Seismic Loads for Liquid‐Containing Rectangular RC Tank, According ACI 350.

3‐06 , Appendix B Method
Based on 1997 Uniform Building Code Rev1.1

Project :‐ Tanque Septico rio frio celda 2 Y Designed by:‐ Armando Jose Rivero


Building :‐ Building Checked by:‐ Armando Jose Rivero
Element:‐ Element Date:‐ 30‐Jan‐20
Location:‐ Location M.A.S.

General Input :‐
tr= 0.20 m

Seismic Force
Direction of
L= 5.15 m tw= 0.30 m HL= 2.20 m Hw= 2.50 m
γL= 12.0 KN/m3

B= 5.00 m
Rectangular Tank Plan Rectangular Tank Elevation

γc= 24.0 KN/m3
fc= 28.0 N/mm2 Ec= 24870.1 N/mm2 ACI318‐08, Clause 8.5.1
g= 9.81 m/sec2

Importance factor I = 1.25 ACI 350.3‐06, Table 4.1.1(a)


Rc = 1.00 ACI 350.3‐06, Table 4.1.1(b)
Ri = 3.00 ACI 350.3‐06, Table 4.1.1(b)
SEISMIC ZONE 1
Z factor 0.075 UBC 97, TABLE 16‐I
Soil Profile  Stiff Soil
Soil Profile Type SD UBC 97, TABLE 16‐J
Na For Zone 4 only 1 UBC 97, TABLE 16‐S
Nv For Zone 4 only 1 UBC 97, TABLE 16‐T
Ca 0.120 UBC 97, TABLE 16‐Q
Cv 0.180 UBC 97, TABLE 16‐R
Ts =0.40Cv/Ca 0.600 sec UBC 97, FIGURE 16‐3

1‐Calculation the Equivalent Weight for impulsive Wi & convective Wc component:

WL = 679.8 KN  , L / HL = 2.34 ,Ww = 387.0 KN ,Wr = 138.6 KN

= 0.48 WL = 323.9 KN ACI 350.3‐06, Eq 9‐1 ,Ww perp = 190.8 KN

= 0.54 WL = 367.2 KN ACI 350.3‐06, Eq 9‐2

2‐Calculation the Height of center of gravity for impulsive hi & convective hc components:

= 0.825 m ACI 350.3‐06, Eq 9‐3 & Eq 9‐4

= 1.241 m ACI 350.3‐06, Eq 9‐5

3‐Calculation the fundamental period of oscillation of the tank for impulsive Ti & convective Tc components:

= 849.5 KN = 1.25 m = 2.60 m


,        ,

= 1.06 m , = 142410.8 KN/m ACI 350.3‐06, R9.2.4

= 0.15 sec ACI 350.3‐06, Eq 9‐11

= 5.21 = 2.74 sec ACI 350.3‐06, Eq 9‐13,14

             Seismic Loads for Liquid‐Containing Rectangular RC Tank Page 1 of 4 M.A.S ______ 


Seismic Loads for Liquid‐Containing Rectangular RC Tank, According ACI 350.3‐06 , Appendix B Method
Based on 1997 Uniform Building Code Rev1.1

Project :‐ Tanque Septico rio frio celda 2 Y Designed by:‐ Armando Jose Rivero


Building :‐ Building Checked by:‐ Armando Jose Rivero
Element:‐ Element Date:‐ 30‐Jan‐20
Location:‐ Location M.A.S.

𝟐𝚷 𝑾𝒄
𝑻𝒄 = 𝟐𝚷 , ∴ 𝑲𝒄 = (𝟐𝚷 𝟐
∗ = 196.9 KN/m
𝝎𝒄 𝒈𝒌𝒄 𝑻𝒄

             Seismic Loads for Liquid‐Containing Rectangular RC Tank Page 2 of 4 M.A.S ______ 


Seismic Loads for Liquid‐Containing Rectangular RC Tank, According ACI 350.3‐06 , Appendix B Method
Based on 1997 Uniform Building Code Rev1.1

Project :‐ Tanque Septico rio frio celda 2 Y Designed by:‐ Armando Jose Rivero


Building :‐ Building Checked by:‐ Armando Jose Rivero
Element:‐ Element Date:‐ 30‐Jan‐20
Location:‐ Location M.A.S.

4‐Calculation the total lateral impulsive force Pi & convective force Pc :

= 0.300 ACI 350.3‐06, Appendix B, Eq B‐1,2,3

= 0.096 ACI 350.3‐06, Appendix B, Eq B‐4,5

= 23.9 KN = 17.3 KN ACI 350.3‐06, Appendix B, Eq B‐6,7

= 40.5 KN = 44.0 KN ACI 350.3‐06, Appendix B, Eq B‐8,9

5‐Calculation the total Base Shaer V:
= 92.8 KN ACI 350.3‐06, Appendix B & Eq 4‐5
6‐Dynamic force distribution above base per Wall perpendicular to ground motion:

Pi Top = 0.5 KN/m2

Pi Bottom = 3.2 KN/m2

Pc Top = 2.8 KN/m2 ACI 350.3‐06, R5.3.1

Pc Bottom = 1.2 KN/m2

= 0.9 KN/m2

= 0.9 KN/m2 = 0.9 KN/m2
= 0.5 KN/m2 = 2.8 KN/m2 = 4.1 KN/m2

= 3.2 KN/m2 = 1.2 KN/m2 = 5.4 KN/m2


Wall Inertia Force Pw Impulsive Force Pi  ConvectiveForce Pc Total Seismic Force E per Wall
perpendicular to ground motion
Dynamic force distribution above base per Wall perpendicular to ground motion

7‐ Load Cominations:
Note that, the Calculated Seismic Force E above is based on Strength‐level Forces (ultimate loads).
For allowable stresses Design (ASD) Method (service loads), the design seismic forces shall be reduced by a factor of 1.4
ACI 350.3‐06, Appendix B, Clause B.5
For Ultimate Strength Design method (factored loads), follow ACI 350‐06, Clause 9.2.1 load combinations.

             Seismic Loads for Liquid‐Containing Rectangular RC Tank Page 3 of 4 M.A.S ______ 


Seismic Loads for Liquid‐Containing Rectangular RC Tank, According ACI 350.3‐06 , Appendix B Method
Based on 1997 Uniform Building Code Rev1.1

Project :‐ Tanque Septico rio frio celda 2 Y Designed by:‐ Armando Jose Rivero


Building :‐ Building Checked by:‐ Armando Jose Rivero
Element:‐ Element Date:‐ 30‐Jan‐20
Location:‐ Location M.A.S.

             Seismic Loads for Liquid‐Containing Rectangular RC Tank Page 4 of 4 M.A.S ______ 