information select System
ISScom will print both the Summary Status and Transfer Start Signal.
and Detail information to the default ISScom will display the System Status
printer connected to the computer. and Transfer Start Signal Status screen
See Appendix E, Sequence of Events (Figure 3-40).
Printout Sample.
8. To view the Sequence of Events Pickup System/Sequence of Events/Clear
Input and Output information select The Clear feature clears all Sequence of Events
Pickup I/Os. ISScom will display the Records stored on the MBTS.
Pickup I/Os Status screen (Figure 3-36).
To Clear all Sequence of Events Records perform
the following:
1. From the ISScom Main Screen menu
select System/Sequence of Events/
Clear. ISScom will display the Clear
Sequence of Events Records confirmation
screen (Figure 3-38).
3–25
M‑4172 Instruction Book
Figure 3-40 Sequence of Events System Status and Transfer Start Signal Status Screen
3–26
ISScom – 3
3–27
M‑4172 Instruction Book
3–28
ISScom – 3
System/Oscillograph/Trigger System/Oscillograph/Clear
The Trigger selection allows the user to manually The Clear feature clears all Oscillograph Records
trigger the Oscillograph. This can be confirmed stored on the MBTS.
by observing the Secondary Metering and Status
screen (Figure 3-17). To Clear all Oscillograph Recorder records perform
the following:
To manually Trigger the Oscillograph Recorder
perform the following: 1. From the ISScom Main Screen menu
select System/Oscillograph/Clear.
1. From the ISScom Main Screen menu ISScom will display the Clear Oscillograph
select System/Oscillograph/Trigger. Record confirmation screen (Figure
ISScom will display the Oscillograph 3-45).
Manual Trigger confirmation screen
(Figure 3-43).
3–29
M‑4172 Instruction Book
System/Profile/Active Profile
Active Profile (Figure 3-47) allows user to designate
active profile. The user can select between four
profiles. If a profile is not saved into a profile the
profile will contain factory default settings.
▲ CAUTION: Switching the active profile when the
MBTS is on-line may cause unexpected operation if Figure 3-48 Copy Profile Dialog Screen
the wrong profile is selected.
System/Write File To System
▲ CAUTION: During Profile Switching, relay The Write File To System command is used to write
operation is disabled for approximately 1 second. a saved data file to the MBTS.
To perform a Write File To System command perform
the following:
3–30
ISScom – 3
3–31
M‑4172 Instruction Book
If the level 3 access code is set to 9999, the access User Logo Line
code feature is disabled. When access codes are The user logo is a programmable, two-line by
disabled, the access screens are bypassed, and all 24‑character string, which can be used to identify the
users have full access to all the MBTS menus. The MBTS, and which is displayed locally during power
device is shipped from the factory with the access up after Self Test completion. This information is also
code feature disabled. available in ISScom.
User Control Number
The User Control Number is a user-defined value
which can be used for inventory or identification. The
unit does not use this value, but it can be accessed
through the HMI or the communications interface,
and can be read remotely.
System OK LED
The green SYSTEM OK LED is controlled by the
unit’s microprocessor. A flashing SYSTEM OK LED
Figure 3-52 User Access Codes Reset Dialog indicates proper program cycling. The LED can also
Screen be programmed to be continuously illuminated.
Tools/Miscellaneous Setup
The Miscellaneous Setup menu selection displays
the Miscellaneous Setup screen (Figure 3-53) which
provides the user with the ability to edit/input the
User Logo lines of the HMI display, enter/edit the
User Control Number and set the operating mode
of the System OK LED. See Section 4.1, Unit Setup
for detailed setup instructions.
3–32
ISScom – 3
3–33
M‑4172 Instruction Book
3–34
ISScom – 3
3–35
M‑4172 Instruction Book
3.2 ISSplot
3–36
ISScom – 3
3–37
M‑4172 Instruction Book
ISSplot File Menu ISSplot Select New Source for Delta Angle
The ISSplot File menu allows the user to open an Allows the user to select Source 1 or Source 2.
oscillograph file previously downloaded by ISScom®.
ISScom supports COMTRADE format data files (file
extension *.cfg). The File menu also permits the user
to preview and print selected oscillographs. Exit
closes the ISSplot program.
3–38
ISScom – 3
NOTE: Cursor bars may be dragged to any location by positioning the cursor arrow on a bar and dragging
the mouse. Double click the left key to position one cursor bar and Shift‑Double Click or left mouse
down and click the right key to position the other cursor bar at the current cursor arrow time position.
3–39
M‑4172 Instruction Book
Left key or select left scroll icon in toolbar menu Move left in main display
Right key or select right scroll icon in toolbar menu Move right in main display
End key or select move to end icon in toolbar menu Move to the end of the record in the main display
3–40
ISScom – 3
Value at Marker #1
Value at Marker #2
Time at
Marker #1
Time at
Marker #2
Time at Marker #1
Control status input
and contact output Date and Timestamp Time of Trip
traces (discrete I/O) Time at Marker #2
for record Command
QQ NOTE: Cursor bars may be dragged to any location by positioning the cursor arrow on a bar and dragging
the mouse. Double click the left key to position one cursor bar and Shift-Double Click or double
click the right key to position the other cursor bar at the current cursor arrow time position.
3–41
M‑4172 Instruction Book
3–42
System Setup and Setpoints – 4
4–1
M‑4172 Instruction Book
ISScom® Comm Access Code Setup HMI Comm Access Code Setup
To set the MBTS Comm Access Code perform the 1. Press the ENTER pushbutton.
following: 2. If Level Access is active, the following is
NOTE: Communication must be established with displayed:
the target MBTS for this procedure.
ENTER ACCESS CODE
1. From the ISScom Main Screen menu 0
select Tools/System Access Code/
Comm Access. ISScom will display the a. Input the required Access Code, then
Communication Access Code Reset press ENTER.
dialog screen(Figure 4-1). b. If the proper Access Code has been
entered, the HMI will return:
LEVEL #(1,2 or 3)
A
ccess Granted!
I
NIT TRANSFER
INIT rmte_lcal
c. Go to step 4.
C
OM1 SETUP
COM1 com2 com3 com_adr
Figure 4-2 Communication Access Code Sent 6. Press the Right arrow pushbutton until
Confirmation Screen the following is displayed:
4. Select OK, ISScom will return to the Main COMM ACCESS CODE
Screen. ACCSS eth eth_ip
The new Communication Access Code
will not be in affect until communications 7. Press ENTER, the following will be
have been closed with the MBTS for displayed:
approximately 2.5 minutes.
COMM ACCESS CODE
9999
4–2
System Setup and Setpoints – 4
8. Input the desired Comm Access Code ISScom User Access Codes Setup
as follows: To set the MBTS User Access Codes perform the
a. Utilizing the Up and Down arrow following:
pushbuttons select the desired first NOTE: Communication must be established with
digit. the target MBTS for this procedure.
b. Press the Left arrow pushbutton
once, then repeat the previous step
as necessary to input the desired 1. From the ISScom® Main Screen menu
Comm Access Code digits. select Tools/System Access Code/
User Access. ISScom will display the
c. When the desired Comm Access User Access Code Reset dialog screen
Code has been input, then press (Figure 4-3).
ENTER. The following will be
displayed:
9. Press EXIT.
4–3
M‑4172 Instruction Book
HMI User Access Codes Setup 7. Press ENTER, the following will be
1. Press the ENTER pushbutton. displayed:
2. If Level Access is active, the following is
displayed: L
EVEL #1
9999
ENTER ACCESS CODE
8. Input the desired User Access Code as
0 follows:
a. Input the required Access Code, then a. Utilizing the Up and Down arrow
press ENTER. pushbuttons select the desired first
digit.
b. If the proper Access Code has been
entered, the HMI will return: b. Press the Left arrow pushbutton
once, then repeat the previous step
as necessary to input the desired
LEVEL #(1,2 or 3)
Access Code.
A
ccess Granted! c. When the desired Access Code has
been input, then press ENTER. The
following will be displayed:
I
NIT TRANSFER
INIT rmte_lcal
ENTER ACCESS CODE
c. Go to step 4. LEVEL#1 level#2 level#3
3. If Level Access is not active, then the 9. To set User Access Code Level #2
following is displayed: press the RIGHT arrow pushbutton to
select LEVEL #2, then press ENTER the
following will be displayed:
I
NIT TRANSFER
INIT rmte_lcal
L
EVEL #2
4. Press the Right arrow pushbutton until 9999
the following is displayed:
10. Repeat Step 8 to enter the desired Level
#2 User Access Code.
S
ETUP UNIT
11. To set User Access Code Level #3
stat comm SETUP
press the RIGHT arrow pushbutton to
select LEVEL #3, then press ENTER the
5. If User Access Codes are to be set, following will be displayed:
then use the RIGHT arrow pushbutton
to select ALTER ACCESS CODES. The
following will be displayed: L
EVEL #3
9999
ALTER ACCESS CODES
12. Repeat Step 8 to enter the desired Level
vers sn ACCESS number
#3 User Access Code.
6. Press ENTER, the following will be 13. Press the EXIT pushbutton will return to
displayed: the previous selection screen:
4–4
System Setup and Setpoints – 4
I
NIT TRANSFER
INIT rmte_lcal
S
ETUP UNIT
stat comm SETUP
3. If changing the User Control Number, 6. Press the Right arrow pushbutton until
then enter the desired User Control the following is displayed:
Number.
USER LOGO LINE 1
LOGO 1 logo 2 alrm
4–5
M‑4172 Instruction Book
7. Press ENTER, the following will be 11. Input the desired User Logo Line 2 as
displayed: follows:
a. Utilizing the Up and Down arrow
USER LOGO LINE 1
pushbuttons select the desired first
_BECKWITH ELECTRIC CO.
letter/symbol/digit/blank space.
b. Press the RIGHT arrow pushbutton
8. Input the desired User Logo Line 1 as once, then repeat the previous step
follows: as necessary to input the desired
a. Utilizing the Up and Down arrow User Logo Line 2.
pushbuttons select the desired first c. When the desired User Logo Line 2
letter/symbol/digit/blank space. has been input, then press ENTER.
b. Press the Right arrow pushbutton The following will be displayed:
once, then repeat the previous step
as necessary to input the desired USER LOGO LINE 2
User Logo Line 1.
—
WAIT—
c. When the desired User Logo Line 1
has been input, then press ENTER.
The following will be displayed: USER LOGO LINE 2
logo 1 LOGO 2 alrm
USER LOGO LINE 1
12. Press EXIT.
—
WAIT—
INIT TRANSFER
INIT rmte_lcal
c. Go to step 4.
I
NIT TRANSFER
INIT rmte_lcal
4–6
System Setup and Setpoints – 4
4. Press the Right arrow pushbutton until HMI System OK LED Setup
the following is displayed: 1. Press the ENTER pushbutton.
S
ETUP UNIT 2. If Level Access is active, the following is
displayed:
stat comm SETUP
ENTER ACCESS CODE
5. Press ENTER, the following will be
displayed: 0
S
OFTWARE VERSION a. Input the required Access Code, then
press ENTER.
VERS sn access number
b. If the proper Access Code has been
entered, the HMI will return:
6. Press the Right arrow pushbutton until
the following is displayed: LEVEL #(1,2 or 3)
USER CONTROL NUMBER
A
ccess Granted!
vers sn access NUMBER
I
NIT TRANSFER
7. Press ENTER, the following will be INIT rmte_lcal
displayed:
c. Go to step 4.
USER CONTROL NUMBER
1 3. If Level Access is not active, then the
following is displayed:
8. Input the desired User Control Number
as follows: I
NIT TRANSFER
a. Utilizing the Up and Down arrow INIT rmte_lcal
pushbuttons select the desired first
digit. ▲ CAUTION: Do not enter DIAGNOSTIC MODE
b. Press the Left arrow pushbutton when protected equipment is in service. Entering
once, then repeat the previous step DIAGNOSTIC MODE when protected equipment is in
as necessary to input the desired service removes all protective functions of the MBTS.
User Control Number. 4. Press the right arrow pushbutton until the
c. When the desired User Control following is displayed:
Number has been input, then
press ENTER. The following will be SETUP UNIT
displayed:
stat comm SETUP
DIAGNOSTIC MODE
time error eth DIAG
4–7
M‑4172 Instruction Book
4–8
System Setup and Setpoints – 4
3. If setting the Date and Time manually 5. Press ENTER, then press the RIGHT
then: arrow pushbutton until the following is
displayed:
a. Select "Relay Time".
b. Enter the desired Date and Time. DATE & TIME
c. Select "Save". ISScom will display a TIME
error eth diag
"write values to unit?" confirmation
screen. 6. Press ENTER, the following will be
d. Select "Yes". The Time and Date will displayed:
be set to the desired Time and Date.
ISScom will then return to the main DATE & TIME
screen.
0
8-Jan-2001 00:00:80
HMI SET DATE and TIME
7. Press ENTER, the following will be
1. Press the ENTER pushbutton. displayed:
2. If Level Access is active, the following is
displayed: DATE & TIME
01 Year
ENTER ACCESS CODE
0 8. Input the desired Year as follows:
a. Utilizing the Up and Down arrow
a. Input the required Access Code, then pushbuttons select the desired first
press ENTER. digit.
b. If the proper Access Code has been b. Press the Left arrow pushbutton
entered, the HMI will return: once, then repeat the previous step
as necessary to input the desired
LEVEL #(1,2 or 3)
Year.
A
ccess Granted! c. When the desired Year has been
input, then press ENTER. The
I
NIT TRANSFER following will be displayed:
INIT rmte_lcal
DATE & TIME
c. Go to step 4. J
AN feb mar apr may
3. If Level Access is not active, then the 9. Input the desired Month as follows:
following is displayed:
a. Utilizing the Right or Left arrow
I
NIT TRANSFER pushbuttons select the desired
Month.
INIT rmte_lcal
b. When the desired Month has been
4. Press the RIGHT arrow pushbutton until selected, then press ENTER. The
the following is displayed: following will be displayed:
S
ETUP UNIT DATE & TIME
stat comm SETUP
8 Date
4–9
M‑4172 Instruction Book
10. Input the desired Date as follows: 13. Input the desired Minutes as follows:
a. Utilizing the Up and Down arrow a. Utilizing the Up and Down arrow
pushbuttons select the desired Date pushbuttons select the desired first
first digit. digit.
b. Press the Left arrow pushbutton b. Press the Left arrow pushbutton
once, then repeat the previous step once, then repeat the previous step
as necessary to input the desired as necessary to input the desired
date. Minute(s).
c. When the desired Date has been c. When the desired Minutes have
input, then press ENTER. The been input, then press ENTER. The
following will be displayed: following will be displayed:
11. Input the desired Day as follows: 14. Input the desired Seconds as follows:
a. Utilizing the Right or Left arrow a. Utilizing the Up and Down arrow
pushbuttons select the desired Day. pushbuttons select the desired first
b. When the desired Day has been digit.
selected, then press ENTER. The b. Press the Left arrow pushbutton
following will be displayed: once, then repeat the previous step
as necessary to input the desired
Seconds.
DATE & TIME
c. When the desired Seconds have
01 Hour been input, then press ENTER. The
following will be displayed:
12. Input the desired Hour as follows:
a. Utilizing the Up and Down arrow DATE & TIME
pushbuttons select the desired first
digit. TIME
error eth diag
b. Press the Left arrow pushbutton
once, then repeat the previous step
as necessary to input the desired
Hour.
c. When the desired Hour has been
input, then press ENTER. The
following will be displayed:
4–10
System Setup and Setpoints – 4
• COM Port definitions and Device Address COM3 located on the rear terminal block of the
M‑4172 is an RS-485, 2-wire connection. Appendix
• Ethernet Port Settings
B, Figure B-3 illustrates a 2-wire RS-485 network.
• Installing Modems
Individual remote addressing also allows for
communications through a serial multidrop network.
Serial Ports (RS-232)
Up to 32 MBTSs can be connected using the same
NOTE: COM1 and COM2 can be disabled 2 wire RS-485 communications line.
for secur ity pur poses from the
communications HMI menu. A Level 2
Access Code is required. Direct Connection
In order for ISScom to communicate with the relay
Two serial interface ports, COM1 and COM2, are using direct serial connection, a serial "null modem"
standard 9-pin, RS-232, DTE-configured ports. cable is required, with a 9-pin connector (DB9P)
The front-panel port, COM1, can be used to locally for the system, and an applicable connector for the
set and interrogate the MBTS using a temporary computer (usually DB9S or DB25S). Pin-outs for a
connection to a PC or laptop computer. The second null modem adapter are provided in Appendix B,
RS-232 port, COM2, is provided at the rear of the Communications.
unit. COM2 is unavailable for communications when
the optional ethernet port is enabled. However, the An optional 10 foot null modem cable (M-0423)
Demodulated IRIG-B may still be used through the is available from the factory, for direct connection
COM2 Port when Ethernet is enabled. between a PC and the relay’s front panel COM port,
or the rear COM2 port.
4–11
M‑4172 Instruction Book
STATUS
BECKWITH ELECTRIC CO. 27B BUS UNDERVOLTAGE DELTA PHASE ANGLE OK
r
CLOSE SOURCE 1 BRKR CLOSE SOURCE 2 BRKR
INPUT 2 INPUT 5
INPUT 3 INPUT 6
r OUTPUTS
EXIT ENTER OUT 1 OUT 3 OUT 5 OUT 7
OUT 2 OUT 4 OUT 6 OUT 8
STATUS
BECKWITH ELECTRIC CO. 27B BUS UNDERVOLTAGE DELTA PHASE ANGLE OK
r OUTPUTS
EXIT ENTER OUT 1 OUT 3 OUT 5 OUT 7
OUT 2 OUT 4 OUT 6 OUT 8
STATUS
BECKWITH ELECTRIC CO. 27B BUS UNDERVOLTAGE DELTA PHASE ANGLE OK
STATUS
TRIP SOURCE 1 BRKR TRIP SOURCE 2 BRKR
BECKWITH ELECTRIC CO. 27B BUS UNDERVOLTAGE DELTA PHASE ANGLE OK INPUT 3 INPUT 6
EXIT ENTER OUT 1 OUT 3 OUT 5 OUT 7 M-4172 DIGITAL MOTOR 81/81R BUS FREQ/ROCOF
TRIP SOURCE 1 BRKR
ALARM OUTPUT BLOCK
TRIP SOURCE 2 BRKR
r OUTPUTS
EXIT ENTER OUT 1 OUT 3 OUT 5 OUT 7
OUT 2 OUT 4 OUT 6 OUT 8
STATUS
BECKWITH ELECTRIC CO. 27B BUS UNDERVOLTAGE DELTA PHASE ANGLE OK
r OUTPUTS
EXIT ENTER OUT 1 OUT 3 OUT 5 OUT 7
OUT 2 OUT 4 OUT 6 OUT 8
4–12
System Setup and Setpoints – 4
ISScom COM Port Definitions and System’s 8. When the COM Port settings have been
Communication Address entered, then select Save. ISScom will
To setup the COM Ports and Communication display the COM Port Settings Warning
Addresses perform the following: Screen (Figure 4-9).
4–13
M‑4172 Instruction Book
HMI COM Port Enable/Disable, Definitions and 8. Press ENTER, the following will be
Device Address displayed:
1. Press the ENTER pushbutton.
COM1 BAUD RATE
2. If Level Access is active, the following is
displayed: b
aud_4800 BAUD_9600
a. Input the required Access Code, then 10. Press ENTER, the following will be
press ENTER. displayed:
b. If the proper Access Code has been
COM1 DEAD SYNC TIME
entered, the HMI will return:
50 ms
LEVEL #(1,2 or 3)
A
ccess Granted! 11. Input the desired Dead Sync Time as
follows:
a. Utilizing the Up and Down arrow
I
NIT TRANSFER
pushbuttons select the desired first
INIT rmte_lcal digit.
b. Press the Left arrow pushbutton
c. Go to step 4. once, then repeat the previous step
as necessary to input the desired
3. If Level Access is not active, then the Dead Sync Time.
following is displayed:
c. When the desired Dead Sync Time
I
NIT TRANSFER has been input, then press ENTER.
The following will be displayed:
INIT rmte_lcal
COM1
PARITY
4. Press the Right arrow pushbutton until NONE odd even
the following is displayed:
12. Press the Left or Right arrow pushbutton
C
ommunication as necessary to select the desired Parity
stat COMM setup
setting.
13. Press ENTER, the following will be
5. Press ENTER, the following will be displayed:
displayed:
COM1 STOP BITS
C
OM1 SETUP
1
COM1 com2 com3 com_adr
14. Utilizing the Up or Down arrow
6. Press ENTER, the following will be pushbuttons select the desired Stop Bits.
displayed:
15. Press ENTER, the following will be
P
ORT ACCESS displayed:
enable
DISABLE C
OM1 SETUP
7. Press the Left or Right Arrow pushbutton COM1 com2 com3 com_adr
as necessary to enable or disable the
COM port. 16. Selecting COM2 or COM 3 will activate
the same menu choices as displayed
with the selection of COM1. Repeat as
necessary to setup the remaining COM
Ports.
4–14
System Setup and Setpoints – 4
ETHERNET COMMUNICATION SETTINGS These services allow a user to monitor all metering
The optional RJ45 ethernet port can be enabled values, change settings and also generate
utilizing either ISScom® from the Ethernet Settings unsolicited reports. The metering values are
menu or from the HMI Communication menu. When reported in the metering and measurement nodes
the ethernet port is enabled the COM2 Serial Port data classes (MMTR, MMXU), the setpoints and
is not available for communications. However, the configuration settings are viewed and modified in
Demodulated IRIG-B may still be used through the the protection function nodes and system logical
COM2 Port when ethernet is enabled. nodes data classes (PTOV, PTUV, etc.). These data
classes are defined by the 61850-7-4 document.
The following parameters must be set for proper Furthermore, the M‑4172 is compatible with the
ethernet communication: IEC 61850 substation configuration language (SCL),
making the data set for the report control block highly
DHCP PROTOCOL configurable. In addition to the generation of reports
due to a change in a data value, e.g., a change in
ENABLE: If the network server supports the DHCP
pickup status of a protective function, the M‑4172
protocol the network server will assign the IP
also supports an integrity period, where a report
Address, Net Mask and Gateway Address.
control block is transmitted to the connected SCADA
DISABLE: If the network server does not support system at the expiration of the integrity period.
the DHCP protocol or the user chooses to manually ISScom Ethernet Port Setup with DHCP
input ethernet settings, then obtain the IP Address,
Net Mask and Gateway address from the Network NOTE: Communication must be established with
Administrator and enter the settings. the target MBTS for this procedure.
4–15
M‑4172 Instruction Book
ISScom Ethernet Port Setup without DHCP 6. Use the Right arrow pushbutton to select
NOTE: Communication must be established with ETH (Upper Case).
the target MBTS for this procedure.
E
THERNET SETUP
1. From the ISScom Main Screen menu access ETH eth_ip
select Tools/System Ethernet Setup.
ISScom will display the Ethernet Setup
7. Press ENTER, the following will be
screen (Figure 4-11).
displayed:
2. Select Ethernet Enable.
3. Select DHCP Protocol Disable. E
THERNET
D ISABLE enable
4. Enter values for IP Address, Net Mask
and Gateway. 8. Use the Right arrow pushbutton to select
5. Select Save. The ethernet board is now ENABLE (Upper Case), then press
configured for use and may be accessed ENTER, the following will be displayed:
through a network.
T
CP/IP SETTINGS
HMI Ethernet Port Setup T CP_SETTINGS
1. Press the ENTER pushbutton.
9. Press ENTER, the following will be
2. If Level Access is active, the following is displayed:
displayed:
D
HCP PROTOCOL
NTER ACCESS CODE
E D ISABLE enable
0
10. If the network does not support the DHCP
a. Input the required Access Code, then protocol, then go to Manual Configuration
press ENTER. of Ethernet Board (following page) to
manually configure the ethernet board.
b. If the proper Access Code has been
entered, the HMI will return: 11. If the DHCP Protocol is to be enabled,
then use the Right/Left arrow pushbutton
LEVEL #(1,2 or 3)
to select ENABLE (Upper Case), then
A
ccess Granted! press ENTER, the following will be
displayed:
I
NIT TRANSFER T
CP/IP SETTINGS
INIT rmte_lcal T CP_SETTINGS
I
NIT TRANSFER C
ONFIGURING ETH...
INIT rmte_lcal
4. Press the Right arrow pushbutton until If the ethernet board successfully obtains
the following is displayed: an IP Address the following will be
displayed for approximately 2 seconds:
C
OMMUNICATION
THERNET IP ADDRESS
E
stat COMM setup
xx.xx.xx.xx
5. Press ENTER, the following will be
displayed: The ethernet board is now configured
for use and may be accessed through
a network. The display will return to the
C
OM1 SETUP
following:
COM1 com2 com3 com_adr
4–16
System Setup and Setpoints – 4
C
OM1 SETUP
COM1 com2 com3 com_adr
4–17
M‑4172 Instruction Book
15. Press EXIT, the ethernet board will 3. Verify that the modem is attached to (if
reconfigure and the following will be external) or assigned to (if internal) the
displayed: same serial port as assigned in ISScom.
While ISScom can use any of the 255
C
ONFIGURING ETH... serial ports (COM1 through COM255),
most computers support only COM1 and
COM2.
If the ethernet board is successfully
4. Connect the modem to a telephone line,
configured, then the entered IP Address
then energize the modem.
will be displayed for approximately 2
seconds:
Initializing the PC Modem
THERNET IP ADDRESS
E 1. Verify that the modem is connected
x
x.xx.xx.xx as described in "Connecting the PC
Modem".
The ethernet board is now configured for use and 2. Open ISScom, then select the COMM
may be accessed through a network. menu item.
3. ISScom will display the Communication
INSTALLING THE MODEMS Dialog screen (Figure 4-12).
Using ISScom® to interrogate, set or monitor the
MBTS using a modem requires both a remote modem 4. Select COMM DEVICE/MODEM, ISScom
connected at the MBTS location and a local modem will display the Expanded Communication
Dialog screen (Figure 4-13) to include
connected to the computer with ISScom installed.
modem setup information.
NOTE: Any compatible modem may be used; 5. Enter the required information in the
however, the unit only communicates at PC Modem Settings section of the
1200 to 9600 baud. Communication screen
In order to use ISScom to communicate with the 6. Select INITIALIZE from the expanded
MBTS using a modem, the following must be Communications dialog box.
provided with the MBTS:
• An external modem (1200 baud or higher),
capable of understanding standard AT
commands.
• Serial modem cable with 9-pin connector
for the MBTS and the applicable connector
for the modem.
4–18
System Setup and Setpoints – 4
COMMAND BUTTONS
Serial COM The Serial COM Port selection allows the
Port user to select the COM Port, Baud Rate,
Parity and Stop Bits.
Open COM Initiates contact with the MBTS, either by
direct serial or modem communication.
Close COM Breaks communication with the protective
system, for both direct serial or modem
communication.
TCP_IP O p e n s t h e e t h e r n e t a p p l i c a bl e
communication screen selections to
allow user to enter a TCP_IP address
(if necessary), and opening and closing
communication with the target relay.
Modem Displays the expanded Communication
dialog box.
Cancel Returns you to the ISScom main window;
any changes to the displayed information
are lost.
Open TCP_IP Initiates contact with the protective system
by ethernet connection.
Close TCP_IP Closes Ethernet Connection
COMMAND BUTTONS
Bring Up When selected, following connection to
Terminal the target modem, allows the user to send
Window commands to the modem.
After Dialing Displays the Add/Edit dialog box,
Add allowing you to type a protective system’s
unit identifier, phone number, and
communication address.
Figure 4-13 Expanded
Edit Displays the Add/Edit dialog box, allowing
Communication Dialog Screen you to review and change the user lines
(unit identifier), phone number, and
communication address of a selected
entry.
Delete Deletes a selected entry.
Save Saves any changes to the displayed
information
Initialize Allows the user to send special setup or
other AT commands directly to the modem.
Dial Dials the entry selected from the directory.
Hang Up Ends modem communication, allowing the
user to dial again.
4–19
M‑4172 Instruction Book
Connecting the Local Modem to the MBTS When connected to another terminal device, the
Setup of the modem attached to the MBTS may Terminal Window allows the user to send messages
be slightly complicated. It involves programming or commands. Outgoing communications are
parameters (using the AT command set), and storing displayed in the top pane and incoming messages
this profile in the modem’s nonvolatile memory. are displayed in the bottom two panes, in ASCII text
and HEX format.
After programming, the modem will power up in
the proper state for communicating with the MBTS. There are some variations in the AT commands
Programming may be accomplished by using the supported by modem manufacturers. Refer to the
"Bring Up Terminal Window after dialing" selection hardware user documentation for a list of supported
(Figure 4-13). Refer to your modem manual for AT commands and direction on issuing these
further information. commands.
4–20
System Setup and Setpoints – 4
4–21
M‑4172 Instruction Book
4–22
System Setup and Setpoints – 4
SEQUENCE OF EVENTS RECORDER SETUP 2. Select the desired Inputs and Outputs,
Protective function Pickup, Trip, Dropout and/or then select Save. ISScom will display a
Output/Input Pickup or Dropout are selected to Send Changes to Unit Screen (Figure
trigger the Sequence of Events Recorder. 4-17).
4–23
M‑4172 Instruction Book
4–24
System Setup and Setpoints – 4
NOTE: See Section 4.3, System Diagrams 5. Select the S1/S2 VT Configuration
for Typical VT Three-Line Connection button. ISScom displays the S1/S2 VT
Diagrams. Configuration selection screen (Figure
4-20).
2. Enter the Nominal Voltage.
The S1/S2 VT Configuration allows the
The Nominal Voltage setting (50 to 140 selection of the Source 1 and Source 2
V) is needed for proper normalization of voltage transformer configuration. When
per unit quantities. Nominal Voltage for phase‑ground (three‑phase) is selected,
the following voltage connections is as the phase-to-phase single phase
follows: choices are grayed out and only one
• Line-to-Line VT connections phase to ground choice can be made.
When phase-to-phase (three‑phase)
VNominal = V Bus / VT Ratio is selected, the phase‑to‑ground
single‑phase choices are grayed‑out
• Line-to-Ground VT connections and only one phase‑to‑phase choice can
be made. Both Source 1 and Source 2
VNominal = V Bus / (e3 VT Ratio) must have the same VT Configuration.
3. Enter the Nominal Current. The 6. Select the desired S1 and S2 VT
secondary CT current of the phase CTS. Configuration, then select OK, ISScom
returns to the Setup System screen.
4. Select the Phase Rotation. (ABC or
ACB). 7. Select the Bus VT Configuration
button. ISScom displays the Bus VT
NOTE: See Section 4.3, System Diagrams Configuration selection screen (Figure
for Typical VT Three-Line Connection 4-21).
Diagrams.
4–25
M‑4172 Instruction Book
Some selections are grayed-out 10. Enter the VT and CT ratios (Figure 4-19).
depending on the Source 1/Source 2
The VT and CT ratios are used only
selection. The Bus VT Configuration
for monitoring and displaying system
must have the same phase-to-ground
primary quantities.
or phase-to-phase selection as the
Source 1/Source 2 configuration. If either • Ratio of the Phase VTs
of three-phase selections are chosen Example:
for the Source 1/Source 2, then the
bus must have the same configuration. 13,800 V: 120 V = 13,800/120 = 115: 1
However, if the Source 1/Source 2 single- • Ratio of Phase CTs
phase selection is chosen then the bus Example:
configuration can be either the same
single-phase or the three-phase. 3,000: 5 = 3000/5 = 600: 1
For example, if the Source 1/Source NOTE: If neither pulsed or latched output is
2 selection is phase-to-phase (three enabled, then the output contact will
phase), then the bus must use the default to the Normal Mode. Normal
same phase-to-phase (three-phase) Mode maintains the output contact
configuration. If the Source 1/Source energized as long as the condition
2 selection is phase-to-phase (single that caused it to operate exists. After
phase BC), then the bus choices will be the actuating condition is cleared, the
phase-to-phase (single phase BC) or contact will reset after the programmed
phase-to-phase (three phase). seal-in time has elapsed.
8. Select the desired Bus VT Configuration,
then select OK, ISScom® will return to 11. Select Outputs from the LATCHED
the Setup System screen. OUTPUTS section of the System Setup
9. Select the S1/S2 CT Configuration screen. ISScom will display the Latched
button. ISScom displays the S1/S2 CT Outputs Selection Screen (Figure 4-23).
Configuration Selection screen (Figure
4-22).
The S1/S2 CT Confguration Selection
is based on whether the S1 and S2 CTs
are connected to the rear terminals of
the MBTS. The default selection is "Yes"
which includes the current values for
S1 and S2 on the Single Line Diagram
(Figure 3-20). Selecting "No" removes
the S1 and S2 current elements from the
Single Line Diagram.
4–26
System Setup and Setpoints – 4
The Latched Outputs selection screen The Pulsed Outputs selection screen
allows the user to select which outputs allows the user to select which outputs
are latched when they are activated. are pulsed when they are activated. The
Outputs 1 through 4 are the Trip and pulse width is defined in the Output Seal
Close command outputs for the breakers in time section of Figure 4-19, Setup
and cannot be latched (the pulse length System Dialog Screen. If pulse MBTS
of these outputs are set in the Common operation is selected, output will dropout
Settings screen Figure 4-34). These after the seal-in delay expires, even if the
outputs remain latched until reset by an condition which caused the MBTS to pick
ISScom command or by the HMI of the up is still out of band. When selected as
MBTS. When selected as Latched the Pulsed the output will be grayed out in
output will be grayed out in the Pulsed the Latched Output Selection screen.
Output Selection screen.
Outputs 1 through 4 are the trip and close command
12. Select the desired outputs to be Latched, outputs for the breakers, the pulse length of these
then select OK, ISScom will return to the outputs are set in the Common Settings screen
Setup System screen. (Figure 4-34).
NOTE: If neither pulsed or latched output is
enabled, then the output contact will 14. Select the desired outputs to be Pulsed,
default to the Normal Mode. Normal then select OK, ISScom will return to the
Mode maintains the output contact Setup System screen.
energized as long as the condition
that caused it to operate exists. After NOTE: If neither pulsed or latched output is
the actuating condition is cleared, the enabled, then the output contact will
contact will reset after the programmed default to the Normal Mode. Normal
seal-in time has elapsed. Mode maintains the output contact
energized as long as the condition
that caused it to operate exists. After
13. Select Outputs from the PULSED the actuating condition is cleared, the
OUTPUTS section of the System Setup contact will reset after the programmed
screen. ISScom will display the Pulsed seal-in time has elapsed.
Outputs Selection Screen (Figure 4-24).
15. Select Input Status from the INPUT
ACTIVE STATE section of the System
Setup screen. ISScom will display the
Input Active States Selection Screen
(Figure 4-25).
This Input Active States selection screen
allows the user to select the active input
state for each input. Inputs 1 and 4 are
the breaker status inputs which have
predefined terminals for "a" and "b"
contacts. Checking the inputs for the
Active Input Open parameter designates
the "operated" state established by an
opening rather than closing an external
contact. The Input LED on the Status
Module and Input LED on the ISScom's
Input/Output Status Section in the
Secondary Metering and Status screen
will illuminate according to the input
Figure 4-24 Pulsed Outputs Selection Screen "operated" state.
For example: Checking Input 2 for the
Active Input Close parameter designated
the operated state of the 86P-S1 contact
that is closed when the 86P-S1 lockout
relay is tripped.
4–27
M‑4172 Instruction Book
4–28
System Setup and Setpoints – 4
M-4172 M-4172
VA VA
39 45
38 44
VB VB
41 47
40 46
VC VC
43 49
42 48
1 57 59
51 50 53 52 55 54
52S1 56 58 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
4–29
M‑4172 Instruction Book
38 44
VB VB
41 47
40 46
VC VC
43 49
42 48
1 57 59
51 50 53 52 55 54
52S1 56 58 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
4–30
System Setup and Setpoints – 4
M-4172 M-4172
VAB VAB
39 45
38 44
VBC VBC
41 47
40 46
VCA VCA
43 49
42 48
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C respectively.
4–31
M‑4172 Instruction Book
38 44
VB VB
41 47
40 46
VC VC
43 49
42 48
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
2 VT-S1, VT-S2 and VT-B are single phase VTs. They all must be connected to the same
phase, either Phase A-To-Ground, Phase B-To-Ground or Phase C-To -Ground.
4–32
System Setup and Setpoints – 4
M-4172 M-4172
VAB VAB
39 45
38 44
VBC VBC
41 47
40 46
VCA VCA
43 49
42 48
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
2 VT-S1, VT-S2 and VT-B are single phase VTs. They all must be connected to the same
phase, either Phase A-To-Phase B, Phase B-To-Phase C or Phase A-To -Phase C.
4–33
M‑4172 Instruction Book
38 44
VB VB
41 47
40 46
VC VC
43 49
42 48
1 57 VA VB VC 59
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
2 VT-S1 and VT-S2 are single phase VTs. They both must be connected to the same
phase, either Phase A-To-Ground, Phase B-To-Ground or Phase C-To -Ground.
4–34
System Setup and Setpoints – 4
38 44
VBC VBC
41 47
40 46
VCA VCA
43 49
42 48
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
2 VT-S1 and VT-S2 are single phase VTs. They both must be connected to the same
phase, either Phase A-To-Phase B, Phase B-To-Phase C or Phase A-To -Phase C.
4–35
M‑4172 Instruction Book
4–36
System Setup and Setpoints – 4
TRANSFER SETTINGS
COMMON SETTINGS (CS)
Path: System/Setup/Setpoints/Common Settings
4–37
M‑4172 Instruction Book
4–38
System Setup and Setpoints – 4
Common Settings/Transfer Mode transfer to the new source at the same time. Since
Transfer Mode can be selected as either Simultaneous the existing power is being tripped (due to some
or Sequential: abnormality) and the new source is outside of the
setting range, a transfer will not occur and the motor
Simultaneous — With a transfer initiated,
• bus will lose power.
within 10 ms of transfer initiate, all three
methods of transfer, Fast, In-Phase and Common Settings/Breaker Closing Time
Residual Voltage Transfer are immediately
enabled to supervise closure of the new The Breaker Closing Time setting defines the
source breaker without waiting for the breaker closing time (the time period from when the
breaker status contact confirmation that close command is issued to when the new source
the old source breaker has opened. At breaker status contact closes) of the Source 1 and
the same instant, the commands for Source 2 breakers that the MBTS is controlling. The
the old source breaker and the new breaker closing time is used during an In-phase
source breaker to trip and close are sent transfer. The in‑phase transfer sends the close
simultaneously if and only if the phase command in advance of the phase coinsidence
angle between the motor bus and the new based on this breaker time and the rate of change
source is within the delta phase angle limit of the frequency of the decaying motor bus.
for the Fast Transfer Method immediately The purpose of using the breaker closing time is
upon transfer initiation. However only the to have the breaker actually close just at the time
Fixed Time Transfer is enabled 30 cycles of the phase coinsidence setting is in cycles, so
after the old source breaker has opened. time changes based on frequency. The Adaptation
Refer to Appendix F, Transfer Logic Time feature, when selected calculates the S1 and S2
Sequence for Timing Sequence of Transfer breaker closing times based on the average time
Logic in Simultaneous Transfer Mode. of the Last 8 breaker operations. When initially
• Sequential — With a transfer initiated, the selected, the selected breaker closing time will
command to trip the old source breaker be used until eight breaker operations have been
is sent within 10 ms. Upon confirmation averaged. If ISScom is connected to the M-4172
from the old source breaker status contact and the Common Function Settings screen is active
that the old source breaker is open. Within during a transfer, the Common Function Settings
4ms of receipt of this confirmation, all screen needs to be closed and then reopened in
three transfer methods, Fast, In-Phase order to refresh the breaker closing time value in
Transfer and Residual Voltage Transfer Adaptation Enable mode. Breaker Closing Time
are enabled to supervise closure of the setpoints cannot be changed while this feature is
new source breaker and the Fixed Time enabled.
Transfer is enabled 30 cycles later. Refer
to Appendix F, Transfer Logic Time Common Settings/S1(S2) Breaker Closing
Sequence for Timing Sequence of Transfer Time Deviation
Logic in Sequential Transfer Mode.
The S1(S2) Breaker Closing Time Deviation setting
establishes when the breaker has exceeded the
Common Settings/Upper-Lower Voltage Limit normal expected variations, plus or minus from the
New Source programmed closing time.
This setting defines the upper and lower voltage
limits of the new source. If the new source voltage When the Breaker Closing Time Deviation setting
is not within these limits, then a transfer is blocked. is exceeded a "S1/S2 Breaker Closing Time Out of
Range" indicator on the System Status section of
If a transfer is blocked and an initiate transfer signal the Secondary Metering and Status screen will be
is received, the transfer is not started (no trip or activated. Activation of this indicator would indicate
close command is sent to the supply breakers). This that the breaker may require maintenance.
prevents a transfer to a new source that does not
meet the voltage requirements established by the
Upper and Lower Voltage Limits. The result is that
the motor bus will lose power when the protective
MBTS trips the supply breaker and initiates a
4–39
M‑4172 Instruction Book
4–40
System Setup and Setpoints – 4
COMMON FUNCTION SETTINGS INPUTS TAB The 52a or 52b breaker status input contacts need
Path: System/Setup/Setpoints/Common Settings/Input to be breaker auxiliary contacts that change state
whenever the breaker closes/opens and when the
Figure 4-35, illustrates the MBTS Common Function breaker is in test or fully racked-in (connected)
Settings found under the Inputs Tab on the Common positions. During commissioning, when a bus
Function Settings dialog screen. transfer test is simulated, the M-4172 needs to see
the 52a or 52b contacts change state even when
Common Settings/Breaker Status Inputs the breaker is in test position.
The Breaker Status Inputs section provides the user
with the ability to select the type of 52 breaker status
contact being used for Source 1 and Source 2. One
of the two choices presented must be selected, the
52a or 52b. Only one choice for each breaker can
be selected. The selection must match the physical
connections to the unit for proper operation.
4–41
M‑4172 Instruction Book
4–42
System Setup and Setpoints – 4
4–43
M‑4172 Instruction Book
4–44
System Setup and Setpoints – 4
4–45
M‑4172 Instruction Book
4–46
System Setup and Setpoints – 4
4–47
M‑4172 Instruction Book
• Setup I
NIT TRANSFER
• Fast Transfer INIT rmte_lcal
• In-Phase Transfer
4. Press the Right arrow pushbutton until
• Residual Voltage Transfer the following is displayed:
• Fixed Time Transfer
A
UTO TRANSFER
AUTOMATIC TRANSFER SETTINGS A
UTO_XFER man_xfer
SETUP TAB
Path: System/Setup/Setpoints/Automatic Transfer 5. Press ENTER, the following will be
Settings/Setup displayed:
Figure 4-47, illustrates the MBTS Automatic Transfer
Settings found under the Setup Tab on the Automatic A
UTO TRANSFER
Transfer Settings dialog screen. d
isable enable
Automatic Transfer Settings Setup Tab/Auto 6. Press the Left or Right arrow pushbutton
Transfer Mode as necessary to enable or disable Auto
Tranfer (upper case).
The Auto Transfer Mode (Figure 4-47) can be
Disabled or Enabled. If Disable is selected and 7. Press ENTER. The following will be
then Save is selected, then the remaining settings displayed:
in the Automatic Transfer Settings dialog screen
are grayed out. A
UTO TRANFER
AUTO X_FER
man x_fer
HMI Auto Transfer Mode Enable/Disable
To enable or disable Auto Transfer from the Front 8. The MBTS is now in the selected Auto
Panel perform the following: Tranfer Mode. Press EXIT as necessary
to return to the Main Menu.
1. Press the ENTER pushbutton.
2. If Level Access is active, the following is
displayed:
LEVEL #(1,2 or 3)
A
ccess Granted!
4–48
System Setup and Setpoints – 4
Automatic Transfer Settings Setup Tab/Both S1 Before opening the Source 1 normally-closed
& S2 Breakers Open breaker, an external block transfer signal must
Both the S1 and S2 Breakers Open portion of the be applied to an M‑4172 input FIRST in order to
dialog screen (Figure 4-47) provides a selection block a transfer. This input MUST be set to block
for how the MBTS should respond when both the automatic transfers. When the Source 1 breaker is
Source 1 and Source 2 breakers are open. open resulting in two open breakers, the automatic
transfer is blocked by this external signal. While the
In normal operation either the Source 1 or the Source Source 1 breaker and Source 2 breaker are open,
2 break is closed. If the breaker that is closed is DO NOT remove the external block transfer signal
opened by an external operation when the Block until either the Source 1 breaker or the Source 2
Transfer is selected, then no transfer is performed by breaker is closed. Removing the external blocking
the M-4172. While this condition continues to exist signal will stop blocking the Auto Close function and
any transfer initiated externally or internally will be if both breakers open, the automatic transfer by the
blocked and no transfers will occur. Auto Close function will occur. Remove the external
block transfer signal ONLY after either the Source 1
If the Auto Close feature has been selected, then if breaker or Source 2 breaker is closed.
the breaker that was closed is opened by an external
operation, the automatic transfer is initiated. The Similar steps must be taken in case of a motor bus
other breaker will be closed by the Fast Transfer, fault condition.
In-Phase Transfer, Residual Voltage transfer or Fixed
Time Transfer settings of the Automatic Transfer In a motor bus fault condition, the bus protective
feature. The transfer method used will depend on relay or the bus lockout relay that trips the main
how the motor bus voltage decays when the power (Source 1) breaker MUST apply a block transfer
source is disconnected. For example, assume the signal to the M‑4172 input at the same time to block
Source 1 breaker is closed and the Source 2 breaker transferring a faulted motor bus to the new source.
is open. An operator accidentally opens the Source However, this also results in two open breakers.
1 breaker. The MBTS will close the Source 2 breaker Therefore, the automatic transfer by the Auto Close
based on the Automatic Transfer settings. function is blocked by the protective relay/lockout
relay block signal. This input signal must be latched
The Auto Close selection operates an automatic and remain closed as long as both breakers are
transfer in either direction. The purpose is to permit open. This protective relay/lockout relay input MUST
a transfer when the normally-closed breaker is NOT be removed until one of the breakers is closed.
accidentally/inadvertently tripped resulting in two After the bus fault is clear, DO NOT RESET the
open breakers. This operation is very similar to latched block transfer signal of the protective relay
the regular automatic transfer process except that /lockout relay until the following steps are completed
it does not send out the trip command, since the in sequential order to avoid unexpected/accidental
second breaker is already open. automatic transfer operation:
1. Activate an additional separate external
▲ CAUTION: When the Auto Close Function is block transfer signal (block transfer from
SELECTED, the following steps and procedures DCS or from local control switch) to an
must be performed in order to avoid unexpected/ M‑4172 input first in order to block a
accidental automatic transfer operation. transfer.
Assume the Source 1 breaker is closed and the 2. Then, reset the bus protective relay/
Source 2 breaker is open. An operator plans to lockout relay trip signal.
open the Source 1 normally-closed breaker for
3. Close the main (Source 1) breaker which
maintenance purposes, during normal start up will deactivate/reset the Auto Close
or shut down and does NOT want an automatic function.
transfer operation to occur after the Source 1
breaker is open. 4. Finally, remove the external block transfer
signal (block transfer from DCS or from
local control switch).
4–49
M‑4172 Instruction Book
4–50
System Setup and Setpoints – 4
Automatic Transfer/Auto Transfer Block Figure 4-48 Automatic Transfer Block Input
The Auto Transfer Block selection opens the Auto Settings Dialog Screen
Transfer Block dialog screen (Figure 4-48) that
allows the user to select an input that is used to Automatic Transfer/86P-S1 Initiate (S1 to S2)
block Automatic Transfers. When an input has been The 86P-S1 Initiate (S1 to S2) opens a dialog screen
selected it will be grayed out in other dialog screens similar to Figure 4-48 that allows the user to select
that provide input selection since it has already been an input that is used to initiate Automatic Transfers
assigned. from an 86P Lockout relay.
▲ CAUTION: When the Automatic Transfer Mode The selected input will initiate an Automatic Transfer
is selected (using an external Automatic/Manual from Source 1 to Source 2. If the Source 2 breaker
selector switch on the control panel), the Manual is closed and the Source 1 breaker is open, the
Transfer Block SHOULD BE ENABLED to prevent transfer is blocked since the breakers are in the
an inadvertent Manual Transfer. Conversely, when wrong positions for this transfer, the transfer is
Manual Transfer Mode is selected (using an external ignored. Since Automatic Transfers can occur in
Automatic/Manual selector switch on the control either direction, a separate Transfer Initiate Input
panel), the Automatic Transfer Block SHOULD is needed.
NOT BE ENABLED. If an unexpected event occurs,
tripping the present source while the selector switch When an input has been selected it will be grayed
is in the Manual position, and before a Manual out in other dialog screens that provide input
Transfer is initiated, with the only means of transfer selection since it has already been assigned.
blocked, the motor bus will begin to die. The decay is
so rapid that the operator will not be able to respond Automatic Transfer/86P-S2 Initiate (S2 to S1)
quickly enough to initiate a transfer.
The 86P-S2 Initiate (S2 to S1) opens a dialog screen
similar to Figure 4-48 that allows the user to select
an input or inputs that are used to initiate Automatic
Transfers from an 86P Lockout relay.
The selected input will initiate an Automatic Transfer
from Source 2 to Source 1. If the Source 1 breaker
is closed and the Source 2 breaker is open, the
transfer is blocked since the breakers are in the
wrong positions for this transfer and the transfer
is ignored. Since Automatic Transfers can occur in
either direction, a separate Transfer Initiate Input
is needed.
When an input has been selected it will be grayed
out in other dialog screens that provide input
selection since it has already been assigned.
4–51
M‑4172 Instruction Book
Automatic Transfer/27-S2 Initiate (S2 to S1) For the continuous internal multi-shot automatic
transfer initiation, use the M-4172 ISSlogic® function
The 27-S2 Initiate (S2 to S1) opens a dialog screen to implement this special automatic transfer logic.
similar to Figure 4-48 that allows the user to select
an input or inputs that are used to initiate Automatic The internal initiate transfer signal in ISSlogic stays
Transfers from an external 27 device. high as long as the Input contact initiating a transfer
is high (closed) and there are no blocking transfer
The selected input will initiate an Automatic Transfer conditions and block transfer signals.
from Source 2 to Source 1. If the Source 1 breaker
is closed and the Source 2 breaker is open the If the blocking transfer signal (such as unhealthy
transfer is blocked since the breakers are in the voltage at the new standby source or any external
wrong positions for this transfer and the transfer block input signals) occurs before the Input contact
is ignored. Since Automatic Transfers can occur in initiating a transfer is activated, the transfer is
either direction a separate Transfer Initiate Input is blocked and the internal initiate transfer signal
needed. is off. However, when the blocking condition is
released, the internal initiate transfer signal turns
When an input has been selected it will be grayed on immediately to start a transfer process.
out in other dialog screens that provide input
selection since it has already been assigned. The ISSlogic section is described in detail later in
this chapter.
Automatic Transfer Settings Setup Tab/Save/
Cancel — The Save selection (Figure 4-47) saves
the Automatic Transfer settings either to an open file
or to the target MBTS. Cancel, returns the user to
the previous open screen.
4–52
System Setup and Setpoints – 4
Figure 4-49 Automatic Transfer Settings Fast Transfer Tab Dialog Screen
4–53
M‑4172 Instruction Book
Figure 4-50 Automatic Fast Transfer Blocking Inputs Selection Dialog Screen
4–54
System Setup and Setpoints – 4
Figure 4-51 Automatic Transfer Settings In-Phase Transfer Tab Dialog Screen
4–55
M‑4172 Instruction Book
Automatic In-Phase Transfer/Blocking Inputs • The Delta Frequency between the motor
Selection bus and the new source is within limit
The Blocking Inputs Selection button opens the setting.
Blocking Inputs Selection dialog screen (Figure • The Phase Angle between the motor bus
4-50). Any Input or the Fuse Loss (FL) function can and the new source is changing and must
be selected to block an In-Phase Transfer. When enter the first phase coincidence (first
other functions such as Transfer Block #1 are zero degree crossing) within the In-Phase
selected for these inputs it will be identified next to Transfer time window (adjustable from 10
that input. to 600 cycles).
The In-Phase Transfer feature includes
Automatic In-Phase Transfer Save/Cancel two programmable advanced breaker
The Save selection saves the Automatic In-Phase closing times for Source 1 and Source 2
Transfer Tab settings either to an open file or to breakers (Figure 4-35) to coordinate the
the target MBTS. Cancel, returns the user to the closing of the first phase coincidence.
previous open screen. Programmable breaker closing time is
from 0 to 12 cycles.
The conditions that are necessary to execute an
In‑Phase Transfer are:
•
No Lockout/Blocking conditions exist.
• The conditions for Fast Transfer have not
been matched.
• The Delta Voltage between the motor bus
and the new source is within limit setting.
Figure 4-52 Automatic Transfer Settings Residual Voltage Transfer Tab Dialog Screen
4–56
System Setup and Setpoints – 4
4–57
M‑4172 Instruction Book
Figure 4-53 Automatic Transfer Settings Fixed Time Transfer Tab Dialog Screen
4–58
System Setup and Setpoints – 4
4–59
M‑4172 Instruction Book
MANUAL TRANSFER SETTINGS (MTS) 4. Press the Right arrow pushbutton until
the following is displayed:
Path: System/Setup/Setpoints/Manual Transfer Settings
LEVEL #(1,2 or 3)
A
ccess Granted!
I
NIT TRANSFER
INIT rmte_lcal
c. Go to Step 4.
I
NIT TRANSFER
INIT rmte_lcal
4–60
System Setup and Setpoints – 4
MANUAL TRANSFER SETTINGS SETUP TAB ▲ CAUTION: When the Manual Transfer Mode
Path: System/Setup/Setpoints/Manual Transfer Settings/ is selected (using an external Automatic/Manual
Setup selector switch on the control panel), the Automatic
Figure 4-55, illustrates the MBTS Manual Transfer Transfer Block SHOULD NOT BE ENABLED. If
Settings found under the Setup Tab on the Manual an unexpected event occurs, tripping the present
Transfer Settings dialog screen. source while the selector switch is in the Manual
position, and before a Manual Transfer is Initiated,
Manual Transfer Settings/Manual Transfer with the only means of transfer blocked, the motor
Mode bus will begin to die. The decay is so rapid that
the operator will not be able to respond quickly
Manual Transfer enough to initiate a transfer. Conversely, when
The Manual Transfer Mode (Figure 4-55) can be the Automatic Transfer Mode is selected (using an
Disabled or Enabled. If Disable is selected and then external Automatic/Manual selector switch on the
Save is selected, then the remaining settings in the control panel), the Manual Transfer Block SHOULD
Manual Transfer Settings dialog screen are grayed BE ENABLED to prevent an inadvertent Manual
out. There are settings in the Common Settings that Transfer.
effect the operation of the Manual Transfer.
4–61
M‑4172 Instruction Book
Figure 4-56 Manual Transfer Initiate Input Manual Fast Transfer/Delta Frequency Limit
Settings Dialog Screen The Delta Frequency Limit can be set from 0.02
to 2.0 Hz. The Delta Frequency is the frequency
Manual Transfer Save/Cancel difference between the motor bus and the new
source. This setting can be disabled. If disabled,
The Save selection saves the Manual Transfer
then this parameter is not used as a condition to
Settings Tab either to an open file or to the target
execute a fast transfer.
MBTS. Cancel returns the user to the previous open
screen.
4–62
System Setup and Setpoints – 4
Figure 4-57 Manual Transfer Settings Fast Transfer Tab Dialog Screen
Figure 4-58 Manual Fast Transfer Blocking Inputs Selection Dialog Screen
4–63
M‑4172 Instruction Book
4–64
System Setup and Setpoints – 4
Figure 4-59 Manual Transfer Settings In-Phase Transfer Tab Dialog Screen
4–65
M‑4172 Instruction Book
4–66
System Setup and Setpoints – 4
Figure 4-61 Manual Transfer Settings Residual Voltage Transfer Tab Dialog Screen
Figure 4-62 Residual Voltage Transfer Blocking Inputs Selection Dialog Screen
4–67
M‑4172 Instruction Book
4–68
System Setup and Setpoints – 4
Figure 4-63 Manual Transfer Settings Hot Parallel Transfer Tab Dialog Screen
Figure 4-64 Hot Parallel Transfer Blocking Inputs Selection Dialog Screen
4–69
M‑4172 Instruction Book
4–70
System Setup and Setpoints – 4
4–71
M‑4172 Instruction Book
VS1 VS1
VT-S1 VT-S2
IS1 M-4172 M-4172 IS1
IS2 IS2
VBus VS2 VS2 VBus
CT-S1 CT-S2
52 N.C. N.C. 52
S1 S2
VT-B1 VT-B2
BUS-TIE
STATION BUS SYSTEM BUS 1 BUS 2
52T
CT-B1 N.O. CT-B2
M M M M
4–72
System Setup and Setpoints – 4
4–73
M‑4172 Instruction Book
Figure 4-67 Function Settings Bus Phase Undervoltage Transfer Initiate (S1 to S2) Dialog Screen
Figure 4-68 27B#1 Bus Phase Undervoltage Transfer Initiate Inputs/Outputs Selection Dialog Screen
4–74
System Setup and Setpoints – 4
50BF #1 SOURCE 1 BREAKER FAILURE Time Delay — The time period (1 to 30 cycles) after
the Pickup Current setting is exceeded at which
Path: System/Setup/Setpoints/50BF#1
point the Breaker Failure Alarm is actuated.
The 50BF #1 Source 1 Breaker Failure selection
from the Function Settings group (Figure 4-33) NOTE: To have 50BF #1 Function working
opens the 50BF #1 Source 1 Breaker Failure dialog properly, the time delay should not
be set longer than the trip S1 breaker
screen (Figure 4-69).
command’s pulse width/duration.
Enable/Disable — The top right corner of the
display includes a command button that will disable I/O Selection — The I/O Selection button opens
or enable the function. the 50BF #1 Source 1 Breaker Failure Outputs/
Blocking Inputs Selection Dialog Screen (Figure
Pickup Current — A breaker failure condition is 4-71). This screen allows any input or the Fuse Loss
detected by the continued presence of current (FL) function to be selected to block the 50BF #1
after a trip command has been sent to the Source Function. The 50BF #1 Function can also be used
1 breaker. If the current is greater than the Pickup to activate a selected output when it times out.
Current setting for the time period of the Time Delay
setting after the trip command is sent, then the I/O Initiate — The I/O Initiate button opens the 50BF
breaker failure alarm indicated. #1 Source 1 Breaker Failure Initiate Inputs/Initiate
Outputs Selection Dialog Screen (Figure 4-72). This
If the Simultaneous Transfer mode is selected screen allows the selection of outputs or inputs that
(Common Function SettingsFigure 4-33), then can be used to initiate a breaker failure. Any of the
the breaker that was just closed is tripped open outputs can also be selected to initiate a breaker
to prevent the New Source from continuing to be failure. Figure 4-70 illustrates the logic combinations
connected through the failed breaker to the Old that can be implemented.
Source that could have a fault.
Save/Cancel — The Save selection saves the 50BF
If the Sequential Transfer mode is selected #1 Source 1 Breaker Failure settings either to an
(Common Function SettingsFigure 4-33), then a open file or to the target MBTS. Cancel, returns the
close command will not be sent since the breaker user to the previous open screen.
status would indicate that the tripped breaker did not
open. Since the transfer could not be completed the
Incomplete Transfer Lockout timer would time out
and generate a lockout condition.
4–75
M‑4172 Instruction Book
Output Initiate OR
Input Initiate
Figure 4-71 50BF #1 Source 1 Breaker Failure Figure 4-72 50BF #1 Source 1
I/O Selection Dialog Screen Breaker Failure Initiate Inputs/Initiate
Outputs Selection Dialog Screen
4–76
System Setup and Setpoints – 4
S1 BF SOURCE 1 BREAKER FAILURE I/O Selection — The I/O Selection button opens the
(BREAKER STATUS) S1 BF Source 1 Breaker Failure Outputs Blocking
Inputs Selection Dialog Screen (Figure 4-75). This
Path: System/Setup/Setpoints/S1 BF screen allows any input or the Fuse Loss (FL)
The S1 BF Source 1 Breaker Failure (Breaker function to be selected to block the S1 BF Function.
Status) selection from the Function Settings group The S1 BF Function can also be used to activate a
(Figure 4-33) opens the S1 BF Source 1 Breaker selected output when it times out.
Failure (Breaker Status) dialog screen (Figure 4-74).
Save/Cancel — The Save selection saves the S1 BF
The Source 1 breaker status inputs are monitored for Source 1 Breaker Failure (Breaker Status) settings
breaker failure. The Source 1 breaker is considered either to an open file or to the target MBTS. Cancel,
failed when the breaker status has not changed state returns the user to the previous open screen.
within the programmable time after a trip command
is issued. S2 BF SOURCE 2 BREAKER FAILURE
When the Simultaneous Transfer mode is selected (BREAKER STATUS)
(Common Function Settings (Figure 4-34), and Path: System/Setup/Setpoints/S2 BF
a breaker failure occurs on Source 1 that should
have tripped, the breaker that was just closed will The S2 BF Source 2 Breaker Failure (Breaker
be tripped. This prevents the New Source from Status) selection from the Function Settings group
continuing to be connected through the failed (Figure 4-33) opens the S2 BF Source 2 Breaker
breaker to the old source that may be faulted. Failure (Breaker Status) dialog screen (Figure
4-76). The S2 BF Source 2 Breaker Failure Function
If the Sequential Transfer mode is selected includes the same features as S1 BF except that
(Common Function Settings (Figure 4-34), then a it monitors for a breaker failure of the Source 2
close command will not be sent since the breaker breaker.
status would indicate that the tripped breaker did not
open. Since the transfer could not be completed, the
Incomplete Transfer Lockout timer would time out
and generate a lockout condition.
4–77
M‑4172 Instruction Book
Figure 4-75 S1 BF Source 1 Breaker Failure (Breaker Status) I/O Selection Dialog Screen
4–78
System Setup and Setpoints – 4
60FL BUS VT FUSE LOSS I/O Selection — The I/O Selection button opens the
60FL Bus VT Fuse-Loss I/O Selection Dialog Screen
Path: System/Setup/Setpoints/60FL
(Figure 4-77) that allows any input to be selected
The 60FL Bus VT Fuse Loss selection from the to block the 60FL Function. The 60FL Function can
Function Settings group (Figure 4-33) opens the also be used to activate a selected output when it
60FL Bus VT Fuse Loss dialog screen (Figure 4-78). times out.
Enable/Disable — The top right corner of the The Fuse-loss (FL) function is activated immediately
display includes a command button that will disable with NO time delay when the Bus VT fuse loss
or enable the function. condition is detected. The FL function is still
operated internally according to the Delta Voltage
NOTE: When the 60FL function is disabled, it Pickup setting of the 60FL function even though the
will only disable the Block Transfer or 60FL function is DISABLED.
Fixed Time Transfer operation in the Bus
VT Fuse Loss Condition. The status of
the Fuse Loss (FL) Input is still active in
all other functions, such as 27B1, 27B2,
27B3, 27B4, etc.
Time Delay — A Time Delay can be applied to delay Figure 4-77 60FL Bus VT Fuse-Loss Function
the 60FL Bus VT Fuse-Loss function output.
Inputs/Outputs Selection Dialog Screen
Bus VT Fuse Loss Condition — When the
difference in voltage between the bus and the
connected source (with connected source breaker
in closed position) is present for the time delay,
the MBTS will respond based on the selection to
either Block Transfer or perform an automatic Fixed
Time Transfer when a transfer is initiated. Since the
bus voltage cannot be observed the only possible
transfer that could be performed is the Fixed Time
Transfer.
4–79
M‑4172 Instruction Book
4–80
System Setup and Setpoints – 4
81R (Rate Of Change Of Frequency) Time Delay — A Time Delay can be applied to delay
(BUS VOLTAGE) the 81R ROCOF (Bus Voltage) function output. The
time delay and magnitude settings of the 81R should
Path: System/Setup/Setpoints/81R be based on simulation studies.
Figure 4-81 displays the settings for the 81R #1 Negative Sequence Voltage Inhibit — The function
ROCOF (Bus Voltage) function. The settings for uses the negative sequence voltage to block the
the 81R #2 ROCOF (Bus Voltage) are the same as 81R.
the 81R #1.
Increasing ROCOF — The Increasing ROCOF
NOTE: Bus VT configuration must be set to
(Bus Voltage) can be selected as either Enable or
Three-Phase to enable the 81R ROCOF
Disable. When the Increasing ROCOF is selected
Function.
to Disable, the 81R function detects the rate of
Enable/Disable — The top right corner of the change of frequency of the motor bus voltage in the
display includes a command button that will disable decreasing direction only, and the 81R function is
or enable the function. This selection allows the 81R blocked to detect the increasing direction. When the
#1 ROCOF (Bus Voltage) to be disabled (or enabled) Increasing ROCOF is selected to Enable, the 81R
independent from the 81R #2. function detects the rate of change of frequency of
the motor bus voltage in both the increasing and
Pickup — The 81R Rate of Change of Frequency decreasing directions.
(ROCOF) Bus Voltage function is used to detect
the rate of change of the frequency of the motor I/O Selection — The I/O Selection button opens
bus as it decays. When the bus is disconnected the 81R ROCOF (Bus Voltage) I/O Selection Dialog
from the original source the frequency begins to Screen (Figure 4-82) that allows any input or the
decrease and the longer the bus is disconnected Fuse Loss (FL) function to be selected to block the
the faster the frequency changes. This function is 81R #1(2) Function. The 81R #1(2) Function can
used to recognize that the ROCOF has exceeded also be used to activate a selected output when it
the Pickup setting. times out.
NOTE: Setting the Pickup to a minimum value of Save/Cancel — The Save selection saves the
0.2 Hz/sec is recommended when using 81R #1(2) ROCOF (Bus Voltage) Function Dialog
nominal frequencies. Screen settings either to an open file or to the target
MBTS. Cancel, returns the user to the previous
This function is typically used for load shedding. If a open screen.
load that is causing the frequency to change quickly
can be disconnected, then a transfer may still be
possible. The 81R Function is automatically disabled
during unbalanced faults and other disturbances.
4–81
M‑4172 Instruction Book
Figure 4-81 81R #1(2) ROCOF (Bus Voltage) Function Dialog Screen
Figure 4-82 81R #1(2) ROCOF (Bus Voltage) Inputs/Outputs Selection Dialog Screen
4–82
System Setup and Setpoints – 4
Figure 4-83 displays the settings for the ISSL There are three Blocking Input sources:
(ISSLogic) function. The settings for the ISSL #2 • Blocking Inputs
through 6 are the same as the ISSL #1. • Block System Status
The MBTS provides six logic functions and • Blocking using the Communication Point
associated ISSLogic. The logic functions can be
used to allow external devices to trip through the The activation state of the input function selected
MBTS, providing additional target information for the in the Initiating Function can be either Timeout
external device. More importantly, these functions (Trip) or Pickup. The desired Time Delay for security
can be used in conjunction with ISSLogic to expand considerations can be obtained in the ISSLogic
the capability of the MBTS by allowing the user to Function Time Delay setting.
define customized operating logic.
The ISSLogic Function can be programmed to
Enable/Disable — The top right corner of each perform any or all of the following tasks:
ISSlogic tab includes a command button that will • Change the Active Setting Profile
disable or enable the function. This selection allows
the ISSL #1 (ISSlogic) to be disabled (or enabled) • Close an Output Contact
independent from the ISSL #2, #3, #4, #5 and #6. • Be activated for use as an input to another
ISSLogic Function
ISSLogic Settings and Logic Functions
• Initiate a transfer
ISSlogic includes six Initiating Input sources:
• Block a transfer
• Initiating Outputs
• Initiating Function Time Out
• Initiating Function Pickup (including the
ISSLogic Functions themselves)
• Initiating Inputs
• Initiating System Status
• Initiation using the Communication Point
4–83
M‑4172 Instruction Book
4–84
System Setup and Setpoints – 4
4–85
M‑4172 Instruction Book
10. If desired select the Initiating System 12. Select the desired Logic Function (AND/
Status button. ISSLogic® will display the OR/NOR/NAND). The selected Logic
Initiating System Status Selection screen Function (AND/OR/NOR/NAND) will
(Figure 4-87). apply only to the Initiating Function
Timeout Selection(s), Initiating Function
11. Select the desired Initiating System Pickup Selection(s) and Initiating System
Status selection(s), then select OK. Status Selection(s). The selected Logic
Function will ignore the functions and
System Status that are not selected.
4–86
System Setup and Setpoints – 4
13. If desired select the "Initiate via 20. Select the desired Block System
Communication point". Select Check Status(s), then select OK.
Box.
21. Select the desired Blocking Inputs/Block
14. If desired select Initiating Input button. System Status Logic Function (AND/
ISSLogic® will display the Initiating Input OR). The selected Blocking Inputs/
Selection screen (Figure 4-88). Blocking System Status Logic Function
(AND/OR) will apply only to the selected
Blocking Input(s) and Blocking System
Status Selection(s); the selected Logic
Function will ignore the Inputs and
System Status that are not selected.
22. If desired select the "Block via
Communication point". Select Check
Box.
23. Select the desired Time Delay.
NOTE: The DO/RST Timer is described in detail
in the "Dropout/Reset Timer Feature"
later in this section.
4–87
M‑4172 Instruction Book
Change Active Profile (ISSLogic) When an ISSLogic® Function is enabled and the
To change the active profile simply select the logic becomes "true" the ISS# is always activated
desired profile. The "Not activated" selection means so it could be used as an initiating input to any other
the profile will not be changed. If the presently active ISSLogic.
profile is selected as the profile to which to change
Since there are six ISSLogic Functions per setting
there is effectively no change since it would change
profile, depending on the number of different MBTS
to the same profile.
settings defined, the scheme may provide up to 24
different logic schemes.
4–88
System Setup and Setpoints – 4
PU Time Delay
Setting (30) Seal in Delay
Seal in Delay E
PU Time Delay Timing Dropout Delay
B
Output
A C D
ISSLogic Functions (1 - 6) D
C F
PU Status
Reset Reset
Reset Delay
B Delay Delay
PU Time Delay
10 Cycles
Setting (30)
A G
Seal In
PU Time Delay Timing Timer
E
Output
4–89
4–90
ISSLogic Functions
Initiating Outputs This section of ISSLogic
used to activate the desired Output
This section of ISSLogic initiates
the Function Operation
Outputs
Transfer
Initiating Function
Programmable
function(s) Initiate
(Incl. ISSLogic Selectable And/Or
Transfer
and System
Status) Programmed
Time Delay
Selectable And/Or/Nor/Nand
ISSLogic # N
Activated
Initiating Inputs
Programmable
Inputs and AUX
Input
Selectable And/Or
Initiate Via
Blocking Inputs
This section of ISSLogic is used
to Block the Function Operation
Programmable
Inputs and AUX
Input
Selectable And/Or
Block Via
Communication
Point
Installation – 5
5 Installation
5.1 General Information................................................................. 5–1
5–1
M‑4172 Instruction Book
5.2 Mechanical/Physical
Dimensions
17.50 ± .12
.00
[44.5 +.30 - .00]
9.97
[25.32]
19.00
[48.26]
18.31 0.35
[46.51] [0.89]
2.25 5.21
M-4172 DIGITAL MOTOR [13.23]
BUS TRANSFER SYSTEM [5.72]
1
2
3
4
5
6
7
8
1.48
[3.76]
0.40 [1.02] X 0.27
NOTE: Dimensions in brackets are in centimeters. [0.68] Slot (4X)
5–2
18.31
[46.51]
0.32
[0.81]
[0.71]
NOTE: Dimensions in brackets are in centimeters.
M-4172 (HORIZONTAL)
TOLERANCE: .XX ± .015
5–3
Installation – 5
M‑4172 Instruction Book
5.65
[14.40]
5.59
[14.20] 0.03
Actual [0.076]
2.25 1.67
0.35 [5.72] [4.24] 2.25 1.67
[0.89] [5.72] [4.24]
0.28 [0.71]
Dia. (4X)
STATUS
19.00
[48.26]
OUTPUTS
OUT 1 OUT 3 OUT 5 OUT 7
18.31
OUT 2 OUT 4 OUT 6 OUT 8
[46.51]
17.5
[44.45]
ACTUAL
17.68
[44.91]
EXIT ENTER
STATU S
R ES ET
PS 2 PS 1
B R KR BRK R
O PE N O PE N
S O URC E SO URC E
1 2
BRKR BRK R
C LO S E D C LO S E D
SY S D IA G /
OK T IM E
SY NC
CO M 1
M-4172 M-4205
DIGITAL MOTOR
BUS
FASTTRANSFER SYSTEM
TRANSFER SYSTEM
RR
Integrated Synchronizing Systems
B EC
EC K W IIT
TH
CO
O.. I NC .
EL
E L EC T R
RIIC
Ma d e in U .S .A .
9.97 10.20
[25.32] [25.91]
19.00
[48.26]
5–4
Installation – 5
Insulation Coordination
5.3 External Connections
Sensing Inputs: 60 V to 140 V, Installation Category
8 WARNING: The protective grounding terminal IV, Transient Voltages not to exceed 5,000 V.
must be connected to an earthed ground
anytime external connections have been made Torque Requirements
to the unit. • Terminals 1–34: 12.0 in-lbs
8 WARNING: ONLY DRY CONTACTS must be Terminals 35–63: 8.0 in-lbs, minimum,
•
connected to inputs (terminals 5 through 10 and 9.0 in-lbs, maximum
with 11 common because these contact inputs
are internally wetted. Application of external s CAUTION: Over torquing may result in terminal
voltage on these inputs may result in damage damage.
to the units.
8 WARNING: Do not open live CT circuits. MBTS Outputs
Live CT circuits should be shorted prior to All outputs are shown in the de-energized state for
disconnecting CT wiring to the M-4172. Death standard reference. MBTS standard reference is
or severe electrical shock may result. defined as the non-asserted state, or power to the
MBTS is removed.
To fulfill requirements for UL and CSA listings,
terminal block connections must be made with No. Output contacts OUTPUT1 through OUTPUT4
22‑12 AWG solid or stranded copper wire inserted in are predefined to Trip and Close the Source 1 and
an AMP #324915 (or equivalent) connector, and wire Source 2 breakers and are closed for a defined pulse
insulation used must be rated at 75° C minimum. length (pulse length can be programmed from 15 to
30 Cycles). The power supply alarm output contact
Power Supply (form 'b') and the self-test alarm output contact (form
'c'), and one output contact for lockout or blocking
If the M-4172 is equipped with the optional second status (form 'c'). These outputs are predefined.
power supply (Figure 5-4), the power source may
be the same or two different sources. The three programmable output contacts OUTPUT5
through OUTPUT7 (two form 'a' and one form 'c'),
the Lockout/Block alarm output contact OUTPUT8
(form 'c'), the power supply alarm output contact
(form 'b') and the self-test alarm output contact (form
58 59 60 61 62 63
'c'), are all rated as per IEEE C37.90 for tripping.
(Make 30 A for 0.2 seconds, carry 8 A, break 6 A
@ 120 Vac, break 0.5A @ 48 Vdc; 0.3A @ 125 Vdc;
0.2A @ 250 Vdc with L/R = 40 mSec.)
5–5
M‑4172 Instruction Book
5–6
Installation – 5
B EC K W IT H E L ECT R IC C O . INC .
VA
6 19 0 118 t h AV E NO .
L A RG O , F L 3 3 7 7 3
VAB S
727- 5 4 4 - 23 26
VC RS 4 8 5
COM 3 4
VCA
respectively.
+
43
6 5
R 0 IN6
44
A
-
T 1 IN5 6
V
0
V VA
52/S2
a/b IN4
7 3.
O
L 5
VAB
S
O
IN3 8 terminal must be connected to an
T
A
G
0
/
6
U
R IN2 9 earthed ground any time external
E 0
45 C
E 52/S1
a/b IN1
1 connections have been made to the
Danger! Contact avec les terminaux peut causer un choc electrique
10
H
&
unit.
z 2
46
VB 2
(
N
O 47
VBC
INPUTS !
M
I
IN
N
A
48
VC RT N 11 NOTE: All relays are shown in the de-
energized state, and without power
L
VCA
49
(
12
50
P/S
13
applied to the relay.
VA
SELF TEST
VAB 14
51
52
BUS 15
NOTE: The self-test relay is energized
when the relay has performed all
VB
16
VBC
53
L B
OL
17 self-tests successfully.
54 CO
VC KC 8 18
OK
VCA U I
55
TN
NOTE: The Lockout Blocking Output is
19
G
1A S
R
C
U
56
I S1
O
U
R
20
energized when any Lockout/
Blocking condition occurs. See
C
7 21
(
MODEL: M-4172
A RN 57 E
1
T RO
E E M
Lockout/Blocking section for details.
5 0 Hz
22
D
(
N S
58 O
T U
I S2 R 23
C
5A 59 E
2
6
6 0 Hz
24
OUT-
60 PUTS QQ NOTE: The power supply relay (P/S) is
+
25
18- 5 6
85-265 PS 2 5 energized when the power supply
FIRMWARE: D-0229
61 - 26
is functioning properly.
62 27
+
18- 5 6
PS 1 4
S E RIA L NO .
85-265 CLOSE
63 - S2
28
29
3
TRIP
30
S2
F3 F1
31
2
PS 2 CLOSE
32
S1
3 A MP,
F4 33
250V, F2
(3A B) 1
TRIP
34
S1
PS 1
5–7
M‑4172 Instruction Book
M-4172 M-4172
VA VA
39 45
38 44
VB VB
41 47
40 46
VC VC
43 49
42 48
1 57 59
51 50 53 52 55 54
52S1 56 58 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
5–8
Installation – 5
38 44
VB VB
41 47
40 46
VC VC
43 49
42 48
1 57 59
51 50 53 52 55 54
52S1 56 58 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
5–9
M‑4172 Instruction Book
M-4172 M-4172
VAB VAB
39 45
38 44
VBC VBC
41 47
40 46
VCA VCA
43 49
42 48
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C respectively.
5–10
Installation – 5
38 44
VB VB
41 47
40 46
VC VC
43 49
42 48
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
2 VT-S1, VT-S2 and VT-B are single phase VTs. They all must be connected to the same
phase, either Phase A-To-Ground, Phase B-To-Ground or Phase C-To -Ground.
5–11
M‑4172 Instruction Book
M-4172 M-4172
VAB VAB
39 45
38 44
VBC VBC
41 47
40 46
VCA VCA
43 49
42 48
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
2 VT-S1, VT-S2 and VT-B are single phase VTs. They all must be connected to the same
phase, either Phase A-To-Phase B, Phase B-To-Phase C or Phase A-To -Phase C.
5–12
Installation – 5
38 44
VB VB
41 47
40 46
VC VC
43 49
42 48
1 57 VA VB VC 59
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
2 VT-S1 and VT-S2 are single phase VTs. They both must be connected to the same
phase, either Phase A-To-Ground, Phase B-To-Ground or Phase C-To -Ground.
5–13
M‑4172 Instruction Book
38 44
VBC VBC
41 47
40 46
VCA VCA
43 49
42 48
51 50 53 52 55 54
56 58
52S1 52S2
B B
C C
MOTOR MOTOR
1 CT-S1 and CT-S2 are single phase CTs. They both must be connected to the same phase,
either Phase A, Phase B or Phase C.
2 VT-S1 and VT-S2 are single phase VTs. They both must be connected to the same
phase, either Phase A-To-Phase B, Phase B-To-Phase C or Phase A-To -Phase C.
5–14
Installation – 5
5–15
M‑4172 Instruction Book
3 up 4 up Run Mode
3 up 4 down Initialize EEPROM to default* See CAUTION below.
3 down 4 up Initialize Access Codes and Communication*
3 down 4 down Factory Use
2 up Flash Update Disable (Factory Default)
2 down Flash Update Enable
1 up Redundant Power Supply Unit (Optional)
1 down Single Power Supply Unit (Standard M‑4172 PS)
* After power up the OK LED remains extinguished and the Diagnostic LED will illuminate
when operation has been satisfactorily completed.
▲▲ CAUTION: A loss of calibration,setpoints and configuration will occur when the EEPROM is initialized to
default.
5–16
Installation – 5
Dip Switch
J46
J18
J22 J21
J5 J20
J61
J60
5–17
M‑4172 Instruction Book
ISScom Installation and Setup The MBTS and ISScom Communications and
ISScom runs with the Microsoft Windows® 98 Analysis Software are shipped from the factory
operating system or later. ISScom only supports with the same default communication parameters.
communication using the MODBUS protocol. Therefore, it may not be necessary to set up
communication parameters.
ISScom is available on CD-ROM, or may
be downloaded from our website at www. In order for ISScom to communicate with the MBTS
beckwithelectric.com using direct serial connection, a serial "null modem"
cable is required, with a 9-pin connector (DB9P)
The M-3871 ISScom Communications and Analysis for the MBTS, and an applicable connector for the
Software is not copy-protected. For more information computer (usually DB9S or DB25S). Pin-outs for a
on your specific rights and responsibilities, see the null modem adapter are provided in Appendix B,
licensing agreement enclosed with your software or Communications.
contact Beckwith Electric.
Activating initial communications using default
Hardware Requirements communication parameters is accomplished as
follows:
ISScom will run on any IBM PC-compatible
computer that provides at least the following: 1. Verify that a direct serial connection
between the PC hosting ISScom and the
• 8 MB of RAM target MBTS COM1 (front) is in place.
• Microsoft Windows 98 or later
2. Select the ISScom icon (Figure 5-15)
• CD-ROM drive from the Becoware folder or Desktop.
• one serial (RS-232) communication port The ISScom Main Screen (Figure 3-5)
is displayed.
• pointing device (mouse)
3. Select the COMM menu item. ISScom
will display the Communication Dialog
Installing ISScom
Screen (Figure 3-7).
1. Insert software CD-ROM into your drive.
4. If the computer is connected through
An Auto-Install program will establish either an RS-232 port or RS-485 port
a program folder (Becoware) and perform the following:
subdirectory (ISScom). After installation,
the ISScom program item icon (see a. Select Serial COM Port from the
Figure 5-15) is located in Becoware. The Comm Device selection.
default location for the application files b. Select the PC Comm Port that is
is on drive C:, in the new subdirectory connected to the MBTS.
"ISScom" (C:\Becoware\ISScom).
c. Select Open Com. This action
attempts to establish communication.
5–18
Installation – 5
COM1 PARITY
none odd even
5–19
M‑4172 Instruction Book
5–20
Installation – 5
Setup Procedure
NOTE: Setup Record forms are available in
Appendix A, Setup Record Forms, to
record settings for future reference.
5–21
M‑4172 Instruction Book
5–22
Testing – 6
6 Testing
6.1 Power On Self Test ................................................................. 6–1
Testing Overview
6.1 Power On Self Test
For the purposes of site acceptance and verifying
the MBTS hardware is operating properly and is
Equipment Required
connected correctly, Beckwith Electric recommends
the following tests: • If the MBTS permanent power supply
source is not available, then a portable
• Power on Self Tests power supply (>50 W) matched to the
• Diagnostic Tests installed MBTS power supply (indicated
by check box on rear of unit Figure 6-1)
• Metering Tests will be required.
The M‑4172 has an available redundant
PS2 Power Supply. To determine if the
PS2 Power Supply is present inspect the
two squares in the box on the rear of the
box under the PS2 connections. If neither
of these two boxes is checked then the
PS2 supply is not installed and only PS1
needs to be connected. If PS2 is present
then please note that PS1 and PS2 can
have different voltage inputs.
• Digital Multi Meter
58 59 60 61 62 63
+ - +-
Figure 6-1 Power Supply Connection
6–1
M‑4172 Instruction Book
QQ NOTE: The following test is written assuming 5. The following sequence of actions will
both power supplies are present. If the take place:
PS2 Power Supply is not present then
connections to it are not required and the a. Power supply, PS1 and PS2 (optional
PS2 LED will not light during the tests. PS), LED(s) will illuminate.
b. The power supply contact will
energize (open) (Terminals 12 and
To perform the Power On Self Test proceed as 13)
follows:
c. The internal hardware test executes.
1. Verify the power supply contact is in the d. All LEDs will illuminate for
normal state. (Closed) approximately 1 second.
2. Determine if the permanent power supply e. As each Power On Self Test routine
source is connected and available. is completed satisfactorily the HMI
8 WARNING: Applying power to the MBTS will display an "X".
may cause equipment connected to the MBTS
6. Upon successful completion of all Power
to operate.
On Self Tests:
3. If the permanent power supply source is a. The PS1 and PS2 (optional PS)
connected and available, then energize LEDs will remain illuminated.
the power supply (The Power On Self
Test will automatically begin) and go to b. All other LEDs will extinguish.
Step 5. c. The diagnostic contact will energize.
4. If the permanent power supply source d. The SYS OK LED will flash (or
is not connected or is unavailable, then remain illuminated as programed in
proceed as follows: the diagnostic menu).
a. Ensure that the permanent power e. The unit will display the Model
supply source breaker is open Number, Firmware Version, Current
and applicable safety tagging is CT Rating, Nominal Frequency
complete. Rating and the Serial Number.
b. Disconnect and tag/identify the f. The BREAKER CLOSED and
permanent power supply source BREAKER OPEN LEDs will be
connections (Figure 6-1) from illuminated for Source 1 based on
the MBTS (60/62 HOT and 61/63 the position of the breaker position
NEUTRAL). contacts (52a and/or 52b) connected
to the Status Inputs 1 and 4.
c. Connect the portable power supply to
terminals (62 Hot and 63 Neutral for 6. Verify the power supply contact is
PS1; 60 Hot and 61 Neutral for PS2 energized (open).
optional redundant power supply).
7. Restore any connections that may have
8 WARNING: Applying power to the MBTS been disconnected in Step 4.
may cause equipment connected to the MBTS
to operate. Torque Requirements
d. Energize the por table power • Terminals 1– 34: 7.5 in-lbs, minimum, and
supply. The Power On Self Test will 8.0 in-lbs, maximum
automatically begin. Terminals 35 – 63: 8.5 in-lbs, minimum,
•
and 9.0 in-lbs, maximum
QQ NOTE: A Power On Self Test failure is indicated
by no display or SYSTEM HALT ERROR
CODE XX. If a failure occurs, then stop
any further testing and contact the
factory.
6–2
Testing – 6
6–3
M‑4172 Instruction Book
4. Ensure that the Diagnostic Menu is • Output relay energizes (On position)
selected to OUTPUT (Upper Case). • Appropriate RED OUTPUT LED
illuminates.
OUTPUT TEST (RELAY)
If testing all output relays, then press EXIT to return
OUTPUT input led module to the output relay selection menu, then repeat Steps
button disp 6, 7 and 8 for each output relay.
com1 com2 com3 clock
led cal factory
9. The DMM can now be used to verify that
the output relay contact is in the operated
If OUTPUT is not selected (Upper or ON position. The readings should
Case), then use the Right/Left arrow be the opposite of the initial reading
pushbuttons to select OUTPUT. determined in Step 2.
5. Press ENTER, the MBTS will display the 10. When output relay testing is complete,
following: then restore all output relays to their
de-energized or OFF positions listed in
R
ELAY NUMBER Table 6-1 and press EXIT to return to the
Diagnostic Menu.
1
11. If all Diagnostic Testing is complete,
6. Select the Output Relay (from Table 6-1) then exit the diagnostic menu by
to be tested, utilizing the Up/Down arrow pressing EXIT, PRESS EXIT TO EXIT
pushbuttons. DIAGNOSTIC MODE is displayed, then
press EXIT a second time.
6–4
Testing – 6
If INPUT is not selected (Upper 9. If testing all inputs, press EXIT to return
Case), then use the Right/Left arrow to the input selection menu, then repeat
pushbuttons to select INPUT. Steps 5, 6, 7 and 8 for each input.
4. Press ENTER. The following is displayed:
Input Number Common Terminal Terminal
I
NPUT NUMBER 1 (52/S1 a/b) 11 10
1 2 11 9
3 11 8
5. Select the MBTS Input (from Table 6-2)
to be tested utilizing the Up/Down arrow 4 (52/S2 a/b) 11 7
pushbuttons. 5 11 6
6. Press ENTER. The following is displayed 6 11 5
for the selected input:
Table 6-2 Input Contacts
INPUT NUMBER 1
C
IRCUIT OPEN
6–5
M‑4172 Instruction Book
Front Panel Status LED Test 5. When Status LED testing is complete
The Front Panel STATUS LED TEST menu enables press EXIT to return to the Diagnostic
the user to check the front-panel Status LED Menu.
individually. 6. If all Diagnostic Testing is complete,
then exit the diagnostic menu by
1. If the MBTS is already in the Diagnostic pressing EXIT, PRESS EXIT TO EXIT
Mode, then go to Step 2. DIAGNOSTIC MODE is displayed, then
If the MBTS is NOT in the Diagnostic press EXIT a second time.
Mode, then enter the MBTS diagnostic
mode by performing the steps described
Module LED Test
in the Entering MBTS Diagnostic Mode
section of this chapter, then go to Step 2. The MODULE LED TEST menu allows the user to
check each M-3976 Module LED individually.
2. Ensure that the Diagnostic Menu is
selected to LED (Upper Case). 1. If the MBTS is already in the Diagnostic
Mode, then go to Step 2.
STATUS LED TEST
If the relay is NOT in the Diagnostic
output input LED module Mode, then enter the MBTS diagnostic
button disp mode by performing the steps described
com1 com2 com3 clock in the Entering MBTS Diagnostic Mode
led cal factory
section of this chapter, then go to Step
2.
If LED is not selected (Upper Case), then 2. Ensure that the Diagnostic Menu is
use the Right/Left arrow pushbuttons to selected to MODULE (Upper Case).
select LED.
3. Press ENTER. LED #1 (RELAY OK) MODULE LED TEST
illuminates and the following is displayed: output input led MODULE
button disp
STATUS LED TEST
com1 com2 com3 clock
LED NUMBER 1 = ON
led cal factory
4. If testing all Status LEDs, press the right If MODULE is not selected (Upper
arrow pushbutton to toggle through the Case), then use the Right/Left arrow
remaining LEDs illustrated in Figure 6-2. pushbuttons to select MODULE.
The PS1 and PS2 LEDs are tested in the 3. Press ENTER. MODULE LED #1 lights
System Power On Tests. and the following is displayed:
MODULE LED TEST
LED NUMBER 1 = ON
4. If testing all MODULE LEDs, press the
right arrow pushbutton to toggle through
the remaining MODULE LEDs illustrated
in Figure 6-3.
5. When Module LED testing is complete
press EXIT to return to the Diagnostic
Menu.
6–6
Testing – 6
1. If the relay is already in the Diagnostic
Mode, then go to Step 2.
If the relay is NOT in the Diagnostic Mode,
then enter the relay diagnostic mode by
performing the steps described in the EXIT ENTER
6–7
M‑4172 Instruction Book
D
ISPLAY TEST
output input led module
button DISP
com1 com2 com3 clock
led cal factory
6–8
Testing – 6
6–9
M‑4172 Instruction Book
Clock ON/OFF
3 4
This feature provides the user with the ability to
either start or stop the clock.
1. If the MBTS is already in the Diagnostic
Mode, then go to Step 2.
If the MBTS is NOT in the Diagnostic
Mode, then enter the MBTS diagnostic
mode by performing the steps described
in the Entering MBTS Diagnostic Mode
section of this chapter, then go to Step 2.
2. Ensure that the Diagnostic Menu is
selected to CLOCK TEST (Upper Case).
C
LOCK TEST
Figure 6-6 RS‑485 2‑Wire Testing
output input led module
7. Press a key on the PC keyboard, then button disp
verify the following: com1 com2 com3 CLOCK
led cal factory
a. The character pressed is displayed
temporarily on the relay display.
If CLOCK is not selected (Upper
b. The character pressed is displayed Case), then use the Right/Left arrow
on the PC monitor. pushbuttons to select CLOCK.
8. When communication has been verified, NOTE: ‘80’ will be displayed in the seconds place
press EXIT, the following is displayed: when the clock is stopped.
COM3 ECHO TEST 2WIRE
3. Press ENTER, the following is displayed:
-
DONE-
a. If the clock is already running the
9. Press EXIT to return to the DIAGNOSTIC following will be displayed and will
Menu. continue to update.
10. Close the COM port on the PC, and exit C
LOCK TEST
the terminal program.
0
1-Jan-2003 01:01:01
11. If all Diagnostic Testing is complete,
then exit the diagnostic menu by b. If the clock was NOT running the
pressing EXIT, PRESS EXIT TO EXIT following will be displayed:
DIAGNOSTIC MODE is displayed, then
press EXIT a second time. C
LOCK TEST
0
1-Jan-2003 01:01:80
C
LOCK TEST
C
LOCK STOP
C
LOCK TEST
0
1-Jan-2003 01:01:80
6–10
Testing – 6
6–11
M‑4172 Instruction Book
6–12
Testing – 6
50 HZ CALIBRATION
50_HZ
6–13
M‑4172 Instruction Book
39
38
41
40
43
42
45
44
47
46
49
48
51
50
53
52
55
54
57
56
59
58
6–14
Appendix – A
This Appendix contains photocopy–ready forms The Setup System Settings Record Form (page
for recording the configuration and settings of the A–3) reproduces the Setup System menus. For each
M‑4172 Motor Bus Transfer System (MBTS). The function or setpoint, refer to the configuration you
forms can be supplied to field service personnel have defined using the MBTS Configuration Table,
for configuring the MBTS, and kept on file for future and check whether it should be enabled or disabled,
reference. the output contacts it will activate, and the inputs that
will block its operation.
A copy of the MBTS Configuration Table (Table A‑1)
is provided to define and record the blocking inputs The System Setpoints Transfer Settings Record
and output configuration. For each function, check Form (page A–5) allows recording of the specific
the Enabled or Disabled checkbox. If the function values entered for each transfer. The form follows
is Enabled, then check the output contacts to be the Transfer Settings section of the System Setpoints
operated by the function, and the inputs designated dialog screen.
to block the function operation.
The System Setpoints Function Settings Record
The Communication Settings Record Form (page Forms, beginning on page A–13, allow recording
A–2) reproduces the System Communication Setup of the specific values entered for each function.
menus. This form records definition of the parameters The forms follow the Function Settings section of
necessary for communication with the MBTS. the System Setpoints dialog screen. If a function is
disabled, the input/output screens for that function
will not be displayed.
A–1
M‑4172 Instruction Book
COM 1
1200/ 2400
Baud Rate 9600
4800/ 9600
Stop Bit 1 or 2 1
COM 2
1200/ 2400
Baud Rate 9600
4800/ 9600
Stop Bit 1 or 2 1
COM 3 / RS485
Stop Bit 1 or 2 1
ETHERNET SETTINGS
Remote/Local Control
A–2
Appendix – A
Firmware Version – –
Nominal Frequency 50 Hz or 60 Hz –
CT Secondary Rating 1A/5A –
SYSTEM SETTINGS
S1/S2 CT Configuration
S1 and S2 CT Connected to
Yes or No No
Rear Terminals
A–3
M‑4172 Instruction Book
VT and CT Ratios
Latched Outputs
Outputs 1 2 3 4 5 6 7 8
– – – – –
Pulsed Outputs
Outputs 1 2 3 4 5 6 7 8
– – – – –
A–4
Appendix – A
Profile
SETPOINT PROFILE
Simultaneous/
Transfer Mode Sequential
Sequential
A–5
M‑4172 Instruction Book
Profile
S1 52a (Input 1) or
Breaker Status Inputs: S1 52a (Input 1)
S1 52b (Input 1)
S2 52a (Input 4) or
S2 52a (Input 4)
S2 52b (Input 4)
S2 52 Service Position
Inputs 1 2 3 4 5 6
– – – –
Transfer Block #2
Inputs 1 2 3 4 5 6
– – – –
Transfer Block #3
Inputs 1 2 3 4 5 6
– – – –
A–6
Appendix – A
Profile
A–7
M‑4172 Instruction Book
Profile
Block Transfer/
Both S1 and S2 Breakers Open Block Transfer
Auto Close
A–8
Appendix – A
Profile
Blocking 1 2 3 4 5 6 FL
Inputs – –
Blocking 1 2 3 4 5 6 FL
Inputs – –
Blocking 1 2 3 4 5 6 FL
Inputs – –
A–9
M‑4172 Instruction Book
Profile
Blocking 1 2 3 4 5 6 FL
Inputs – –
A–10
Appendix – A
Profile
Blocking 1 2 3 4 5 6 FL
Inputs – –
Blocking 1 2 3 4 5 6 FL
Inputs – –
A–11
M‑4172 Instruction Book
Profile
Blocking 1 2 3 4 5 6 FL
Inputs – –
Blocking 1 2 3 4 5 6 FL
Inputs – –
Blocking 1 2 3 4 5 6 FL
Inputs – –
A–12
Appendix – A
Profile
27B – BUS PHASE UNDERVOLTAGE TRANSFER INITIATE (S1 TO S2) (#1 TO #4 STEPS)
27B #1
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
27B #2
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
27B #3
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
A–13
M‑4172 Instruction Book
Profile
27B #4
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
A–14
Appendix – A
Profile
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – Inputs
Outputs 1 2 3 4 5 6 7 8 Inputs 1 2 3 4 5 6
Initiate – – – – – Initiate
S1 BF Enable/Disable Enable
Time Delay 0 to 30 Cycles 7
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – Inputs
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – Inputs
Outputs 1 2 3 4 5 6 7 8 Inputs 1 2 3 4 5 6
Initiate – – – – – Initiate
S1 BF Enable/Disable Enable
Time Delay 0 to 30 Cycles 7
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – Inputs
A–15
M‑4172 Instruction Book
Profile
60FL
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
A–16
Appendix – A
Profile
81 #1
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
81 #2
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
Function 81 Setpoints
A–17
M‑4172 Instruction Book
Profile
81R #1
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
81R #2
Outputs 1 2 3 4 5 6 7 8 Blocking 1 2 3 4 5 6 FL
– – – – – Inputs
A–18
Appendix – A
Profile
ISSLogic #
Initiating 1 2 3 4 5 6 7 8
Outputs
A–19
M‑4172 Instruction Book
Profile
Auto Fast Transfer Delta Phase Angle OK Manual Fast/Hot Parallel Transfer Delta Phase Angle OK
Auto Fast Transfer Delta Voltage OK Manual Fast/Hot Parallel Transfer Delta Voltage OK
Auto Fast Transfer Delta Frequency OK Manual Fast/Hot Parallel Transfer Delta Frequency OK
Auto InPhase Transfer Delta Voltage OK Manual In-phase Transfer Delta Voltage OK
Auto InPhase Transfer Delta Frequency OK Manual In-phase Transfer Delta Frequency OK
Auto Fast Transfer Ready Manual Fast/Hot Parallel Transfer Ready
Transfer Ready Auto Close Initiated
Auto Transfer Enabled Manual Transfer Enabled
Auto Transfer Initiated Manual Transfer Initiated
Fixed Time Transfer Selected (60FL Condition) Hot Parallel Transfer In Process
27B#1 Bus Phase UV Transfer Initiated (S1 to S2) Hot Parallel Transfer Operated
27B#2 Bus Phase UV Transfer Initiated (S2 to S1) Auto Trip Enabled
Open Transition Transfer In Process Auto Trip Operated
Transfer Completed New Source Upper Voltage Limit Transfer Blocked
Fast Transfer Operated New Source Lower Voltage Limit Transfer Blocked
In-Phase Transfer Operated Bus VT Fuse Loss Transfer Blocked
Residual Voltage Transfer Operated Both Breakers Open Transfer Blocked
Fixed Time Transfer Operated Both Breakers Close Transfer Blocked
Fast Transfer Load Shedding Incomplete Transfer Blocked
InPhase Transfer Load Shedding Blocking After Transfer Alarm
Residual Voltage Transfer Load Shedding S1/S2 Breaker Closing Time Out Of Range
Fixed Time Transfer Load Shedding S2 Breaker Failure
Load Shedding (27B#3, 81#1, 81R#1) S2 Breaker Opened
S1 Breaker Failure S2 Breaker Closed
S1 Breaker Opened Trip S2 Breaker Command
S1 Breaker Closed Close S2 Breaker Command
Trip S1 Breaker Command Source 2 (New Source)
Close S1 Breaker Command Remote Mode
Source 1 (New Source)
A–20
Appendix – A
Profile
Initiating 1 2 3 4 5 6 FL Blocking 1 2 3 4 5 6 FL
Inputs Inputs
Auto Fast Transfer Delta Phase Angle OK Manual Fast/Hot Parallel Transfer Delta Phase Angle OK
Auto Fast Transfer Delta Voltage OK Manual Fast/Hot Parallel Transfer Delta Voltage OK
Auto Fast Transfer Delta Frequency OK Manual Fast/Hot Parallel Transfer Delta Frequency OK
Auto InPhase Transfer Delta Voltage OK Manual In-phase Transfer Delta Voltage OK
Auto InPhase Transfer Delta Frequency OK Manual In-phase Transfer Delta Frequency OK
Auto Fast Transfer Ready Manual Fast/Hot Parallel Transfer Ready
Transfer Ready Auto Close Initiated
Auto Transfer Enabled Manual Transfer Enabled
Auto Transfer Initiated Manual Transfer Initiated
Fixed Time Transfer Selected (60FL Condition) Hot Parallel Transfer In Process
27B#1 Bus Phase UV Transfer Initiated (S1 to S2) Hot Parallel Transfer Operated
27B#2 Bus Phase UV Transfer Initiated (S2 to S1) Auto Trip Enabled
Open Transition Transfer In Process Auto Trip Operated
Transfer Completed New Source Upper Voltage Limit Transfer Blocked
Fast Transfer Operated New Source Lower Voltage Limit Transfer Blocked
In-Phase Transfer Operated Bus VT Fuse Loss Transfer Blocked
Residual Voltage Transfer Operated Both Breakers Open Transfer Blocked
Fixed Time Transfer Operated Both Breakers Close Transfer Blocked
Fast Transfer Load Shedding Incomplete Transfer Blocked
InPhase Transfer Load Shedding Blocking After Transfer Alarm
Residual Voltage Transfer Load Shedding S1/S2 Breaker Closing Time Out Of Range
Fixed Time Transfer Load Shedding S2 Breaker Failure
Load Shedding (27B#3, 81#1, 81R#1) S2 Breaker Opened
S1 Breaker Failure S2 Breaker Closed
S1 Breaker Opened Trip S2 Breaker Command
S1 Breaker Closed Close S2 Breaker Command
Trip S1 Breaker Command Source 2 (New Source)
Close S1 Breaker Command Remote Mode
Source 1 (New Source)
A–21
M‑4172 Instruction Book
Profile
Dropout Timer/
DO/RST Timer Reset Timer
Reset Timer
Profile Switch
Not Activated #1 #2 #3 #4
Outputs 1 2 3 4 5 6 7 8
– – – –
No Transfer Initiate
Initiate S1 to S2 Transfer
Initiate S2 to S1 Transfer
Transfer Block
A–22
Appendix – A
Profile
Function Pickup
27B #1 27B #4 60FL 81R #1 ISSL #2 ISSL #5
27B #2 50BF #1 81 #1 81R #2 ISSL #3 ISSL #6
27B #3 50BF #2 81 #2 ISSL #1 ISSL #4
Function Timeout
27B #1 27B #4 60FL 81R #1 ISSL #2 ISSL #5
27B #2 50BF #1 81 #1 81R #2 ISSL #3 ISSL #6
27B #3 50BF #2 81 #2 ISSL #1 ISSL #4
Function Dropout
27B #1 27B #4 60FL 81R #1 ISSL #2 ISSL #5
27B #2 50BF #1 81 #1 81R #2 ISSL #3 ISSL #6
27B #3 50BF #2 81 #2 ISSL #1 ISSL #4
Input Status
Input Pickup Status Input Dropout Status
Input 1 (S1 52a) Input 1 (S1 52a)
Input 2 (86P-S1 Initiate (S1 to S2) ) Input 2 (86P-S1 Initiate (S1 to S2) )
Input 3 (Manual Transfer Initiate) Input 3 (Manual Transfer Initiate)
Input 4 (S2 52a) Input 4 (S2 52a)
Input 5 Input 5
Input 6 Input 6
FL FL
Output Status
Output Pickup 1 2 3 4 5 6 7 8
Status
Output Dropout 1 2 3 4 5 6 7 8
Status
A–23
M‑4172 Instruction Book
Profile
Oscillograph Setup
SETTING RANGE DEFAULT SETTING
Number of Records 1 to 16 6
Inputs
Trigger Inputs Trigger Dropout Inputs
Input 1 (S1 52a) Input 1 (S1 52a)
Input 2 (86P-S1 Initiate (S1 to S2) )
Input 3 (Manual Transfer Initiate)
Input 4 (S2 52a) Input 4 (S2 52a)
Input 5
Input 6
FL
Outputs
Trigger 1 2 3 4 5 6 7 8
Outputs
Oscillograph Setup
A–24
Appendix – A
Profile
OUTPUTS BLOCKING INPUTS
Function Enable Disable
1 2 3 4 5 6 7 8 1 2 3 4 5 6 FL
A–25
M‑4172 Instruction Book
Profile
OUTPUTS BLOCKING INPUTS
Function Enable Disable
1 2 3 4 5 6 7 8 1 2 3 4 5 6 FL
In-Phase
Transfer N/A – –
Res. Voltage
Transfer N/A – –
Fixed-Time
Transfer N/A – –
In-Phase
Transfer N/A – –
Res. Voltage
Transfer N/A – –
Hot Parallel
Transfer N/A – –
A–26
Appendix – A
Profile
OUTPUTS BLOCKING INPUTS
Function Enable Disable
1 2 3 4 5 6 7 8 1 2 3 4 5 6 FL
A–27
M‑4172 Instruction Book
Profile
OUTPUTS BLOCKING INPUTS
Function Enable Disable
1 2 3 4 5 6 7 8 1 2 3 4 5 6 FL
ISSL – ISSLogic®
A–28
Communications: Appendix – B
B Communications
B–1
M‑4172 Instruction Book
NOTE: Also see Table 5-1, Table 5-2 and Figure 5-14.
B–2
Communications: Appendix – B
PC Master
Echo Cancel On
25 pin or
9‑25 pin Straight‑Through Cable
REP
OFF
T R
FOC FOC
FOC FOC
R T R T R T
B–3
M‑4172 Instruction Book
‑ + ‑ +
PC Master
B(‑) 200 Ω*
A(+)
Twisted
RS‑232 to RS‑485 2‑wire
converter or RS‑485 PC Card
▲ CAUTION: Due to the possibility of ground potential difference between units, all units should be mounted
in the same rack. If this is not possible, fiber optics with the appropriate converters should be used for isolation.
NOTE: Each address on the network must be unique. Only the last physical slave on the network should
have the termination resistor installed. This may be completed externally or using a jumper internal
to the unit. See Section 5.4, Circuit Board Switches and Jumpers.
B–4
Self-Test Error Codes Appendix – C
1
2 Battery backed RAM test fail
3 EEPROM write power-up fail
4 EEPROM read back power-up fail
5 Dual port RAM test fail
6 EEPROM write calibration checksum fail
7 EEPROM write setpoint checksum fail loss of power
8 EEPROM write setpoint checksum fail loss of battery backed RAM
9 DMA checksum/physical block fail
10 Oscillograph Memory Test fail
11 DSP external program RAM fail
12 DSP A/D convert fail
13 DSP ground channel fail
14 DSP reference channel fail
15 DSP PGA gain fail
16 DSP DSP<-> HOST interrupt 1 fail
17 DSP DSP -> HOST interrupt 2 set fail
18 DSP DSP -> HOST interrupt 2 reset fail
19 DSP program load fail
20 DSP not running run mode code
21 DSP not running primary boot code
22 DSP DPRAM pattern test fail
23 EEPROM write verify error
26 WARNING calibration checksum mismatch warning
27* WARNING setpoint checksum mismatch warning
28 WARNING low battery (BBRAM) warning
29 Supply/mux PGA running test fail
*If a system Setpoint has been changed and power is removed from the MBTS within 5 minutes, an Error Code 27 will be
displayed when power is applied to the MBTS. This condition is normal and the Error Code 27 should be reset.
C–1
M‑4172 Instruction Book
34 Restart Error
35 Interrupt Error
36 Trap Error
37 Calibration running check fail
38 Ethernet Board not running (Warning)
50 Stack Overflow
51 Setpoint Write Overflow
C–2
Self-Test Error Codes Appendix – C
C–3
M‑4172 Instruction Book
C–4
Appendix – D
D–1
M‑4172 Instruction Book
Page 1
D–2
Appendix – D
Input Pickup: 1 4
Output Pickup: 2 3 7
Transfer : 4
Page 2
D–3
M‑4172 Instruction Book
Input Pickup: 4
Output Pickup: 1 4 7
System Status: Auto Fast Transfer Delta Phase Angle OK,
Auto Fast Transfer Delta Voltage OK,
Auto Fast Transfer Delta Frequency OK,
Auto In-Phase Transfer Delta Voltage OK,
Auto In-Phase Transfer Delta Frequency OK,
Transfer Ready,
Auto Transfer Enabled,
Auto Transfer Initiated,
27B #1 Bus Phase UV Transfer Initiated (S1 to S2),
Open Transition Transfer In Process,
Fast Transfer Operated,
S1 Breaker Opened,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Phase Angle OK,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Manual Fast/Hot Parallel Transfer Delta Frequency OK,
Manual In-Phase Transfer Delta Voltage OK ,
Manual In-Phase Transfer Delta Frequency OK,
Manual Transfer Enabled,
S2 Breaker Opened,
Close S2 Breaker Command,
Source 2 (New Source),
Remote Mode,
Page 1
D–4
Appendix – D
Transfer : 1
Input Pickup:
Output Pickup: 1 4 7
System Status: Auto Fast Transfer Delta Phase Angle OK,
Auto Fast Transfer Delta Voltage OK,
Auto Fast Transfer Delta Frequency OK,
Auto In-Phase Transfer Delta Voltage OK,
Auto In-Phase Transfer Delta Frequency OK,
Auto Transfer Enabled,
Auto Transfer Initiated,
27B #1 Bus Phase UV Transfer Initiated (S1 to S2),
Transfer Completed,
Fast Transfer Operated,
S1 Breaker Opened,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Phase Angle OK,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Manual Fast/Hot Parallel Transfer Delta Frequency OK,
Manual In-Phase Transfer Delta Voltage OK ,
Manual In-Phase Transfer Delta Frequency OK,
Manual Transfer Enabled,
Blocking After Transfer Alarm ,
S2 Breaker Closed,
Close S2 Breaker Command,
Source 2 (New Source),
Remote Mode,
Input Pickup:
Output Pickup: 2 3 7
Page 2
D–5
M‑4172 Instruction Book
Page 3
D–6
Appendix – E
This Appendix contains Illustrations of the print‑ready screens provided by the ISScom® Sequence of Events
Recorder Print Summary and Print Detail features.
E–1
M‑4172 Instruction Book
Page 1
E–2
Appendix – E
1 06/22/2015, 13:01:49.523
Current Profile: 1
Input Pickup: 1
Output Pickup: 1
Input Drop:
Output Drop:
System Status: Transfer Ready,
Open Transition Transfer In Process,
S1 Breaker Closed,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Delayed In-Phase Transfer Delta Voltage OK ,
Manual In-Phase Transfer Delta Frequency OK,
Manual Transfer Enabled,
Manual Transfer Initiated,
S2 Breaker Opened,
Source 2 (New Source),
Local Mode,
2 06/22/2015, 13:05:03.548
Current Profile: 1
Input Pickup: 1
Output Pickup: 1
Input Drop:
Output Drop:
System Status: Transfer Ready,
Open Transition Transfer In Process,
S1 Breaker Closed,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Delayed In-Phase Transfer Delta Voltage OK ,
Manual In-Phase Transfer Delta Frequency OK,
Manual Transfer Enabled,
Page 1
E–3
M‑4172 Instruction Book
3 06/22/2015, 13:06:55.715
Current Profile: 1
Input Pickup: 1
Output Pickup: 1
Input Drop:
Output Drop:
System Status: Transfer Ready,
Open Transition Transfer In Process,
S1 Breaker Closed,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Delayed In-Phase Transfer Delta Voltage OK ,
Manual In-Phase Transfer Delta Frequency OK,
Manual Transfer Enabled,
Manual Transfer Initiated,
S2 Breaker Opened,
Source 2 (New Source),
Local Mode,
4 06/22/2015, 13:07:58.548
Current Profile: 1
Input Pickup: 1
Output Pickup: 1
Page 2
E–4
Appendix – E
Input Drop:
Output Drop:
System Status: Transfer Ready,
Open Transition Transfer In Process,
S1 Breaker Closed,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Delayed In-Phase Transfer Delta Voltage OK ,
Manual In-Phase Transfer Delta Frequency OK,
Manual Transfer Enabled,
Manual Transfer Initiated,
S2 Breaker Opened,
Source 2 (New Source),
Local Mode,
5 06/22/2015, 13:08:41.336
Current Profile: 1
Input Pickup: 1
Output Pickup: 1
Input Drop:
Output Drop:
System Status: Transfer Ready,
Open Transition Transfer In Process,
S1 Breaker Closed,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Delayed In-Phase Transfer Delta Voltage OK ,
Manual In-Phase Transfer Delta Frequency OK,
Manual Transfer Enabled,
Manual Transfer Initiated,
S2 Breaker Opened,
Source 2 (New Source),
Local Mode,
Page 3
E–5
M‑4172 Instruction Book
6 06/22/2015, 13:09:19.182
Current Profile: 1
Input Pickup: 1
Output Pickup: 1
Input Drop:
Output Drop:
System Status: Transfer Ready,
Open Transition Transfer In Process,
S1 Breaker Closed,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Delayed In-Phase Transfer Delta Voltage OK ,
Manual In-Phase Transfer Delta Frequency OK,
Manual Transfer Enabled,
Manual Transfer Initiated,
S2 Breaker Opened,
Source 2 (New Source),
Local Mode,
7 06/22/2015, 13:10:24.986
Current Profile: 1
Input Pickup: 1
Output Pickup: 1
Input Drop:
Output Drop:
System Status: Transfer Ready,
Open Transition Transfer In Process,
S1 Breaker Closed,
Trip S1 Breaker Command,
Device ON,
Manual Fast/Hot Parallel Transfer Delta Voltage OK,
Delayed In-Phase Transfer Delta Voltage OK ,
Page 4
E–6
Appendix – E
Page 5
E–7
M‑4172 Instruction Book
E–8
Appendix – F
F–1
M‑4172 Instruction Book
F–2
Appendix – F
IN-PHASE TRANSFER
ENABLE
F–3
M‑4172 Instruction Book
F–4
Appendix G
Appendix G includes the recommended storage Layup of the M-4172 requires verifying that the
parameters, periodic surveillance activities and system clock is stopped. The steps necessary to
layup configuration for the M‑4172 Motor Bus verify system clock status are as follows:
Transfer System.
▲▲ CAUTION: Do not use the diagnostic mode in
relays that are installed in an active protection
Storage Requirements (Environment) scheme.
The recommended storage environment parameters
for the M-4172 are: For units with the optional HMI panel:
• The ambient temperature where the 1. Verify that the Power Supply (PS) fuses
M‑4172 is stored is within a range of 5° are installed.
C to 40° C 2. Determine the unit power supply rating
• The maximum relative humidity is less by observing the check box below the
than or equal to 80% for temperatures up PS terminals on the rear of the unit.
to 31° C, decreasing to 31° C linearly to 3. Apply power to the unit consistant with
50% for relative humidity at 40° C. the rating determined in Step 2 (see
• The storage area environment is free Section 5.3 , External Connections). The
of dust, corrosive gases, flammable unit will enter the selftest mode.
materials, dew, percolating water, rain and 4. When the selftests are complete, then
solar radiation. press ENTER to begin main menu.
5. Press the right arrow pushbutton until
Storage Requirements (Periodic Surveillance SETUP UNIT is displayed.
During Storage)
6. Press ENTER to access the SETUP
The M-4172 power supply contains electrolytic
UNIT menu.
capacitors. It is recommended that power be applied
to the relay (PS1 and optional PS2 redundant power 7. Press the right arrow pushbutton until
supply when installed) every three to five years for DIAGNOSTIC MODE is displayed.
a period of not less than one hour to help prevent 8. Press ENTER. A reset warning will be
the electrolytic capacitors from drying out. displayed:
G–1
M‑4172 Instruction Book
10. Press the right arrow pushbutton until 4. Install M-3871 ISScom® Communications
the following is displayed: and Oscillograph Analysis Software (see
Section 5.5, ISScom Communications
C
LOCK TEST and Analysis Software Installation) on
a PC that includes the following:
CLOCK led cal factory
• Microsoft WindowsTM 98 Operating
11. Press ENTER. The following is displayed: System or above
• Equipped with a serial port
C
LOCK TEST
0
3-JAN-1998 09:00:00.000 5. Connect a null modem cable from COM1
of the relay to the PC serial port.
12. If the clock is running, press ENTER to 6. Open communications with the relay
stop the clock. The following is displayed: utilizing Section 5.6, Activating Initial
Local Communications.
C
LOCK TEST
7. Select System/Setup/Set Date/Time
-
CLOCK STOP- from the menu bar. ISScom will display
the "Set Date/Time" dialog screen Figure
QQ NOTE: When the relay clock is stopped, the 3-15.
seconds will be displayed as 80.
8. Verify that "Start Real-Time Clock" is
13. Press ENTER and verify the relay clock displayed, then proceed as follows:
is stopped. A display similar to the a. If "Star t Real-Time Clock" is
following is shown with the seconds displayed, then select "Save" and
stopped: go to Step 9.
b. If "Stop Real-Time Clock" is
C
LOCK TEST displayed, then select "Stop Real-
0
3-JAN-09:01:80.000 Time Clock" and then select "Save".
14. When the clock has been verified to 9. Close communications with the unit by
be stopped, then press EXIT until the selecting "Comm" from the menu bar
following message appears: and then select "Exit".
10. Disconnect the null modem cable and
PRESS EXIT TO
then remove power from the unit. The
EXIT DIAGNOSTIC MODE
unit can now be placed in storage.
16. Remove power from the unit. The unit Maintenance Requirements
can now be placed in storage. The M-4172 Motor Bus Transfer System does not
require any maintenance over the length of its
service life. However, the unit includes diagnostic
For units without the optional HMI panel: features that provide the means to functionally test
1. Verify that the Power Supply (PS) fuses each element of the Motor Bus Transfer System. The
are installed. M-4172 also includes the capability to test inputs,
outputs and metering quantities of the interfacing
2. Determine the unit power supply rating system application. Chapter 6, Testing contains the
by observing the check box below the individual tests and procedures that are available to
PS terminals on the rear of the unit. be integrated into the user’s periodic Surveillance/
3. Apply power to the unit consistent with Testing program.
the rating determined in Step 2 (see
Section 5.3 , External Connections). The
unit will enter the selftest mode.
G–2
Appendix – H
H Index
A B
Accessing Switches, 5-15 B-0970, 5-15, 5-17
Activating Initial Local Communications, 3-1, 5-1, Blanking, 2-1
5-18, G-2 Block System Status, 4-83, 4-87:4-88
Active Profile, 2-14, 3-30, 4-87:4-88 Blocking
Alphanumeric Display, SP-15, 1-2, 2-1 After Transfer Time, SP-9, 4-40
Application, SP-4, SP-23:SP-24, 1-1:1-2, 1-5, 1-7, Inputs Selection, 4-54, 4-56:4-57, 4-59, 4-63:4-
4-1, 4-12, 4-71:4-72, 5-5:5-7, 5-18, 5-20, 6-5, G-2 71, 4-75, 4-77, 4-87
Arrow Pushbuttons, 2-1, 4-3:4-4, 4-6:4-10, 4-14,
Breaker
6-3:6-11, 6-13
Closing Time Deviation, SP-9, SP-14, 4-39
ATS, 3-8, 4-48
Failure
Auto Calibration, 1-3, 2-4, 6-1, 6-3, 6-13
I, 4-76
Auto Fast Transfer Ready
Initiate Inputs, 4-75:4-76
Output Selection, 4-43
Logic Diagran, 4-76
Outputs, 4-43
Status
Auto Transfer
Inputs, SP-10, SP-14, 4-27, 4-36, 4-41, 4-77
Block, 4-51
LED Input Configurations, 2-2
Mode, 4-48
LEDs, 2-2
Auto Trip Save, 4-71
Trip Option, SP-5, 4-71
Automatic
Bus
Fixed Time Transfer Save, 4-59
Phase Undervoltage Transfer Initiate Inputs,
In-Phase Transfer Save, 4-56
4-73:4-74
Residual Voltage Transfer Save, 4-57
Voltage Frequency Function Inputs, 4-80
Automatic Transfer VT
Block Input Settings, 4-51 Configuration Selection, 4-25
Initiation, 4-52 Fuse Loss, SP-4, SP-6, 4-45, 4-79
Settings Fast Transfer, 4-53 Fuse-Loss Function Inputs, 4-79
Settings Fixed Time Transfer, 4-58
Settings In-Phase Transfer, 4-55
Settings Residual Voltage Transfer, 4-56:4-57
Settings Setup, 4-48:4-52
Trip Settings, 4-72
H–1
M‑4172 Instruction Book
H–2
Appendix – H
H–3
M‑4172 Instruction Book
H–4
Appendix – H
J Manual Transfer
Block Input Settings, 4-61
Jumpers, 4-8, 4-13, 5-1, 5-15, B-1, B-4 Initiate Input Settings, 4-62
Mode, 4-60:4-61
L Save, 4-62
Large Induction Motor, 1-8 Settings Fast Transfer, 4-62:4-63
Latched Outputs Selection, 4-26:4-27 Settings Hot Parallel Transfer, 4-68:4-69
Layup, SP-17, 1-2, G-1 Settings In-Phase Transfer, 4-64:4-65
LED, SP-13:SP-14, 2-2, 2-4, 2-9:2-10, 3-11, 3-32, Settings Residual Voltage Transfer, 4-66:4-67
4-1, 4-5, 4-7:4-8, 4-27, 5-16, 6-2:6-11, 6-13, G-2 Settings Setup, 4-61
Load Shedding MBTS
Output Selection, 4-45:4-47 Front Panel, 1-4, 2-8, 2-10:2-13, 2-15, 2-17, 3-13,
Outputs, 4-45:4-47 4-60, 5-19:5-20
Time Delay, SP-7:SP-8, 4-47, 4-57:4-59, 4-66 Outputs, 5-5
Local Setpoints, 3-8
Button, 3-1 Setup System, 4-24
Control, SP-3, SP-15, 2-1, 2-4, 2-9:2-10, 3-1, 3-3, Mechanical, SP-17, 1-1, 2-7, 5-1:5-2, 5-4
3-14 Message Menu Flow, 2-3
Manual Initiate Time Delay, 4-40 Metering
Mode, 2-4, 2-8:2-10, 3-1, 4-40 Current Input Configuration, 6-14
Modem, 4-18, 4-20 Test Setup, 6-12
Logic Functions, 4-83 Tests, 6-1, 6-12
Voltage Input Configuration, 6-14
M Miscellaneous Setup, 3-32, 4-5
M-3976 Status Module, SP-3, SP-15, 2-2, 6-7 Modems, 4-11, 4-18, B-1
M-4172 Module LED Test, 2-4, 6-6
Circuit Board, 5-15, 5-17 Monitor Status, 2-17, 3-11, 3-31, 4-3
Horizontal Front Panel, 2-3 Motor Bus Transfer System, SP-1:SP-2, SP-4,
1-1:1-2, 1-5, 2-1, 4-1, 4-12, 4-36, 4-71, 5-1, 5-21,
Machine Interface Module, 2-1, 6-7 6-13, A-1, B-1, G-1:G-2
Main Menu Flow, 2-4 MTS, 4-60
Main-Tie-Main Application Example, 4-72 Multiple Systems Addressing Using
Manual Fast Transfer Communications-Line Splitter, 4-12
Blocking Inputs Selection, 4-63:4-64
Save, 4-64 N
Manual Hot Parallel Transfer, 3-14, 4-44, 4-68, 4-70 New
Manual In-Phase Transfer, 4-64, 4-66 Command, 3-4
Manual Operation, 1-1, 2-1, 2-6, 3-34 System, 3-4
Manual Residual Voltage Transfer Save, 4-68 User Access Code Sent, 4-3
H–5
M‑4172 Instruction Book
O R
Off Dialog Box, 2-11, 3-3 Rate Of Change Of Frequency, SP-3, SP-11, 1-10,
One Phase Grounded VT Three-Line Connection 3-17, 4-81
Diagram, 4-30, 5-9 Read Data From System, 3-4, 3-6, 3-31
Open Recorder Partitions, 4-22
Command, 3-4 References, 1-11
Delta Three-Line Connection Diagram, 4-35, 5-14 Remote Manual Initiate Time Delay, 4-40
Order of Possible Open Transition Transfer MBTS, Replacement Fuses, 5-5
1-11 Reset
Oscillograph Buttons, 3-1
Analysis Software, SP-15, 1-3:1-4, 3-17, G-2 Delay Timer Logic Diagram, 4-89
Manual Trigger Command, 3-29
Residual Voltage
Records Cleared, 3-29
Limit, SP-2, SP-7:SP-8, 4-47, 4-57, 4-66
Setup Sent, 4-22
Transfer Blocking Inputs Selection, 4-57, 4-67:4-
Output 69
Contacts, SP-3, SP-10, SP-13, SP-15:SP-16,
Retrieve Oscillograph Record, 3-28
2-17, 3-7, 4-36, 5-5, 6-4, A-1
ROCOF, SP-11, 4-73, 4-81:4-82
Counters, 2-12, 3-34
RS-232, SP-3, SP-15, 3-1, 3-3, 4-11:4-13, 4-20,
Relay Test, 6-4
5-18, 6-12, B-3
Relays, 2-10, 6-4
RS-485, SP-3, SP-15, 4-11, 5-18, B-4
Outputs Selection, 4-26:4-27, 4-47, 4-73:4-76,
4-79:4-80, 4-82, 4-85
S
Overview of Manual Transfer Methods, 2-6
S1 BF Source, 4-77:4-78
P S2
BF Source, 4-77:4-78
Panel Mount Cutout Dimensions, SP-27, 5-3
Breakers Open, 4-49
PC Modem, 4-18
CT Configuration Selection, 4-26
Phase-Ground VT Three-Line Connection Diagram,
4-32, 5-11 VT Configuration Selection, 4-25
Phase-Phase VT Three-Line Connection Diagram, Save As Command, 3-4
4-33, 5-12 Secondary Metering, 2-8, 2-10:2-11, 2-15:2-16,
Phasor Diagram, 2-17, 3-11, 3-14:3-15 3-11:3-13, 3-16:3-17, 3-22, 3-29, 4-27, 4-39, 5-20
Physical Dimensions, 5-1:5-2, 5-4 Select
Power On Self Test, 6-1:6-2, 6-12 Active Profile, 2-14, 3-30
Power Supply Connection, 5-5, 6-2 Waveforms, 3-38
Pre-Commissioning Checkout, 5-1, 5-20 Self Test, SP-14, 1-2, 3-32, 6-1:6-2, 6-4, 6-12
Primary Metering, 2-15, 3-11:3-12, 3-16 Sequence of Events
Print Setup Command, 3-4 Dropout I, 3-25
Printed, SP-28, 3-38, 5-15 File Summary, 3-24
Profile, 2-14, 2-18, 3-6, 3-28, 3-30, 4-20, 4-83, Pickup I, 3-25
4-87:4-88, A-5:A-26
Record Cleared, 3-25
Pulsed Outputs Selection, 4-27
Recorder Download, 2-18, 3-22:3-23
H–6
Appendix – H
H–7
M‑4172 Instruction Book
H–8
Declaration of Conformity Appendix – I
I Declaration of Conformity
DECLARATION OF CONFORMITY
( in accordance to ISO/IEC 17050-1:2004 )
The manufacturer hereby declares under our sole responsibility that the M-4172 product conforms to the following product standard
as of July 25th, 2006 in accordance to Directive 2004/108/EC for equipment incorporated into stationary installations:
BS EN 60255-26:2005
Electromagnetic compatibility ( EMC )
Requirements for measuring relays and protection equipment
Electromagnetic Immunity
1 MHz Disturbance
IEC 60255-22-1:2005
Fast Transients 5ns/50ns Bursts @ 5kHz for 15ms 300ms for 1 min.
2kV power supply lines and earth 2kV signal data and control lines
EN 60255-22-4:2002
Surge 1Kv Line to Line coupling, 2Kv Line to Earth coupling power supply lines
IEC 60255-22-5:2002
DC voltage interruptions
IEC 60255-11:1979
EN 61010-1: 2001 Safety requirements for electrical equipment for measurement, control, and
laboratory use Part 1. General requirements European Safety Directive
Manufacturers Contact:
Manager of Engineering
6190 118th Ave North
Largo, FL 33773-3724
Tel ( 727 ) 544-2326
I–1
This Page Left Intentionally Blank
Legal Information
Patent Indemnification
The Seller shall not be liable for any property
The units described in this manual are covered by damages whatsoever or for any loss or damage
U.S. Patents, with other patents pending. arising out of, connected with, or resulting from
Buyer shall hold harmless and indemnify the Seller, this contract, or from the performance or breach
its directors, officers, agents, and employees from thereof, or from all services covered by or furnished
any and all costs and expense, damage or loss, under this contract.
resulting from any alleged infringementof United In no event shall the Seller be liable for special,
States Letters Patent or rights accruing thereform or incidental, exemplary, or consequential damages,
trademarks, whether federal, state, or common law, including but not limited to, loss of profits or
arising from the Seller’s compliance with Buyer’s revenue, loss of use of the equipment or any
designs, specifications, or instructions. associated equipment, cost of capital, cost of
purchased power, cost of substitute equipment,
facilities or services, downtime costs, or claims or
All rights reserved by Beckwith Electric Co., Inc. No reproduction may be made without prior written approval
of the Company.
This Page Left Intentionally Blank
BECKWITH ELECTRIC CO., INC.
6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A.
PHONE (727) 544-2326 • FAX (727) 546-0121
marketing@beckwithelectric.com
www.beckwithelectric.com
ISO 9001:2015