1. What is the PGC for the new controllers?


New PGC is 540. Discount schedule remains as K8.

2. What documentation is available for my customer


Document title/ Description Publication Number
Ethernet/ IP Modules Installation ENET-IN002
Instructions
Ethernet/IP Network ENET-UM001
Configuration user manual
CompactLogix Communication 1769-TD007C
Modules Specifications
Technical
1. What does 1769-AENTR do?
This product will allow distribution of 1769 I/O via the Ethernet/IP network.

2. Does 1769-AENTR support DLR?


Yes, 1769-AENTR has two Ethernet Ports and it supports DLR function.

3. Can customer set the 1769-AENTR IP address using BOOTP-DHCP server


utility?
Yes, the user could use BOOTP-DHCP server utility to set IP address (DHCP
server could be used to set IP address). Please refer to Ethernet/IP Network
configuration user manual ENET-UM001

4. Does 1769-AENTR support redundancy features with redundant ControlLogix


system?
No
5. How many 1769 I/O modules can be connected to the 1769-AENTR?
The 1769-AENTR will support one local bank and up to two banks of expansion.
A maximum of 30 1769 I/O module will be supported on each adapter.

6. How many TCP/ IP connections does 1769-AENTR support?


96.

7. What are the supported 1769 I/O modules?


The 1769-AENTR supports all 1769 I/O modules which have an existing Logix
profile. The current list of supported modules is shown in the table below:

Catalog Vendor Catalog Vendor


1769-IA8I Allen-Bradley 1769-IF16V Allen-Bradley
1769-IA16 Allen-Bradley 1769-IR6 Allen-Bradley
1769-IM12 Allen-Bradley 1769-IT6 Allen-Bradley
1769-OA8 Allen-Bradley 1769-OF2 Allen-Bradley
1769-OA16 Allen-Bradley 1769-OF4 Allen-Bradley
1769-IG16 Allen-Bradley 1769-OF4CI Allen-Bradley
1769-IQ16 Allen-Bradley 1769-OF4VI Allen-Bradley
1769-IQ16F Allen-Bradley 1769-OF8 Allen-Bradley
1769-IQ32 Allen-Bradley 1769-OF8C Allen-Bradley
1769-IQ32T Allen-Bradley 1769-OF8V Allen-Bradley
1769-IQ6XOW4 Allen-Bradley 1769sc-IF4IH Spectrum
1769-OB8 Allen-Bradley 1769sc-IF8U Spectrum
1769-OB16 Allen-Bradley 1769sc-IR6I Spectrum
1769-OB16P Allen-Bradley 1769sc-IT6 Spectrum
1769-OB32 Allen-Bradley 1769sc-OF4IH Spectrum
1769-OB32T Allen-Bradley 1769-ARM Allen-Bradley
1769-OG16 Allen-Bradley 1769-ASCII Allen-Bradley
1769-OV16 Allen-Bradley 1769-BOOLEAN Allen-Bradley
1769-OV32T Allen-Bradley 1769-HSC Allen-Bradley
1769-OW8 Allen-Bradley 1769-SM1 Allen-Bradley
1769-OW8I Allen-Bradley 1769-SM2 Allen-Bradley
1769-OW16 Allen-Bradley HI1769-xFC Hardy
1769-IF4 Allen-Bradley HI1769-xWS Hardy
1769-IF4I Allen-Bradley 1769-SDN Allen-Bradley
1769-IF4XOF2 Allen-Bradley MVI69 Prosoft
1769-IF4XOF2F Allen-Bradley HM1525 Helm
1769-IF8 Allen-Bradley
1769-IF16C Allen-Bradley

8. Does 1769-AENTR has a built-in Web Server?


Yes, 1769-AENTR has a built in web server for display of diagnostic information
and configuration of network parameter.

9. How could the customer enable the built in Web server?


The web server will be disabled by default from factory. The web server is
enabled by a manual administrative function, as described in the steps below:
1) The Module is powered up with the IP Address switches set to “000.” In
this state, the module is inoperative and the Module LED is flashing RED.
2) The switches are set to a value other than “000” or “888”
3) The module is power cycled. When the module completes power up, the
web server will be enabled with the password set to a device unique value
which consists of the 8 character ASCII representation of the 32 bit CIP
serial number assigned to the device.
4) If this administrative procedure is performed while the web server is
already enabled, the web server will continue to be enabled and the
password will have been reset to the default value for that device (CIP
serial number).
The above information can also be found in the EtherNet/IP Network
Configuration User manual: ENET-UM001

12. Does it support class 1 and class 3 messaging?

Yes. It supports up to 30 I/O connections. There is a limit of 1 exclusive owner


connection or 1 listen only connection per module depending on IO module type.
No other class 1 connection types are supported (i.e. – no rack optimized so all
direct module connections). RPI value doesn’t affect connection count. The
module supports up to 32 class 3 explicit messages directed through the adapter to
various I/O modules.

13. What version of RSLogix5000 or Studio5000 do I need?


It is supported from RSLogix5000 V20 onwards with a separate install of the
Add-On Profile. V22 and greater will automatically install the required Add-On
Profile with any install of the Studio5000.

14. How the Add-On Profile be obtained?


The Add-On profile can be downloaded from Rockwell Automation’s Product
compatibility and Download center:
https://download.rockwellautomation.com/esd/download.aspx?downloadid=addo
nprofiles

15. How to configure AOP in RSlogix5000


Step 1

Step 2

Step 3

Step 4
16. Where do I configure the User Defined safe state?
The User Defined Safe State setting will be available in the profile of the IO
module when the module is placed under the 1769-AENTR.

17. Is the 1769-AENTR adapter firmware upgradable?


Yes, the 1769-AENTR adapter is field firmware upgradable using the
ControlFlash.

18. How can I obtain the 1769-AENTR adapter firmware?


The firmware could be downloaded from the Rockwell Automation Product
compatibility and Download center:
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page

19. What is the RPI range supported by 1769 IO Modules on 1769-AENTR The
1769-AENTR support I/O modules with 2.0 to 750.0 ms RPI.

20. Does it support bridging and routing?


Yes. For example, user could reach a DeviceNet Module on 1769-SDN with
connect to the 1769-AENTR. Note that explicit unconnected messages are
supported. Class 1 and class 3 connections to modules on remote networks are
not supported.

21. How do I clear the fault on the 1769-AENTR?


Use AENTR module profile to reset the module to clear the fault.

22. How do I estimate the 1769-AENTR performance?


Please refer to the 1769-AENTR Performance Estimation Guide.