301 / 303 / 304

Differential pressure switches 381 / 384

 Good repeatability  High static pressure 


 Set point adjuster with locking device 
 Weatherproof or flameproof housing 
 Overtravel stop  Robust design 

Style 301 in GK flameproof enclosure Style 301 in GM weatherproof enclosure

Series 300 Pressure Difference Switches are designed and pressure capability. The sensing element is mounted
made to the latest standards to comply with current external to the switch mechanisms which are of stainless
international philosophy of process instrumentation. The steel for ardous atmospheres and high humidity. Enclosures,
series is compact , easy to install and features high sensitivity sensing element and switching modes can be combined
over the entire adjustable range together with very high static to offer the variety needed to suit the different applications.

General specifications
Enclosure Scale Accuracy ± 5% FSR (Note 6)
GM GM style aluminium pressure die Switching Element Instrument quality SPDT microswitch
cast, weatherproof to IP67 (Notes 10 & 11)
GA4 GA style 304 stainless steel casting, Switching differential Fixed or Wide band adjustable, refer
weatherproof to IP66 tables ‘A’ & ‘B’.
GA6 GA style 316 stainless steel casting, Max. Working Pressure 110 bar for 301, 303 & 381
weatherproof to IP66 250 bar for 304 & 384
GK GK style aluminium pressure die 50 bar for B1K & 80 bar for B2K
cast, weatherproof to IP66 and Ambient Temperature (–)25°C to (+)60°C
flameproof to group IIC as per IS/ Max. Process Temp. 110°C. For higher temperatures use
IEC 60079 (Note 1) longer impulse lines. (Note 15)
GR GR style aluminium pressure die Ask for piping nomogram #441184-4
cast, weatherproof to IP66 and Process Connection 1/4" NPTF standard. Adaptors for
flameproof to Gr.IIC (Note 1) other sizes optional
Ranges Several standard ranges between Electrical Connection 1/2" NPTF standard
3 mbar to 15 bar Dual entry on request.
Sensor 316L SS Diaphragm Mounting Back panel/wall/Field. Vertical
Wetted parts 304 SS or 316 SS or 316L SS position only
Repeatability ±1% FSR (Note 4) Conformity Generally to BS 6134:1991
Ordering matrix

ENCLOSURE
GM style aluminium pressure die cast, weatherproof to IP67 –––––––––––––––––––– GM
GA style 304 stainless steel casting, weatherproff to IP66 ––––––––––––––––––––––– GA4
GA style 316 stainless steel casting, weatherproff to IP66 ––––––––––––––––––––––– GA6
GK style aluminium pressure die cast, weatherproof to IP66 and flameproof to
group IIC as per IS/IEC 60079 –––––––––––––––––––––––––––––––––––––––––––––– GK
GR style aluminium pressure die cast, weatherproof to IP66 and flameproof to
group IIC as per IS/IEC 60079 –––––––––––––––––––––––––––––––––––––––––––––– GR

MODEL
Basic differential pressure switch having fixed non-adjustable switching
differential actuated by a stainless steel diaphragm. –––––––––––––––––––––––––––––––– 301
Same as 301 but with auxiliary mechanism permitting switching differential
adjustment over a wide band (not available with GR enclosure). –––––––––––––––––––––– 303
Same as 301 but suitable for higher static pressure upto 250 bar. ––––––––––––––––––––– 304
A variant of series 301, employs twin levers each operating a SPDT microswitch
actuated by a single sensor through a unique linkage thereby providing
two independent adjustable set points, each with its own setting scale,
spring and switch. Minimum separation between setpoints must be more than
sum of on-off differentials or 10% of FSR whichever is higher.
(Not available with GR enclosure) ––––––––––––––––––––––––––––––––––––––––––––– 381 / 384

SENSOR AND WETTED PARTS


316L SS diaphragm with 304 SS wetted parts ––––––––––––––––––––––––––––––––––––––––––– 04
316L SS diaphragm with 316 SS wetted parts –––––––––––––––––––––––––––––––––––––––––––– 02
316L SS diaphragm with 316L SS wetted parts ––––––––––––––––––––––––––––––––––––––––– OL
Nitrile diaphragm with 304SS wetted parts for applications with pressure reversal, MWP 40 bar –– B4
Nitrile diaphragm with 316 SS wetted parts for applications with pressure reversal, MWP 40 bar – B2

RANGE CODE : Refer Table–1 –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– 

SWITCH CODE AND RATING : Refer Table–2 –––––––––––––––––––––––––––––––––––––––––––––––––––– 

ELECTRICAL ENTRY : Refer Table–3 –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– 

OPTIONS
Ammonia service (EPDM ‘O’ ring mandatory) ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– SA
Oxygen service (Viton ‘O’ ring mandatory) ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– SO
NACE preparation (available only with ‘OL’ wetted parts) ––––––––––––––––––––––––––––––––––––––––––––––––––– SC
Nuclear service ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– SN
Blow out disc ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– S8
Special repeatability ±0.5% (not available in ranges C6D, B7K and P8B) § ––––––––––––––––––––––––––––––––––– SR
Chemical seal (not available in ranges C6D and E1D) –––––––––––––––––––––––––––––––––––––––––––––––––––– S1
Seal ‘O’ ring – Viton (MWT 205°C, not available in B4 and B2 wetted parts) ––––––––––––––––––––––––––––––––––– OV
Seal ‘O’ ring – EPDM (MWT 130°C, not available in B4 and B2 wetted parts) –––––––––––––––––––––––––––––––––– OE
Optional scale accuracy ±2% (not available in GR) –––––––––––––––––––––––––––––––––––––––––––––––––––––––– S10
CE conformity (not applicable for GR enclosure) –––––––––––––––––––––––––––––––––––––––––––––––––––––––––– CE

§ Not available with chemical seal


Table–1 : RANGE CODE & AVAILABILITY Table 3 : ELECTRICAL ENTRY

RANGE Single Entry Dual Entry


RANGE 301 / 304 303 381 / 384
CODE Size 
C6D 3 to 25 mbar  ×  GM/GA GK/GR GM/GA GK/GR

E1D 5 to 120 mbar    1/2" NPTF B B N N


E8D 50 to 350 mbar    3/4" NPTF 
. . C --- O ---
G5B 0.1 to 1.5 bar    M20 × 1.5 . D D P P
J0B 0.2 to 4 bar  ×  Through Connector
B7K  0.7 to 7 bar  × 
7 pin plug # 3 --- --- ---
P8B  1.5 to 15 bar  × ×
9 pin plug # 4 --- --- ---
B1K  10 to 40 bar  × ×
 Cable gland available on request.
B2K  10 to 60 bar  × ×   Cable entry is optional through adaptor.
 55, 9, G, J, K micro switches are not available. # Available only in GM enclosure.
  Available only in 301 with 02 and 0L only.

Table–2 : SWITCH CODE, RATING & AVAILABILITY

SWITCH DC RATING IN AMPS AVAILABILITY AVAILABILITY


AC
CODE RESISTIVE INDUCTIVE OF SPDT IN OF DPDT IN
RATING
(SPDT) 220V 110V 24V 220V 110V 24V MODELS MODELS

301, 304,
D 15A 250 / 125V 0.2 0.4 2.0 0.02 0.03 1.0 301 & 304
381 & 384
301, 304,
3 15A 250 / 125V N.R. N.R. N.R. N.R. N.R. N.R. 301 & 304
381 & 384

W 15A 250 / 125V 0.3 0.5 6.0 0.05 0.1 4.0 303 303

301, 304,
4 1A 125V N.A. 0.5 0.5 N.A. 0.25 0.25 301 & 304
381 & 384

5 5A 250 / 125V 0.2 0.4 4.0 0.2 0.4 3.0 301 & 304 301 & 304

J 5A 250V N.A. N.A. 5.0 N.A. N.A. 3.0 301 & 304 301 & 304

K 1A 125V N.A. N.A. 1.0 N.A. N.A. 0.5 301 & 304 301 & 304

9 1A 115V; 400 Hz N.A. N.A. 3.0 N.A. N.A. 1.0 301 & 304 301 & 304

G N.R. N.R. N.R. 1.0 N.R. N.R. 0.25 301 & 304 301 & 304

Codes 3, D & W – For General purpose usages. Code K – Argon sealed micro switch with gold contact.
Code 4 – With Gold alloy contact. Code 9 – Hermetically sealed, inert gas filled with silver alloy contact.
Code 5 – For General purpose with DC rating. Code G – Hermetically sealed, inert gas filled with gold plated
Code J – Argon sealed micro switch with silver contact. contact.
Note : In model 381 and 384 DPDT for Individual set point is not available.

For DPDT, change switch code ‘3’ to ‘33’, ‘4’ to ‘44’, etc., while ordering
N.A. – Not Available N.R. – Not Recommended

Diaphragm chemical seals

Diaphragm chemical seals can be provided as optional extra While ordering it is important to specify ambient and process
either direct mounted or remote with capillary and threaded / temperatures, setpoint, maximum process pressure, relative
flanged connection, duly evacuated and filled with suitable elevation between connection and switch head, nature of
filling liquid. This device permits the use of differential pressure process medium and whether reactive to common filling liquids
switches for viscous / aggressive fluids and permits higher should the diaphragm seal leak into the process.
process temperatures. Switching lag will be present, when
pressure changes rapidly.
Switching differential data

TABLE : A — GM / GA Enclosures
On-off Differential in mbar
Range Fixed Adjustable
Range
Code Models 301 / 304 Model 381/4 Model 303
D/3 4 5 J/K 9/G D /3 / 4 W
C6D 3 to 25 mbar 6 6 6 10 10 7.5 ---
E1D 5 to 120 mbar 5 6 10 12 12 20 45 to 70
E8D 50 to 350 mbar 12 15 20 30 30 40 70 to 200
G5B 0.1 to 1.5 bar 60 60 85 120 120 250 300 to 900
J0B 0.2 to 4 bar 175 200 350 500 500 400 ---
B7K 0.7 to 7 bar 300 350 500 --- --- 600 ---
P8B 1.5 to 15 bar 800 800 1350 --- --- --- ---

TABLE : B — GK Enclosure
On-off Differential in mbar
Range Fixed Adjustable
Range
Code Models 301 / 304 Model 381/4 Model 303
D/3 4 5 J/K 9/G D/3/4 W
C6D 3 to 25 mbar 10 10 10 17 17 12 ---
E1D 5 to 120 mbar 8 10 16 20 20 30 50 to 70
E8D 50 to 350 mbar 20 25 40 50 50 55 90 to 200
G5B 0.1 to 1.5 bar 100 100 140 200 200 350 425 to 900
J0B 0.2 to 4 bar 300 340 520 900 900 600 ---
B7K 0.7 to 7 bar 500 600 750 --- --- 1000 ---
P8B 1.5 to 15 bar 1350 1350 1750 --- --- --- ---
Note: For B1K and B2K differential values consult sales.

TABLE : C — GR Enclosure
On-off Differential in mbar
Range Models 301 / 304
Range
Code
D/3 4 5 J/K 9/G
C6D 3 to 25 mbar 10 12 10 15 15
E1D 5 to 120 mbar 8 10 20 20 20
E8D 50 to 350 mbar 15 20 30 40 40
G5B 0.1 to 1.5 bar 80 90 115 200 200
J0B 0.2 to 4 bar 250 300 500 750 750
B7K 0.7 to 7 bar 375 450 650 --- ---
P8B 1.5 to 15 bar 1100 1300 1600 --- ---

On-off differential values for DPDT switching,  In case of adjustable on-off differential models the
DPDT (2 × SPDT) multiplication factor is to be applied only to the lower
limit of the differential values. Upper limit values remain
 For style GM/GA enclosures apply a multiplication factor
unchanged.
of 1.3 to values in Table–A.
 For instruments with chemical seal, switching differentials
 For style GK enclosure apply a multiplication factor of 1.2 to
will be higher. Apply a Multiplication factor of 1.3 for SPDT
values in Table–B.
and 1.5 for DPDT to values given in table for GM housings
 For style GR enclosures apply a multiplication factor of and apply a multiplication factor of 1.2 for SPDT and 1.5 for
1.3 to values in Table–C. DPDT to values of table for GK housings.
Notes

1. Gr.IIC of IS/IEC 60079–1 is equivalent to NEC CL.1, DIV.1, 11. Contact life of microswitches are 5 × 105 switching cycles
Gr.A&B. for nominal load. To quench DC sparks, use diode in
parallel with inductance, ensuring polarity. A ‘R–C’
2. Style GM/GA is weatherproof only if all entries and joint network is also recommended with ‘R’ value in Ohms
faces are properly sealed. Style GK/GR is weatherproof equal to coil resistance and ‘C’ value in micro Farads
only if cover ‘O’ ring is retained in position and flameproof equal to holding current in Amps.
only if proper FLP cable gland is used. It is recommended
to procure cable glands along with style GK/GR 12. Model 301 can be supplied with Nitrile diaphragm for
instruments to avoid neglect of it during installation. applications where pressure reversal is envisaged.

3. Intrinsic Safety (Exi) — Differential Pressure switches 13. All differential pressure switches are calibrated by applying
are classified as simple apparatus as they neither pressure to HI port, venting LO port to atmosphere.
generate nor store energy. Hence differential pressure Inspection will also be limited to such a practice.
switches in weatherproof (GM / GA) enclosures also may
be used in intrinsically safe systems without certification 14. Ambient temperature range: All models are suitable for
provided the power source is certified IS. Because of operating within a range of ambient temperature from
the low voltages and currents it is recommended to use (–) 25°C to (+) 60°C provided the process does not freeze
gold contact and / or sealed contacts. within this range. Below 0°C, precautions should be
taken in humid atmospheres to prevent frost formation
4. Accuracy & Repeatability are not different for all blind inside the instrument from jamming the mechanism.
differential pressure switches. A shift of ±2% may be Occasional excursions beyond this range are possible
observed in setpoint when pressure falls from full static but accuracy might be impaired. The microswitch is the
pressure. Settings will also shift with varying temperature. limiting factor which should never exceed the limits
(–) 50°C to (+) 80°C.
5. The instrument is calibrated in the mounting position
depicted in the drawing. Mounting in any other direction 15. Fluid Temperature: A Differential Pressure switch when
will cause a minor range shift, especially in low and connected to the process is not subjected to through
compound ranges. Ranges above 1 bar will not flow and therefore is not fully exposed to the fluid
experience this shift. temperature. Use of adequate length of impulse piping
will greatly reduce excessive heating of the sensing
6. A Differential Pressure switch is a switching device and element. For example connection of 7.5 cm of 12 mm
not a measuring instrument — eventhough it has a scale dia impulse piping will reduce water temperature of 100°C
with ±5% FSR accuracy to assist setting. For this reason, to 65°C at an ambient temperature of 50°C. Ask factory
Test Certificates will not contain individual ON-OFF for piping nomogram #441184–4 for different
switching values at different scale readings. Maximum temperatures.
differential obtained alone will be declared, besides other
specifications. 16. Ensure that impulse pipework applies no stress on
sensing element housing and use spanners to hold
7. Select working range of the instrument such that the set pressure port / housing when connections are made.
value lies in the mid 35% of the range i.e., between 35%
and 70% of range span. 17. Custom built instruments are available for special service
requirements under Special Engineering Category.
8. For switching differential values please refer respective
Differential table. Switching differentials furnished are 18. For less rigorous applications models 306 / 386 with
nominal values under test conditions at mid-scale and Nitrile diaphragm & Aluminium wetted parts are available
will vary with range settings and operating conditions. at lesser cost.

9. On and off settings should not exceed the upper or lower 19. Complementary instrumentation for pressure is available
range value. in 200 series.

10. DPDT action is achieved by two SPDT switches 20. Accuracy figures are exclusive of test equipment
synchronised to practical limits i.e., ±2% of FSR. Deadband tolerance on the claimed values.
for DPDT contacts are higher than that of SPDT as force
required to actuate the contacts are more. Please refer 21. All performance data are guaranteed to ±5%.
respective differential table.
Dimensions in mm

Range Codes : E1D, E8D, G5B, J0B, B7K & P8B


GM Enclosure
Surface / Wall Mounting Pipe Mounting

GK Enclosure
Pipe Mounting

Range Code : C6D only 

GM Enclosure GK Enclosure
Pipe Mounting Pipe Mounting

2" Pipe Mounting Details


Notes :
Fixing on Fixing on 1. Dimensions for Model 304 / 384 are different.
Vertical Pipe Horizontal Pipe Ask for applicable drawing.
2. For C6D range surface / wall mounting bracket
is not available.
3. Pipe mounting bracket can be used for surface /
wall mounting also.
Use 2× 3/8" × 25 long screws and nuts for
surface mounting or coach screws for
wall mounting instead of ‘U’ bolts and nuts.
Dimensions in mm contd...
GR Enclosure
Model GR 301
Range Codes : E1D, E8D, G5B, J0B, B7K, P8B
2" Pipe
Optional Cable Entry Mounting
118 140
Additional 1/2" NPTF
Cable Entry
1/2" NPTF

127

40
66 57

Low 88Ø High Pr. Conn. 64


1/4" NPTF

Range Codes : C6D


167

40
69 57

113Ø Pr. Conn.


Low High 90
1/4" NPTF

Model GR 304
Range Codes : G5B, J0B, B7K, P8B
160

51
93 77

100Ø Pr. Conn. 84


Low High 1/4" NPTF

Range Codes : E8D, E1D, C6D

174

51
77
93

126Ø Pr. Conn.


Low High 97
1/4" NPTF

This is not a contractual document. Prior notification of changes in specifications is impracticable due to continuous improvement

Switzer Process Instruments Pvt. Ltd. www.switzerprocess.co.in


REGD. OFFICE : 128, SIDCO North Phase, Ambattur Estates, Chennai 600 098 CIN : U29255TN2014PTC095662
WORKS & SALES OFFICE
128, SIDCO North Phase, Ambattur Estates, Chennai 600 050
Ph : 044–2625 2017 / 2018 / 4324 / 4991 Fax : 044–2624 8849
e-mail : works@switzerprocess.co.in; sales@switzerprocess.co.in
SALES OFFICES
DPS-301-00-01/2018

Bangalore Phone : 080–4204 4350 Mumbai Phone : 022–28575915 / 28575916


e-mail : bangalorebr@switzerprocess.co.in e-mail : mumbaibr@switzerprocess.co.in
Chennai Phone : 044–2625 2017 / 2018 / 4991 Fax : 044–26248849 New Delhi Phone : 011–42331470 / 42331478
e-mail : chennaibr@switzerprocess.co.in e-mail : delhibr@switzerprocess.co.in
Hyderabad Phone : 040–2700 6201 Pune Mobile: 020–66293361 to 3367
e-mail : hyderabadbr@switzerprocess.co.in e-mail : punebr@switzerprocess.co.in
Kolkata Phone : 033–68888819 Vadodara Phone : 0265–2322906 Fax : 0265–2331649
e-mail : kolkatabr@switzerprocess.co.in (Agent) e-mail : vadodara.ag@switzerprocess.co.in

S-ar putea să vă placă și