Documente Academic
Documente Profesional
Documente Cultură
Manual
electronics
Type CPX−SF34
Type CPX−SF35
PCWORX integrated
Network protocol
PROFINET IO
Manual
570 541
en 1007NH
[748 167]
Contents and general instructions
Original . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . de
Edition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . en 1007NH
Designation . . . . . . . . . . . . . . . . . . P.BE−CPX−SF34+SF35−EN
PROFINET IO®, PHOENIX CONTACT®, PCWORX®, SPEEDCON®, TORX®, TÜV® and VDE®
are registered trademarks of the respective trademark owners in certain countries.
Contents
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII
Instructions on this description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VIII
Important user instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IX
1. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−1
2. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−1
3. Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−1
B. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B−1
Intended use
Note
The CPX−SF34/35 may be used only in combination with
CPX metal interlinking blocks.
Warning
· Use only PELV circuits as per IEC/DIN EN 60204−1 for the
electric power supply (protective extra−low voltage,
PELV).
· Also comply with the general requirements for PELV
circuits laid down in IEC/DIN EN 60204−1.
· Use only power sources that guarantee reliable
electrical isolation of the operating voltage as per
IEC/DIN EN 60204−1.
Target group
Service
E−mail: automation@phoenixcontact.com
www.profinet.com
Danger categories
This manual contains instructions on the possible dangers
which may occur if the product is not used correctly. These
instructions are marked (Warning, Caution, etc.), printed on a
shaded background and marked additionally with a picto
gram. A distinction is made between the following danger
warnings:
Warning
This means that failure to observe this instruction may
result in serious personal injury or damage to property.
Caution
This means that failure to observe this instruction may
result in personal injury or damage to property.
Note
This means that failure to observe this instruction may
result in damage to property.
Pictograms
Information:
Recommendations, tips and references to other sources of
information.
Accessories:
Information on necessary or sensible accessories for the
Festo product.
Environment:
Information on environment−friendly use of Festo products.
Text markings
Term/abbreviation Significance
AB / QB Output byte
CPX modules Common term for the various modules which can be incorporated into a
CPX terminal
EB / IB Input byte
Term/abbreviation Significance
IPC Industrial PC
I/O modules Collective term for the CPX modules which provide digital inputs and
outputs
Pneumatic interface The pneumatic interface is the interface between the modular electrical
periphery and the pneumatics
PROFINET IO Fieldbus system based on Industrial Ethernet for data exchange be
tween the system control (PLC/IPC), system controller (e.g. CPX−FEC)
and field devices (I/O devices) or drives and valve terminals; further
information: www.profibus.com/pn, www.profibus.de
QB / AB Output byte
QX / AX Digital output
Chapter 1
Contents
1. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−1
Warning
Before carrying out installation and maintenance work,
switch off the following:
compressed air supply
the operating voltage supply for the electronics/sensors
the load voltage supply for the outputs/valves
Caution
The CPX control block contains electrostatically sensitive
components.
· Therefore, do not touch any components.
· Observe the handling specifications for electrostatically
sensitive devices.
1 PROFINET−specific
network status 6
LEDs and
CPX−specific LEDs 5 1
2 Memory card
3 Mains 4
connections:
2
CPX−SF34: 2 x
push−pull RJ45
CPX−SF35: 2 x
SCRJ
3 3
4 DIL switch
(PLC boot
settings)
5 Unused, always
seal with cover
cap
Note
To ensure protection class IP65/IP67, the unused network
connections must be closed with cover caps. These must
be ordered separately (type CPX−M−AK−C, part no. 548753,
see also section 1.6).
Note
The CPX−SF34/35 must be the first module in the CPX
terminal (counted from the left).
3
2
Note
For the CPX−SF34/35, use only metal interlinking blocks
and suitable screws:
For metal interlinking blocks:
screws with metric thread.
In order to set the DIL switches and change the memory card,
first the cover must be removed.
Caution
The CPX control block contains electrostatically sensitive
components.
· Therefore, do not touch any components.
· Observe the handling specifications for electrostatically
sensitive devices.
Note
Observe the following instructions when removing or
attaching the cover:
· Disconnect the power supply before removing the cover.
· Make sure that the seal is seated correctly when
attaching the cover.
· Tighten the two fastening screws at first by hand and
then with max. 0.4 Nm.
With the DIL switches (see Fig.1/3), choose the boot settings
of the PLC:
Procedure:
1 DIL switch 1:
Boot settings
of the PLC
2 DIL switch 2:
Reserved
Note
A requirement for automatic starting of the Boot program
with AUTORUN is that there are no deviations between the
actual and nominal configuration (see section 2.4.2).
Caution
Risk of malfunctions or damage.
Inserting or removing the memory card while the power
supply is switched on can result in malfunctions of or
damage to the memory card.
· Disconnect the power supply before you insert or
remove the memory card.
Note
The memory card must always be plugged in when the
CPX−SF34/35 is started!
Replacing the memory The memory card is under a cover (see Fig.1/1). You need a
card screwdriver in order to remove or attach this cover.
Note
Components with PROFINET interfaces may be operated
only innetworks where all connected network components
are supplied with PELV power supplies or integrated power
supplies with similar protection.
Installation guidelines
www.profinet.com
Unmanaged Switches:
For small Ethernet solutions with a low network load or
minimal requirements for deterministics.
Managed switches:
Networks can also be diagnosed and controlled,
redundant paths recognised and communication
solutions segmented.
Note
In case of faulty installation or high transmission rates,
data transmission errors can occur as a result of signal
reflections and attenuations.
Causes of transmission faults may be:
incorrect screened connection
branches
transmission over long distances
unsuitable cables
Observe the cable specification!
Cable specification
CPX−SF35 2 x push−pull socket, SCRJ, Plug from Festo, type POF fibre optic cable
AIDA conforming FBS−SCRJ−PP−GS for POF Cable length:
fibre−optic cable, max.segment length
650nm, corresponding 50m between network
to IEC61754−24 participants
(corresponding to
specifications for
Ethernet networks,
ISO/IEC 11801,
PROFINET Installation
Guide)
3
2
1
8
7
5
5 Reserved
6 RD Received data
7 Reserved
8 Reserved
Metal covering FE Screening/functional earth
(Shield/functional earth, FE)
Note
To ensure protection class IP65/IP67, the unused network
connections must be closed with cover caps. These must
be ordered separately (see Tab.1/5).
Warning
· Use only PELV power circuits according to IEC/DIN
EN60204−1 (Protective Extra−Low Voltage, PELV) for the
power supply.
Also take into account the general requirements for
PELVpower circuits according to IEC/DINEN60204−1.
· Use only power sources that guarantee reliable
electrical isolation of the operating voltage as per
IEC/DINEN60204−1.
System supply and The CPX terminal is supplied with operating and load
additional supply voltage via the interlinking blocks with system and
additional power supply. Further interlinking blocks are in
preparation.
Note
The CPX−SF34/35 may be used only in combination with
CPX metal interlinking blocks.
Chapter 2
Contents
2. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−1
You can operate the CPX control block in two different ways:
Remote Controller PROFINET and Stand Alone.
TCP/IP
PROFINET
TCP/IP
Note
Every module occupies a certain number of IO bits, bytes
or words in the context of module communication. The
total number of available bytes per CPX terminal is limited
(max. 512 inputs and 512 outputs).
Also, certain functions, like status bits, reduce thenumber
of available IO bytes.
Take account of this fact for the planning of your CPX
terminal.
Analogue
Digital
PLC
Pneumatic"
Pneumatic interface"
Caution
Danger of malfunctions, damage or injuries to people
Before commissioning, ensure that the connected el
ements (e.g.actuators) do not perform any undesired or
uncontrollable movements.
Recommendation:
If the safety concept of your machine/system permits,
commission the CPX terminal with both operating voltages
but without compressed air. You can then test the CPX
terminal without triggering undesired reactions.
Note
In case of deviations of the actual configuration from the
target configuration, the CPX terminal with the control
block CPX−SF34/35 does not start up in PC WORX.
Fig.2/4: With the program NetNames+: set the IP address of the CPX−SF34/35
Create new project 1. Create a new project in PC WORX: Menu [File] [New
Project...]
Bus Structure
Device Catalog
Device Details
Read in configuration 1. In the Bus Structure" window, click with the right
mouse key on the PROFINET" entry and then to the left
on Read PROFINET...".
A window is displayed with a list of the PROFINET
controllers and devices available in the network
(seeFig.2/8).
1 2 3 4
Optional: flashing 2. Use the Flashing On" function in order to identify your
CPX terminal in the network (the LEDs TP1 and TP2 of
the CPX−SF34/35 then flash simultaneously). This
function helps you with the allocation of the Device
Name. You can also use this function to test whether
there is a data connection to the CPX terminal
(seeFig.2/8).
Device name 6. Use the automatically created device name or issue your
own device name:
Device Details" window in the PROFINET Settings" tab,
a PROFINET device name for the CPX−SF34/35
(seeFig.2/11).
7. When reading in the configuration, 64 IO bytes are
automatically created
4. Pull the process data of the right window into the left
window onto the lines of the variables (marked
individually or jointly, see Fig.2/12).
Fig.2/12: Assignment of the process data to the variables of the PLC by drag & drop
ST
1 tempvar0:=NewVar1[0];
2 tempvar1:=NewVar1[1];
3 NewVar2[0]:=WORD_TO_BYTE(ONBOARD_INPUT);
Line Explanation
ST
1 Q_2_D08:=I_1_DI8;
2 PND_S1S1_OUTPUTS[0]:=I_1_DI8;
3 PND_S1S1_OUTPUTS[1]:=CPX_STATUSBITS;
4 tempvar0:=PND_S1S1_INPUTS[0];
Line Explanation
1
2 Send process data of the CPX−8DE module to the PLC via PROFINET.
Since PND_S1S1_OUTPUTS" is a byte array, access to byte 0 takes place via
PND_S1S1_OUTPUTS[0]"
Create new project 1. Click in PC WORX in the menu on [File] [New Project...]
The window New Project" is displayed.
2. For the application case Stand Alone: Click on the
CPX"tab.
In the standard case, use the prepared template:
Create the new project with a double click on
CPX−SF34..." or SF35.
If you want to use other settings than those listed in
Tab.2/3, configure your project with the Project
Wizard" (not shown here).
Resource CPX
Task DEFAULT
4. Save the project with [File] [Save Project as...]. With this
you can assign a project name.
3 2 1
Generate variables
· Repeat the last two steps in this example for the outputs
with Output#".
You have now created 8 variables each for the inputs and
outputs. In the next step, the process data of the input and
output modules of the CPX terminal are assigned to these
variables.
6. Drag the process data of the right window into the left
window onto the lines of the variables Input0" ...
Input7" (see Fig.2/14).
Fig.2/14: Assignment of the process data of the CPX−8DE module to the variables of the
PLC by drag & drop
Module no.: 0 1 2 3 4 5 6
DIL: 8A
1 2 3
1 2
1 Configuration
2 Setting of the monitoring system parameter (see section 2.7.2)
Fig.2/16: Configuration of the sample terminal from Fig.2/15
2.7 Parametrisation
1 2
Module parameters
Note
Monitoring system parameter KZS/KSA/KZV, UOUT/VAL:
The short−circuit /overload and undervoltage diagnostic
messages for the complete CPX terminal can be
suppressed using the monitoring system parameter.
The settings made separately for each module with the
CPX module parameter monitoring are not affected by the
setting of the system parameters monitoring.
Additional information on parametrisation can be found in
the CPX system manual (P.BE−CPX−SYS−..) in Appendix B.
1 2
Note
Module parameters can refer to:
Properties of the complete module
Properties of an individual channel of a module
1 Input for 1 2
1stsensor
(with default
parametrisation)
2 Parametrised
input for
2ndsensor
(see text)
Î ÎÎ
1. Sensor
2. Sensor
Fig.2/20: Application example for parametrisation of input debouncing time and signal
stretching time on the 2nd sensor
www.festo.com/fieldbus
Note
Risk of operative malfunctions or damage.
Inserting or removing the memory card while the power
supply is switched on can result in operating malfunctions
of or damage to the memory card.
· Disconnect the power supply before you insert or
remove the memory card.
Replacing the memory The memory card is under a cover (see Fig.1/1). You need a
card screwdriver in order to remove or attach this cover.
Procedure:
Chapter 3
Contents
3. Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−1
Diagnostics via The status bits are stored in Access to error messages Section 3.3
global CPX PCWORX in a global system in the PLC user program,
system variable. They supply coded independent of the
variables/ common diagnostic messages. interface and
status bits 4 additional system variables IOController.
give additional diagnostic
information.
Note
Note that the diagnostic information shown can depend on
the settings (see section 1.4.2) as well as on the
parametrisation (see section 2.7) of the CPX terminal.
1 Network−specific
NF PS
LEDs: 1
PL
NF: Network Failure TP1 SF
TP2: Link/Traffic 2
2 CPX−/controller−
specific LEDs: NF PS 2
PL
PS: Power system
TP1 SF
PL: Power load TP2 M
M: Motion/RUN
LED illuminated
ON Flickering: Data transmission
OFF
is running (traffic)
ON Both LEDs are flashing: Module location: e.g. for fault
LED flickers or
OFF Module location finding or during configuration
flashes 1)
(section 2.5)
1) Appears as lit in the case of fast flickering. The light intensity depends on data traffic.
ON
No error, operating voltage/
OFF
sensor supply applied
LED illuminated
ON
No error, load voltage None
OFF
applied
LED illuminated
ON No error
OFF
LED is off
M (Motion/RUN)
LED (yellow) Sequence Status Significance
ON
User program of the PLC is IEC−61131 runt−time system
OFF
not running successfully initialised.
LED flashing
Controller in the STOP condition
ON
User program of the PLC is Controller in the RUN condition
OFF
running
LED illuminated
1 Status bits
2 Additional diagnostic information for localisation of the error
Fig.3/2: Global system variables for diagnostic purposes
5 Short circuit/overload
6 Wire break
7 Other errors
24h = 00100100 Bit 2 and bit 5 supply logic 1 Error at input module
Short circuit/overload
0 No error
1 General diagnostics
(see description for the relevant module)
2 Short circuit/overload
3 Wire break
5 Undervoltage
6Ū8 Reserved
12 Reserved
14Ū15 Reserved
2
1
Warning
· Ensure that valves and outputs are put into a safe state
if the above−named errors occur.
An incorrect status of the valves and outputs can lead to
dangerous situations!
Note
Please note the following if the outputs are reset after PLC
stop, network interruption or disturbance:
Single−solenoid valves move to the basic position.
Double−solenoid valves remain in the current position.
Mid−position valves move to the mid position (depending
on the valve type: pressurised, exhausted or blocked).
Note
If the electronics/sensors operating voltage falls below
17.5 V, the PLC of the CPX−SF34/35 goes into the STOP
status.
After voltage recovery, the controller does not restart
automatically − even if the DIL switch for the PLC operating
status is set to AUTORUN (see Tab.1/1).
Appendix A
Contents
Network−specific characteristics
Interfaces
CPX−SF34 2 x RJ45, Cu, AIDA−conforming,
see Tab.1/2 in section 1.5.2
PLC
Programming languages AWL/IL, FB, KOP, SFC, ST (as per IEC 61131−3)
Galvanic isolation
PROFINET interfaces for UEL/SEN Galvanically isolated (transformer, 1500 V)
Galvanic isolation
PROFINET interfaces for UEL/SEN by means of fibre−optic cable
2 1
DINT_TO_INT DWORD_TO_STRING GT
DINT_TO_UDINT EQ I_BIT_IN_WORD
DIV_T_R GE INT_TO_DINT
INT_TO_STRING MAX NE
INT_TO_W_BCD MAX_SINT OR
LE MEMSET PARITY_WORD
LN MUL RD_DWORD_BY_SYM
LT MUL_T_AN RD_INT_BY_SYM
REAL_TO_BUF RS SHR
SR TOF UINT_TO_BOOL
STRING_TO_DINT TP UINT_TO_DWORD
USINT_TO_BYTE WORD_TO_SINT
USINT_TO_DINT WORD_TO_STRING
USINT_TO_DWORD WORD_TO_UDINT
USINT_TO_INT WORD_TO_UINT
USINT_TO_REAL WORD_TO_USINT
USINT_TO_SINT WR_BOOL_BY_SYM
USINT_TO_STRING WR_BYTE_BY_SYM
USINT_TO_UDINT WR_DINT_BY_SYM
USINT_TO_UINT WR_DWORD_BY_SYM
USINT_TO_WORD WR_INT_BY_SYM
W_BCD_TO_DINT WR_OUTPUT_GROUP
W_BCD_TO_INT WR_REAL_BY_SYM
W_BCD_TO_SINT WR_SINT_BY_SYM
WARM_RESTART WR_STRING_BY_SYM
WORD_TO_BOOL WR_TIME_BY_SYM
WORD_TO_BUF WR_UDINT_BY_SYM
WORD_TO_BYTE WR_UINT_BY_SYM
WORD_TO_DINT WR_USINT_BY_SYM
WORD_TO_DWORD WR_WORD_BY_SYM
WORD_TO_INT XOR
Appendix B
Contents
B. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B−1
Abbreviations , product−specific . . . . . . . . . . . . . . . . . . . XI
Additional power supply . . . . . . . . . . . . . . . . . . . . . . . . . 1−18
Application cases . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−5 , 2−10
AUTORUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−9 , 3−16
B
Boot settings of the PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−9
Brief instructions on commissioning . . . . . . . . . . . . . . . . . 2−3
C
Cables, Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−13
Commissioning, brief instructions . . . . . . . . . . . . . . . . . . 2−3
Configuration
Remote controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−14
Stand Alone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−25
Configuration differences, Starting up . . . . . . . . . . . . . . 2−10
Configuration example . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−32
Connecting
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−11
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−17
Connection technology, network . . . . . . . . . . . . . . . . . . . 1−13
CPX status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−10
D
Diag+, . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−12
Diagnosis
over PROFINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−12
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−3
via CPX status bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−10
E
Electric modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−8
Electrical connection and display elements . . . . . . . . . . . 1−4
Error characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−15
Error numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−11
F
Fail safe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−15
FDCML file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−10 , 2−40
fibre−optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−14
Function blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A−6
G
Global CPX system variables, Diagnostics . . . . . . . . . . . . 3−9
GSDML file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−10 , 2−40
I
Important user instructions . . . . . . . . . . . . . . . . . . . . . . . . . IX
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−3
Instructions on the description . . . . . . . . . . . . . . . . . . . . . VIII
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI
IP65/IP67 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−16
L
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−4
M
M LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−8
Memory card
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−10
Formatting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−9
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−40
Module parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−38
Modules of the CPX terminal . . . . . . . . . . . . . . . . . . . . . . . 2−7
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−5
N
NetNames+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−11
Network cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−13
Network connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−13
NF−LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−6
P
Parametrisation
Application example . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−39
CPX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−36
Module parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−38
PROFINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−35
System parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 2−36
PC WORX
Configuration Remote Controller PROFINET . . . . . . . . 2−14
Configuration Stand Alone . . . . . . . . . . . . . . . . . . . . . . 2−25
PELV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−17
Pictograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
Pin allocation, Network interface . . . . . . . . . . . . . . . . . . 1−15
Q
Quick instructions on startup . . . . . . . . . . . . . . . . . . . . . . 2−3
R
Remote Controller PROFINET . . . . . . . . . . . . . . . . . 2−5 , 2−14
RJ45 sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−15
S
SCRJ sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1−14
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII
Setting
Boot settings of the PLC . . . . . . . . . . . . . . . . . . . . . . . . . 1−9
T
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII
Technical data
CPX−SF34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A−3 , A−5
CPX−SF35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A−3 , A−5
Text markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X
TP1/TP2−LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−6
U
Undervoltage
Behaviour of the PLC . . . . . . . . . . . . . . . . . . . . . . . . . . 3−16
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−7