Documente Academic
Documente Profesional
Documente Cultură
Microprocessor controlled
Constant Current Regulator
Type
MCR 2.5kVA to 30kVA
Multiwire remote control
AM 06.350e-MW Edition 3.2
1
AM 06.350e-MW Edition 3.2
Safety
Regulatory safety precautions are applicable in some countries, on some
precautions sites; in absence of such legal prescriptions, the operating and maintenance
personnel should refer to the FAA Advisory Circular AC 150/5340-26
"Maintenance of Airport Visual Aid Facilities" for instructions on safety
precautions. Personnel must observe the safety regulations at all times.
While every practicable safety precaution has been incorporated in this
equipment, the following rules must be strictly observed.
Keep away
Operating and maintenance personnel must at all time observe all safety
from live regulations. Do not change neither lamps nor components or make
circuits adjustments inside equipment with the light circuit energised.
See FAA Advisory Circular AC 150/5340-26 concerning safety precautions.
Resuscitation
Operating and maintenance personnel should familiarise and keep
themselves trained in the resuscitation techniques found in the First Aid
Instruction Manual.
Electrostatic
Modules and components susceptible to electrostatic damage
Discharge
ESD Electronic modules and components should be touched only when this is
unavoidable e.g. soldering, replacement,…
A human being must first of all eliminate electronic charges from his own
body just before touching an electronic module or component.
The easiest way of discharging a human being's body is to touch a
conductive earthed object.
Electronic modules or components must not be brought in contact with highly
insulating materials such as plastic sheets, synthetic fibre clothing,…
They must be laid down on conductive surfaces.
The tip of the soldering iron must be earthed.
Electronic modules and components must be stored and transported in
conductive packing.
2
AM 06.350e-MW Edition 3.2
Use
This Instruction Manual is the property of
restriction
notice n.v. ADB s.a.
585, Leuvensesteenweg
B-1930 Zaventem - Belgium
Tel 32 2 722 17 11 Fax 32 2 722 17 64
http://www.atd.siemens.de/airports
This manual or parts thereof may not be reproduced, stored in a retrieval
system, or transmitted, in any form or by any means, electronic, mechanical,
photocopying, recording, nor otherwise, without ADB's prior written consent.
Guarantee N.V. ADB S.A. guarantees that the performance of the inset lights described
in this manual, when sold by ADB or its licensed representatives, meets the
requirements of ICAO Annex 14 volume 1 and FAA specification AC
150/5345-46.
Any defect in design, material or workmanship, which may occur during
proper and normal use over a period of one (1) year from date of shipment,
will be repaired or replaced by ADB free of charge, ex works. Operational
failure resulting from lamp burnt out, improper maintenance or installation,
damage due to runway maintenance equipment, snow ploughs or aircraft
arresting gear hooks is not considered a result of proper use and is beyond
the scope of the warranty.
Warranty does not cover natural wear and tear nor damage arising after
delivery owing to faulty or negligent handling, excessive strain, unsuitable
materials for Operation, deficient civil engineering Work, unsuitable soil
conditions, and such chemical, electrochemical or electrical influences as
were not assumed at the time of the Contract.
All liability for consequences of any inexpert alterations or repairs carried out
by Purchaser or a third party shall be waived.
N.V. ADB S.A. shall in no event be liable to Purchaser for any further claims,
particularly claims for damages not affecting the goods themselves.
The above constitutes the limits of ADB’s liabilities in connection with the
inset lights covered by this manual.
3
AM 06.350e-MW Edition 3.2
Table of content
Section 2 Installation 43
2.1 Introduction 43
2.2 Installation 44
2.3 Electrical connection 46
2.4 Starting procedure 51
2.4.1 Tap selection 52
2.4.2 Tap wiring 57
2.5 Reparations and modifications 60
2.5.1 Replacement of modules 60
2.5.2 Replacement of EPROMs 61
Section 3 Maintenance 62
Section 4 Troubleshooting 63
Section 6 Drawings 80
4
AM 06.350e-MW Edition 3.2
5
AM 06.350e-MW Edition 3.2
Table of Pictures
FIG 1-1: POWER FACTOR AND EFFICIENCY FOR A MCR RATED 30 KVA 11
FIG 1-2: MCR STAND-ALONE UNIT 13
FIG 1-3: MCR 2.5 KVA 14
FIG 1-4: MCR 4-10 KVA 15
FIG 1-5: MCR 4 TO 10 KVA WITH EFD MODULE FRONT VIEW - OPEN 16
FIG 1-6: MCR 4 TO 10 KVA REAR VIEW - OPEN 16
FIG 1-7: MCR 12.5-30 KVA 18
FIG 1-8: MCR 12.5 TO 30KVA WITH EFD & LFD MODULES FRONT VIEW - OPEN 19
FIG 1-9: MCR 12.5 TO 30KVA REAR VIEW - OPEN 19
FIG 1-10: POWER MODULE KSR 110 A (DOUBLE EUROCARD 6U HIGH) 20
FIG 1-11: POWER MODULE KSR 43 A (DOUBLE EUROCARD 6U HIGH) 20
FIG 1-12: POWER MODULE KSR 43 A 21
FIG 1-13: POWER MODULE KSR 110 A 21
FIG 1-14: CONTROL MODULE (DOUBLE EUROCARD 6U HIGH) 22
FIG 1-15: MCR FRONT PANEL WITH MULTIWIRE REMOTE CONTROL CONNECTOR 23
FIG 1-16: MULTIWIRE REMOTE CONTROL CONNECTION ON THE REAR SIDE 28
FIG 1-17: PCB FOR MULTIWIRE REMOTE CONTROL CONNECTION ON THE REAR SIDE 29
FIG 1.18A: EXPLICIT ON SIGNAL REQUESTED – INTERNAL POWER SUPPLY 48V DC 33
FIG 1.18B: NO EXPLICIT ON SIGNAL REQUESTED – INTERNAL POWER SUPPLY 48V DC 33
FIG 1.18C: EXPLICIT ON SIGNAL REQUESTED – EXTERNAL POWER SUPPLY 24/48V DC 34
FIG 1.18D: NO EXPLICIT ON SIGNAL REQUESTED - EXTERNAL POWER SUPPLY 24/48V DC 34
FIG 1.18E: NO EXPLICIT ON SIGNAL REQUESTED - MCR IN CONNECTION WITH CSM 34
FIG 1-19: EARTH FAULT DETECTOR MODULE (MCR 12.5 TO 30 KVA) 35
FIG 1-20: LAMP FAULT DETECTOR MODULE (MCR 12.5 TO 30KVA) 37
FIG 1-21: MCR NAME PLATE 42
FIG 2-1: INSTALLATION OF MCR, MINIMUM CLEARANCE WALLS 44
FIG 2-2: DETAIL OF A TYPICAL INSTALLATION 45
FIG 2-3: CONNECTING A 2.5KVA MCR 48
FIG 2-4: CONNECTING A 4 TO 10 KVA MCR (SERIES CABLE, SUPPLY CABLE AND REAR REMOTE
CONTROL CABLES) 49
FIG 2-5: CONNECTING A 4 TO 10 KVA MCR (SERIES CABLE, SUPPLY CABLE AND REAR REMOTE
CONTROL CABLES) WITH CUTOUT SCO 49
FIG 2-6: CONNECTING A 12.5 TO 30 KVA MCR (SERIES CABLE, SUPPLY CABLE AND REAR
REMOTE CONTROL CABLE) - FRONT VIEW 50
FIG 2-7: CONNECTING A 12.5 TO 30 KVA MCR- REAR VIEW 50
FIG 2-8 : 2.5 KVA POWER TRANSFORMER TOP VIEW 57
FIG 2-9 : TAP ADAPTATION MCR 4 TO 10 KVA 58
FIG 2-10 : TAP ADAPTATION MCR 12.5 TO 30 KVA 58
FIG 2-11: TAP WIRING 59
6
AM 06.350e-MW Edition 3.2
Table of Tables
7
AM 06.350e-MW Edition 3.2
1 Section 1
1.1 Introduction
The MCR The ADB MCR is a microprocessor controlled Constant Current Regulator
specially designed for the supply of airport lighting series loops at various
intensity levels.
Scope This manual covers the ADB MCR microprocessor controlled Constant
Current Regulator manufactured in full compliance with:
• ICAO: Aerodrome Design Manual, Part 5 paragraphs 3.2.1.4/5/6
• FAA : AC 150/5345-10E and L829
• European: EMC EN 50081-2 and EN 50082-2 for industrial environments
• France: STNA approved.
Operation The constant current regulators are designed for use in airport series lighting
limits circuits.
They are designed to meet the requirements of the various specifications
mentioned above.
Operation outside the design limitations of these specifications may result in
degradation of performance, damage or failure of regulator components or
hazardous conditions.
All regulators are designed for indoor operation, at an ambient temperature
from -20°C (-40°C on special request) up to +55°C.
All the regulators are air cooled without fans.
Using the regulator at ambient temperatures out of the specified range could
cause damage. Good ventilation shall be provided specially when operation
near the maximum temperature limit is expected.
EMC - According to EN50081-2, para. 7.1, the MCR regulator will not be used in
conformity residential, commercial and light-industrial environment.
8
AM 06.350e-MW Edition 3.2
Rated powers 2.5/ 4/ 5/ 7.5/ 10/ 12.5/ 15/ 20/ 25/ 30 kVA.
Rated input voltages 220/ 230/ 240/ 380/ 400/ 415 V (±15%) (*)
Rated frequencies: 50/ 60 Hz (± 5%).
Series circuit current: Standard 6.6 A; also 20 A for 25 and 30 kVA.
Remote control and 24 or 48 V DC multiwire
monitoring
Rated Output Max. RMS Dielectric test Max. open Max. open
powers current output on output circuit RMS circuit peak
(A) voltage circuit - V - (1) output volt.(2) voltage (3)
9
AM 06.350e-MW Edition 3.2
Limits The current regulation is guaranteed within the limits of ± 1%, in the following
conditions.
Limitations • operation from -5% to -15% of nominal input voltage with full load can
cause too low output current at maximum brightness step.
• operation at +15% of the nominal input voltage will be restricted to
maximum 1-hour period to avoid over-heating or over-stressing of the
components.
Readjustment Although the nominal input voltage is factory-wired some re-adjustments are
possible in the ranges 220 up to 240V and 380 up to 415 (420V): consult
factory.
RV-DV If the last digit of the code number of your MCR is “1” or above, this means
that it is equipped with RV-DV terminals and, optionally, with a SCO cutout.
The interlocking of the SCO Cutout microswitch and the MCR RV-DV
terminals allows to energise the regulator after the Cutout contacts are
engaged and to de-energise the regulator before the Cutout contacts are
totally opened.
10
AM 06.350e-MW Edition 3.2
FAA The power factor and the efficiency are in accordance to or better than the
Accordance FAA specifications.
Power Factor At nominal input power, nominal resistive load and maximum brightness:
• powers up to 10 kVA: 0.9
• powers above 10 kVA: 0.95
Efficiency At nominal input voltage and resistive load and max. brightness: 90 to 92%.
Taps By means of output taps on the secondary (high voltage) side of the power
transformer (PT) the power factor can be optimised versus the actual load at
full brightness. The following taps are provided:
• actual load between 100% and 82% of nominal (8/8)
• actual load between 81% and 71% of nominal (7/8) (*)
• actual load between 70% and 46% of nominal (6/8) (*)
• actual load between 45% and 33% of nominal (4/8)
• actual load between 32% and 22% of nominal (3/8) (*)
• actual load between 21% and 0% of nominal (2/8) (*)
Example Taps
2/8 3/8 4/8 6/8 7/8 8/8
100% Efficiency
90
80 Power Factor
70
60
50
40
Load
12 25 37 50 75 87 100%
Fig 1-1: Power factor and efficiency for a MCR rated 30 kVA
11
AM 06.350e-MW Edition 3.2
Output The lightning arrestors LA1 and LA2 (fig 1.3, 1.5 and 1.8) on the output
voltage surge terminals of the series circuit protect the output of the MCR.
protection
12
AM 06.350e-MW Edition 3.2
Description Each stand-alone MCR will accept, in one enclosure, a power module
KSR43A or KSR110A (as required) fitted with the control module, a fused
input switch (in the low voltage unit), and the high voltage components (in the
high voltage unit). The stand-alone regulators have standard lifting lugs and
optional rolling castors.
1 2
Part Function
1 Power Module KSR 110 A (para. 1.3.5)
2 Control Module (para. 1.3.6)
3 Fused input switch
4 Time counter
5 High voltage compartment
13
AM 06.350e-MW Edition 3.2
Technical data
267
ON
FAULT
FAULT
FAULT
LOCAL
RESET
REM
OFF
S1
S2
S3
S4
S5
S6
S7
S8
X
1
X
3
X
2
14
AM 06.350e-MW Edition 3.2
Technical data
Rated powers 4/ 5/ 7.5/ 10 kVA.
Rated input voltages 220/ 230/ 240/ 380/ 400/ 415 V (±15%)
Rated frequencies: 50/ 60 Hz (± 5%).
Series circuit current: 6.6 A
Remote control and
monitoring
1260
100
15
AM 06.350e-MW Edition 3.2
Pictures Fig 1-5: MCR 4 to 10 kVA with EFD Module Front View - Open
Control Module
Name Plate
Choke L1
RV-DV terminals
Interface module
S6 through S1 Tap
Adaptation to actual load
Output Transformer
Ground Stud M6
16
AM 06.350e-MW Edition 3.2
17
AM 06.350e-MW Edition 3.2
Technical data
Rated powers 12.5/ 15/ 20/ 25/ 30 kVA.
Rated input voltages 220/ 230/ 240/ 380/ 400/ 415 V (±15%) (*)
Rated frequencies: 50/ 60 Hz (± 5%).
Series circuit current: Standard 6.6 A; also 20 A for 25 and 30 kVA.
Remote control and
monitoring
1260
18
AM 06.350e-MW Edition 3.2
Pictures Fig 1-8: MCR 12.5 to 30kVA with EFD & LFD Modules Front View - Open
Name Plate
Lamp Monitor
Transformer TI 2 (option LFD)
Output Current
Transformer TI 1
Earth Fault Detection
Module (option EFD)
S6 through S1 Tap
adaptation to actual load
Lightning Arresters
LA1 - LA2
Output Voltage
Transformer TP1 (option LFD)
Interface module
Output transformer
Ground Studs M6
19
AM 06.350e-MW Edition 3.2
Principle The complete power range from 2.5 to 30 kVA is based on two easily
replaceable power modules, one for max. 43 A (KSR 43 A) and the other for
max. 110 A (KSR 110 A).
These modules are installed in the low voltage unit of the MCR.
Pictures Fig 1-10: Power Module KSR 110 A (Double Eurocard 6U High)
F1 F2
267 mm
x
1
x
3
x
2
244 mm
F1 F2
267 mm
x
1
x
3
x
2
122 mm
20
AM 06.350e-MW Edition 3.2
P2
P7
1 2 5 3 4 6 7
8
F1 F2
P2
MCR-110A
P7
1 2 5 3 4 6
Legend
Part Function
1 Auxiliary fuses F1 and F2
2 Dual in/out terminals
3 Thyristor pack THP1
4 Thyristor trigger and contactor on/off control PCB
5 2-pole contactor K
6 Auxiliary supply transformer T1
7 Plugs P2 and P7 for the Control Module
8 Input current transformer Tin
21
AM 06.350e-MW Edition 3.2
General The module with the on-board microprocessor controls and monitors the
operation of the regulator
167 mm
x
1
x
3
x
2
45,72 mm
Additional • Piggy-back PCB for multiwire remote control, with a DB37 front
piggy-back connector on the front panel.
PCB's • Piggy-back PCB for Lamp Fault detection (option LFD)
22
AM 06.350e-MW Edition 3.2
Front panel Fig 1-15: MCR Front Panel with multiwire remote control connector
Display Selection
CCR-ON
I-Fault 2
Earth Fault
Lamp Fault
Local Operation
23
AM 06.350e-MW Edition 3.2
Front panel: 1. 4 digits multiple info alphanumerically display; with the “display select”
legend push button, the values that can be selected are:
• output current,
• brightness step,
• % of maximum output load (option LFD),
• output voltage (option LFD),
• number of failed lamps (option LFD),
• circuits identification,
• series circuit insulation value (option EFD),
• lamp test.
2. Led's for information about the status of the regulator:
• CCR ON,
• I-fault,
• Earth-fault (option EFD),
• Lamp fault (option LFD),
• Local operation.
3. Reset button,
4. Remote, Off, brightness step 1 to 8 drum selector,
5. DB9-male connector for connection to a PC (X1),
6. DB37-male multiwire remote control connector (X3),
7. DB25-male connector (X2) for feedback signals (current, LFD and EFD)
duplicated to P7 on the rear (ADB-use),
8. Fixing screws.
Drum selector During switch over from one brightness step to another it is possible that,
due to an intermediate position, the output current has a totally different
value or that the regulator switches off.
The output current will however never be higher than the maximum value.
If the drum selector is handled in a normal way this situation will not occur.
For all the local selections above the maximum step (e.g. position 4 for a 3
brightness steps regulator) the output current will equal the maximum step.
The drum selector has no end position. It can be switched, without any
danger, from position 8 to the position "remote control".
24
AM 06.350e-MW Edition 3.2
Introduction The regulator is delivered with factory programmed default brightness values.
Each brightness step can be re-adjusted between the maximum and the
minimum current value with the PC software.
Default values The table below shows the current values for each brightness step in
function of the number of steps.
Imax (A) 20
Imin (A) 5.5
Brightness step Nr of steps
Drum selector 3 4 5 6 7 8
Fig 1-15
1 14.5 10 8.5 8.2 6.7 8.5
2 16.7 13.3 10.3 10 8.5 9.4
3 20 16.7 12.4 11.8 10.3 10.3
4 “ 20 15.8 13.6 12.4 11.8
5 “ “ 20 16.4 15.8 13.9
6 “ “ “ 20 19.4 16.7
7 “ “ “ “ 20 19.4
8 “ “ “ “ “ 20
25
AM 06.350e-MW Edition 3.2
Output current The MCR creates an alarm (indicated by the led “I fault” and on the 4 digits
monitoring for display ("I<<") on the front panel) and switches off when the output current
open circuit drops below the minimum output current. The restart of the MCR is only
possible after troubleshooting and reset (reset button on the front panel).
Output current The MCR creates an alarm (indicated by the led “I fault” and on the 4 digits
monitoring for display ("I>>") on the front panel) and switches off when the output current
over current is higher than one of the two preset levels and after the corresponding time-
delay of each level. The restart of the MCR is only possible after
troubleshooting and reset (reset button on the front panel).
Mains supply Undervoltage: If the mains supply voltage drops below a certain (user-
voltage adjustable) level, the MCR switches off.
monitoring When the mains supply voltage has reached a higher (user-adjustable)
level, the MCR restarts automatically.
Overvoltage: An alarm will be generated when the mains supply voltage
reaches a (user-adjustable) level.
Capacitive With an open circuit on long screened series cables the output current, due
output current to cable capacitance, may remain above the open circuit threshold level
monitoring thus inhibiting the operation of the open circuit shut down.
The MCR creates an alarm (indicated by the led “I fault” and on the 4 digits
display ("I<<") on the front panel) and switches off during open circuit shut
down. The restart of the MCR is only possible after troubleshooting and
reset (reset button on the front panel).
Monitoring of The control module monitors the conduction angle of the thyristor.
the output If the conduction angles of both thyristors are not equal, the MCR switches
current for off (indicated by the led “I fault” and on the 4 digits display "ASY" on the
asymmetry front panel). The restart of the MCR is only possible after troubleshooting
and reset (reset button on the front panel).
Monitoring of In case of overload the output current cannot be guaranteed by the MCR,
overload the reaction of the MCR can be programmed by the user with the PC
software. The default reaction is not to switch off the MCR!
The alarm is indicated by the blinking led “I fault” on the front panel.
Monitoring of A fast response network fires back the thyristors if the peak value of the
output current output current reaches a value greater than twice the maximum peak value
surge in normal operation. The thyristors remain in the off-state for several periods
limitation and the firing angle then goes smoothly from zero back to the normal value.
26
AM 06.350e-MW Edition 3.2
1.6.1 General
CSM circuit When the MCR operates with a CSM circuit selector, the CSM must have
selector the same multiwire remote control system!
1.6.2 Connection
Front or rear Front: DB37-male connector (X3 of fig 1-15) on the front panel of the control
connection module.
Rear: DB37-male connector (P1 of fig 1-16 and fig 1-17) and DB15-female
connector (P3 of fig 1-16 and fig 1-17) or screw terminal strips on the interface
module PCB1448 (fig 1-16 and 1-17).
Control The control signals feed relay coils protected by an RC circuit for transient
signals overvoltage:
Back The back indication signals are provided over dry contact relays.
indication
The maximum contact load is:
• AC-110V-0.5A-60VA
• DC-110V-0.5A-30W.
Wire section The maximum wire section that can be connected to the rear screw terminals
on the interface module is (insulation strip length: 6mm):
• 1.5 sqmm stranded wire
• 2.5 sqmm single core wire
27
AM 06.350e-MW Edition 3.2
Picture Fig 1-16: Multiwire Remote Control connection on the rear side
flat cable to the remote control piggy back on control module
DB37 male
connector
Strap S8: • When the hour counter on the CSM is activated by an external signal
MCR with (EXT), the strap S8 must be in position a!
CSM • S8 is activated only when parameter ”Back indication for maximum step
always S8” (see par. 7.4.5) is set to “YES”.
When the jumper W1 is plugged, the metal cap of the connectors P1 and P3 is earthed.
28
AM 06.350e-MW Edition 3.2
Interface Fig 1-17: PCB for Multiwire Remote Control connection on the rear side
module
PCB1393:
1
37
PCB1448:
1
15
1
37
29
AM 06.350e-MW Edition 3.2
(*) Only available in 48 V DC remote control version and may only be used
as power supply for remote control signals of this regulator.
30
AM 06.350e-MW Edition 3.2
31
AM 06.350e-MW Edition 3.2
Circuit selector
32
AM 06.350e-MW Edition 3.2
S2 S4 S6
CRC
CCI S1 S3S3 S5 S7
S2 S4 S6
CRC
33
AM 06.350e-MW Edition 3.2
S2 S4 S6
C R C
48V or 24V D C
E x te r n a l p o w e r s u p p ly
C C I S1 S3S3 S5 S7
S2 S4 S6
C R C
48V or 24V D C
E x te r n a l p o w e r s u p p ly
S2 S4 S6
C R C
C R C O N
TO W ER
C SM
34
AM 06.350e-MW Edition 3.2
Principle The earth fault detector module measures the insulation resistance between
the series circuit and the ground or the cable screen with the regulator
switched to the supply, even when not running. A stabilised, current limited,
500 V DC voltage is applied between the series circuit and the ground or
cable screen, irrespective of the operating voltage, via a high voltage
resistor. The insulation resistance is determined from the resulting leakage
current.
Measurement The measurement range is from 6.3 kOhm to 0.5 GOhm. The insulation
range resistance can be displayed on the front panel display.
2 levels Two alarm levels are available. Each level can be set in a range from 6,3
kOhm to 150 Mohm.
Alarm If the insulation value drops below the alarm level, the “earth-fault” led on the
front panel is activated and a back indication signal is generated towards the
remote control. If the insulation, then, increases above that level the alarm
remains latched. The reset is possible with the “RESET” button on the front
panel or via a remote control command.
Picture Fig 1-19: Earth Fault Detector module (MCR 12.5 to 30 kVA)
EFD components
(with logic print)
35
AM 06.350e-MW Edition 3.2
Theory The Lamp fault detector module (LFD) measures the reactive power required
to saturate the unloaded lamptransformers of the series loop by integrating
the series loop voltage (obtained through the voltage transformer) during a
measuring window (derived from the unloaded current transformer mounted
in the regulator enclosure).
The measured voltage with all the lamps of the series loop intact is
compensated to obtain a zero volt reading.
With a defined number of lamps in open circuit the module can be calibrated
to obtain a read-out corresponding to the number of lamps de-activated.
Tolerances If the above mentioned restrictions are fulfilled, the obtained tolerance will
be:
• for 0 to 5 burnt lamps : + 1 lamp
• for 6 to 10 burnt lamps: + 2 lamps.
36
AM 06.350e-MW Edition 3.2
Picture Fig 1-20: Lamp Fault Detector module (MCR 12.5 to 30kVA)
Lamp Monitor
Transformer T.I.2
Output Voltage
Transformer T.P.1
37
AM 06.350e-MW Edition 3.2
Cutout SCO As an option, the regulator MCR can be delivered with a cutout SCO
mounted onto the bottom part of the rear panel.
The purpose is to isolate safely the series circuit from the CCR during
maintenance or testing operations. It also allows periodical isolation
resistance measurement series circuit to ground without disconnecting the
series cable.
Refer to instruction manual AM.06.455e.
Diagram Series
CCR Series CCR
CCR Series Circuit
Circuit
Circuit
Measurement
Ground Ground socket
Cover
Handle horizontal turned 90° ccw. turned 90° cw. from position A
from position A
The series circuit connected to the shorted and disconnected from the CCR, shorted and
is CCR grounded connected to the measurement terminal
The CCR is delivering current shorted and shorted and grounded
to the series circuit grounded
The microswitch activated and not activated activated and allows the regulator to be
(2) is allows the CCR to and inhibits the ON
be ON CCR to be ON
The cover can be locked by can be locked can be locked by the key
the key by the key
1. The position of the cover intermediate between B and C, i.e., turned 180° from
position A, cannot be used and the cover cannot be plugged into the body.
2. An activated microswitch means that the normally open contact is closed and that
the normally closed contact is open. For interlocking with the CCR, only the
normally open contact will be used.
38
AM 06.350e-MW Edition 3.2
Time counter As an option, the regulator MCR can be delivered with a time counter
mounted on the right front panel of the low-voltage compartment (see fig
1.2).
Three executions are available:
• Time counter “ON” starts counting as soon as the MCR is
switched ON, independent of the brightness step.
• Time counter: “maximum brightness step” runs only when the
MCR operates in maximum brightness step (6.6A or 20A)
• Both time counter “ON” and “maximum brightness step” are
available.
When the MCR operates with a CSM circuit selector, no time counters
are allowed on the MCR.
Nevertheless, the option time counter is available on the CSM!
39
AM 06.350e-MW Edition 3.2
1.11 Equipment required for installation, start-up and troubleshooting but not
supplied
Tools 1 True RMS Voltmeter (preferable: 5000V AC scale with isolating transformer).
1 Multimeter
1 Ohmmeter "Megger" 5000V insulated
1 Clamp or A-meter true RMS scale 10 and 30Amps
1 Complete set of tools for electrician and mechanic (no special tool required)
40
AM 06.350e-MW Edition 3.2
Floppy A Floppy-disc with the communication program between the MCR and the
PC can be ordered.
Section 7 shows how to install the program and explains the functions of the
software.
Take care that the software version is compatible with the version of the
basic MCR software. (see table 1.2).
compatible with
Basic MCR software version of PC software
version on floppy disc
1.02 1.04
1.05 1.04
1.08 1.08
1.10 1.11
1.11 1.11
1.12 1.12
1.21 1.21
1.22 1.21
1.23 1.24
2.00 2.00
Ordering For information about ordering codes and ADB part numbers, refer to:
codes Section 5 Parts list and spare parts.
41
AM 06.350e-MW Edition 3.2
Values
Output Power Output current Supply Voltage
c d a b e
2.5 kVA 6.6 A 220/ 230/ 240 14 378
4 kVA 6.6 A 220/ 230/ 240 22 606
5 kVA 6.6 A 220/ 230/ 240 28 757
7.5 kVA 6.6 A 220/ 230/ 240 41 1136
10 kVA 6.6 A 220/ 230/ 240 54 1515
12.5 kVA 6.6 A 220/ 230/ 240 67 1894
15 kVA 6.6 A 220/ 230/ 240 77 2272
20 kVA 6.6 A 220/ 230/ 240 103 3030
2.5 kVA 6.6 A 380/ 400/ 415 8 378
4 kVA 6.6 A 380/ 400/ 415 13 606
5 kVA 6.6 A 380/ 400/ 415 17 757
7.5 kVA 6.6 A 380/ 400/ 415 24 1136
10 kVA 6.6 A 380/ 400/ 415 31 1515
12.5 kVA 6.6 A 380/ 400/ 415 39 1894
15 kVA 6.6 A 380/ 400/ 415 45 2272
20 kVA 6.6 A 380 60 3030
20 kVA 6.6 A 400/ 415 57 3030
25 kVA 6.6 A 380/ 400/ 415 75 3788
30 kVA 6.6 A 380/ 400/ 415 88 4545
25 kVA 20 A 380/ 400/ 415 75 1250
30 kVA 20 A 380/ 400/ 415 88 1500
42
AM 06.350e-MW Edition 3.2
2 Section 2
Installation
2.1 Introduction
Introduction This section provides instructions for the installation of the MCR regulators.
Refer to the substation drawings and specifications for the specific installation
instructions.
Unpacking Unpack the crate upon receipt and examine the regulator to insure that no
damage has occurred during shipping. Note any exterior damage to the crate,
which might lead to detection of equipment damage. When handling the
regulator care should be taken to maintain the regulator in the upright position.
If damage to any equipment is noted, a claim form should be filed with the
carrier immediately. The inspection of the equipment by the carrier may be
necessary.
Installation The regulator will be installed in a well-ventilated room with sufficient clearance
criteria for personnel to inspect and maintain the regulator.
The installer should refer to the specific installation plan for implantation.
The series cut-outs and the circuit selector (if any) are generally also installed
in the same room (refer to appropriate manual).
For special models, refer also to the appropriate manuals (outside, portable,
rack-mounted version).
43
AM 06.350e-MW Edition 3.2
2.2 Installation
Regulator If the regulator is equipped with castors, it can simply be pushed to the right
with wheels location in the substation, provided the floor is flat.
Adequate precautions should be taken to avoid overbalancing the regulator if
there are obstacles on the floor such as wires or small unevenness.
Note that the 4 to 10 kVA regulators do not have a square footprint.
Regulator The regulator can be lifted by the lifting lugs on the top (see fig 1-2). Always
without use the 4 lifting lugs to lift it.
wheels
Ventilation Air outlet grids are provided at the rear and the top; air inlet grids, at the
bottom and the front of the regulator.
To avoid overheating of CCR-components, take care never to obturate these
ventilation grids.
Fig. 2-1 gives the position of the regulator with regard to the minimum
clearance necessary to have good ventilation. Side by side, the regulators
have to remain to a minimum of 5 cm from each other.
Air exhaust
Min 50 cm to the wall
Front side
Rear
side
Air intake
Air
exhaust
Air intake
44
AM 06.350e-MW Edition 3.2
Cutout SCO As an option, the regulator MCR can be delivered with a cutout SCO
mounted onto the bottom part of the rear panel.
Refer to the instruction manual AM.06.455e for more information about it.
45
AM 06.350e-MW Edition 3.2
Panels to For connecting the supply, output and remote control cables,
remove • 2,5 kVA: remove top and rear panel
• 4 to 10 kVA: remove the front and rear panels
(MCR with serial number ending on a 3 only rear panel)
• 12.5 to 30 kVA: remove the front and rear panels.
Refer to the previous page for the precautions to take.
Grounding Although the supply cable includes a ground wire, additional safety
grounding is required. Use the ground studs M6 on the rear/ bottom of the
regulator (see Fig 1-6 and Fig 1-9). The grounding wire will have at least 16
mm² and be as short as possible.
Main supply The minimum section of the main supply cable (see table 2.1) is valid under
cable following conditions:
Straps on Check the position of the straps on the interface module (PCB1448).
PCB’s
46
AM 06.350e-MW Edition 3.2
Table 2-1 Table 2-1: Main supply cable sections, fuses, power module,…
47
AM 06.350e-MW Edition 3.2
48
AM 06.350e-MW Edition 3.2
MCR Fig 2-4: Connecting a 4 to 10 kVA MCR (series cable, supply cable and rear remote
4 to 10 kVA control cables)
Supply cable
Rear remote control cable
Series cable
Fig 2-5: Connecting a 4 to 10 kVA MCR (series cable, supply cable and rear remote
control cables) with cutout SCO
Interlock cable
Stress relieve cable clamps
Supply cable
Rear remote control cable
49
AM 06.350e-MW Edition 3.2
MCR Fig 2-6: Connecting a 12.5 to 30 kVA MCR (series cable, supply cable and rear remote
12.5 to 30 kVA control cable) - Front view
Series cable
Supply cable
Series cable
50
AM 06.350e-MW Edition 3.2
Caution Read the safety instructions and check if the installation complies with para.
2.3. Do the following preliminary checks:
• grounding
• main supply cable, routing, wiring and voltage
• series circuit cable, routing, wiring and insulation resistance to earth.
• remote control cable, routing, wiring and voltage.
Procedure The first start-up will be done in local control only (drum selector on front
panel of control module). It is advised, as far as possible, to disconnect the
remote control.
Step Action
1 Open the fused input switch (Fig 1-2) and put the drum selector (Fig 1-
15) in the OFF position.
2 Disconnect the series circuit (if already connected) and short the output
terminals. Measure the output current with an AC current clamp around
the shorting wire. Warning: High voltage!
3 Switch ON the regulator supply on the low voltage distribution board and
measure the input voltage on the main supply terminals (Fig 2-3, 2.4, 2.5
and 2-7). The measured voltage must match the input voltage indicated
on the nameplate within -5 to +10%.
4 Check if the input fuses are correctly positioned.
5 With the drum selector still in the OFF position, close the fused input
switch. The display on the control module will indicate “0.00” (output
current) and the green “ON” led and the yellow “LOCAL” led will be lit.
6 Turn the drum selector to position B1 and measure the output current
with the external A-meter and compare it with the indication on the
display. Repeat the same for all each brightness step by turning the
drum selector through positions B1 to B8.
The value of the actual output current depends on the number of
programmed steps (see para. 1.4)
7 Switch OFF the regulator by turning the drum selector CCW (counter
clock wise) to the OFF position and open the fused input switch.
8 Remove the short circuit on the output and switch the regulator ON
(close the fused switch and turn the drum selector to position B1). The
main contactor will switch ON and after a short period OFF. The display
will indicate “I<<“ and the led “I fault” on the control module lights up,
indicating an open series circuit.
9 Switch OFF the regulator by turning the drum selector CCW (counter
clock wise) to the OFF position and open the fused input switch.
Connect the series circuit to the regulator. Switch ON the regulator and
check the output current. Check that the maximum output current is not
less than 6.6 A (or 20A).
Unless the maximum output current has been reprogrammed, failure to
reach that current indicates a too high series circuit load or a too low
main supply voltage. Switch off the MCR.
With the maximum output current, check that the main input voltage is
not less than the 95% of the nominal value.
10 Proceed with the adaptation of the output transformer secondary taps to
the actual load. (para. 2.4.1)
51
AM 06.350e-MW Edition 3.2
Target Adaptation of the regulator to the installed load by using the right tap
combination.
Preliminary For each method a preliminary visual check will be made on the series circuit.
check Switch ON the CCR at a convenient brightness and check that all the lamps of
the circuit operate. If not, take corrective actions until all lamps are OK.
Check that the mains voltage is at its nominal value.
Step Action
1 Switch ON the MCR to the maximum brightness step 6.6A or 20A
2 Measure the RMS output voltage at the output terminals after
about 10 minutes. Determine the correct tap using table 2.2 -
choose the tap with the nearest higher voltage than the measured
RMS output voltage.
Switch off the MCR and wire the chosen tap (see par 2.4.2).
Warning: High Voltage!
3 Switch ON the regulator at the maximum brightness for about 10-
min. and check that the output current is not below the maximum
value. If the output current is too low, wire to the next higher tap.
4 Close the MCR taking into account the requirements given in par.
2.2.
Table 2.2 Table 2-2: Maximum voltages (V RMS) for each tap, each power and output current.
PWR/ Iout Tap 8/8 7/8 6/8 4/8 2/8
2.5 kVA/ 6.6A 378 - - 190 -
4 kVA/ 6.6A 606 530 450 300 150
5 kVA/ 6.6A 757 660 565 375 185
7.5 kVA/ 6.6A 1136 990 850 565 280
10 kVA/ 6.6A 1515 1320 1130 755 375
12.5 kVA/ 6.6A 1894 1650 1410 940 465
15 kVA/ 6.6A 2272 1980 1695 1130 560
20 kVA/ 6.6A 3030 2645 2260 1505 745
25 kVA/ 6.6A 3788 3305 2825 1880 935
30 kVA/ 6.6A 4545 3965 3390 2255 1120
25 kVA/ 20A 1250 1090 930 620 310
30 kVA/ 20A 1500 1310 1120 745 370
52
AM 06.350e-MW Edition 3.2
Step Action
1 Remove the front panel of the power module (KSR43A or
KSR110A) by loosening the 5 screws.
F1 F2
5 screws to
remove
x
1
x
3
x
2
Do not lose the pin washers, they must be put in place again.
2 Switch ON the regulator to the maximum brightness step.
3 After about 10 minutes, measure the voltage on the terminals
labelled “OUT1” and “OUT2” of the power module.
4 Switch OFF the MCR. Using the table 2.3, select and wire (see
par 2.4.1 and 2.4.2) the tap to be used.
5 Once the taps had been wired, switch ON the regulator again at
the maximum brightness for about 10 minutes and check that the
output current is not below the maximum value. If the output
current is too low, wire to the next higher tap.
6 Close the MCR taking into account the requirements given in
para. 2.2.
53
AM 06.350e-MW Edition 3.2
Table 2-3 Table 2-3: Tap to choose, for each power, depending on the measured primary voltage.
54
AM 06.350e-MW Edition 3.2
Table 2-3 Table 2-3: Tap to choose, for each power, depending on the measured
primary voltage (Continued).
55
AM 06.350e-MW Edition 3.2
Third method You can also use the PC software (see section 7) to determine which tap to
select. Therefore, follow the next procedure.
Procedure
Step Action
1 Wire the 8/8 tap and switch ON the regulator to the maximum
brightness.
2 Connect the PC to the regulator, open the program and go to
menu F8: “power monitoring”. Select in the sub-menu “primary
parameters” the “Thyristor conduction angle” parameter.
3 Read the thyristor conduction angle and select the tap using the
table below:
56
AM 06.350e-MW Edition 3.2
Step Action
1 To gain access to the power transformer terminals (S6 to S1),
remove the top cover and disconnect the ground wire. Note the
position of the ventilation slots.
2 Wire the tap according to fig 2-11.
3 Switch ON the regulator at the maximum brightness step for about
10 minutes
4 Check that the output current is not below the maximum value.
If it is so, wire to the next higher step and check again till the
output current is below the maximum value.
5 Close the MCR taking into account the requirements given in par.
3.2.
P10
P9 S1
P8 S2
P7 S3
P6 S4
P5 S5
P4 S6
P3
P2
P1
57
AM 06.350e-MW Edition 3.2
Step Action
1 Remove the front panel and disconnect the ground wire.
2 Wire the tap according to fig 2-11.
3 Switch ON the regulator at the maximum brightness step for about
10 minutes
4 Check that the output current is not below the maximum value.
If it is so, wire to the next higher step and check again till the output
current is below the maximum value.
5 Close the MCR taking into account the requirements given in par.
3.2.
S6 through S1 tap
adaptation to actual
load
identification label
OUT
OUT
S6
S5
S4
S3
S2
S1
Spare strap
58
AM 06.350e-MW Edition 3.2
S1 wire m1 S1 wire m1
S2 S2
82 to 100 % 71 to 81 %
(8/8) (7/8)
S3 S3
S4 wire m2 S4
S5 S5 wire m2
strap B strap B
S6 S6
S1 S1 wire m1
S2 wire m1 S2
59 to 70 % 22 to 46 %
(6/8) (4/8)
S3 S3
strap A
S4 S4 wire m2
S5 wire m2 S5
strap B strap B
S6 S6
S1 wire m1
S2
8 to 22 %
(2/8)
S3
strap B
S4 wire m2
S5
S6
59
AM 06.350e-MW Edition 3.2
60
AM 06.350e-MW Edition 3.2
61
AM 06.350e-MW Edition 3.2
3 Section 3
Maintenance
Introduction The MCR regulators have been developed using new technologies and in view
of reducing the maintenance tasks to a minimum.
This section establishes the maintenance procedures required for the MCR
regulator. The maintenance tasks must be performed on a securing basis to
insure optimum performance, minimise service interruption and avoid major
breakdowns.
To check Action
Operational • the operation of the • Use eventually a PC to log the
regulation on all data
brightness steps
• all readings.
Electrical • Input voltage • If the regulator voltage is not
within -5% to +15% of rated
voltage, notify the power
company to correct the
voltage.
• Output current (RMS • Record it and adjust if out of
value) tolerance; use a RMS-reading
A-meter.
Visual • the wiring of the • Repair damaged or loose
regulator and circuit wires
• Replace damaged
components
• Housing for rust spots • Clean and repaint rust spots.
and damage. • Repair the eventual damages
• Dust inside housing • Clean by blowing dry air over
the dirty components,
PCB’s,…
62
AM 06.350e-MW Edition 3.2
4 Section 4
Troubleshooting
63
AM 06.350e-MW Edition 3.2
Troubleshooting, Continued
Guideline As a guideline for troubleshooting, use Table 4-1 up to Table 4-3. Three
different cases are given:
Display and Together with these explanations, the next 2 tables show how to interpret the
led’s info. indications on the front panel display and the meaning of the different led’s:
Table Information
Table 4-4 How to interpret the indications on the display?
Table 4-5 Led’s information
Fuses The table 4-6 gives an overview of the fuses (main fuses, fuses on the power
module,…) in the MCR.
64
AM 06.350e-MW Edition 3.2
Troubleshooting, Continued
65
AM 06.350e-MW Edition 3.2
Troubleshooting, Continued
66
AM 06.350e-MW Edition 3.2
Troubleshooting, Continued
Table 4-3 Table 4-3: Regulator does not produce the requested output current.
67
AM 06.350e-MW Edition 3.2
Troubleshooting, Continued
Table 4-4 Table 4-4: How to interpret the indications on the front panel.
The 4 digits display normally indicates the actual values of the chosen
parameter (see par. 1.3.6), but in some cases the display indicates a
character string:
If This means
%--- Percentage of output load not available
V--- Output voltage measurement not available
L--- Lamp fault detector, not present
L*** Lamp fault detector, present but disabled or not adjusted
---M Earth fault detector, not present
???M Earth fault detector, measurement not available
This display will also indicate how the regulator interprets an occurring failure
that causes the regulator to switch off (if the strap ST2 on the PCB1364 is in
position 2 which is a default setting on delivery):
If This means
CS? The regulator is configured to operate with a circuit selector and
expects thus to receive the ON-signal through the remote control
line S1 (PC function: F5/ Hardware/ Multiwire/ “circuit selector
present Yes or No”).
If you select a brightness step in local (position S1 through S8) and
there is no ON-request via the line S1, this message will be
displayed.
I>> The regulator switched OFF for overcurrent
I<< The regulator switched OFF because the output current was below
a minimum level (open circuit, thyristors not operational, main
contactor not closed, loose wire, output current measurement is
failing, …
Asy The regulator switched OFF for asymmetric output current
P>> The regulator switched OFF for overload.
The regulator is set to switch OFF in case of output overload with
the PC function: F5/ Alarm levels output current/ “switch off level if
overload Yes or No.
These failures will disappear after having pushed on the Reset button (Rep 3
on Fig. 1-15) on the front panel.
68
AM 06.350e-MW Edition 3.2
Troubleshooting, Continued
Several led’s are available on the front panel of the control module and
inform you about the status of the MCR.
As a general rule, a blinking led indicates that the considered function is
not available and a permanent lighted led indicates a failure.
Those led’s are installed on the front panel of the basic microcontroller board
(PCB1364). Some of them can only light up if the corresponding option is
installed.
Led Indicates
DS1 TXD, messages to the PC if the serial link is active.
DS2 RXD, messages from the PC if the serial link is active.
DS3 blinks at a rate of once per second if the program runs.
DS4 5V-power supply present.
69
AM 06.350e-MW Edition 3.2
Troubleshooting, Continued
Led Indicates
DS1 5V-power supply present.
Led Indicates
DS1 LOW SCALE, lights up if the actual leakage current is below
20µAdc.
DS2 500 V DC, lights up if the 500 V DC is too low in regard to the
reference voltage.
DS3 IN RANGE, extinguishes if the output current of the module gets
limited.
DS5 OHM-TEST lights up if the relay for the ohm-test is activated.
70
AM 06.350e-MW Edition 3.2
Troubleshooting, Continued
On the boards:
71
AM 06.350e-MW Edition 3.2
5 Section 5
Parts list
Introduction This section covers the main replaceable parts for the MCR regulators.
Caution Replacement of electronic components may be done, only with original spare
parts delivered by ADB. Not doing so can result in severe damage to the unit
and be hazardous for the user or the operator.
Reference A reference code number is assigned to each part contained in the equipment.
designation When ordering, always mention the reference code number of the ordered part
but also the serial number, type, power rating, input voltage, frequency, N° of
brightness steps, output current, which are indicated on the nameplate of the
regulator.
• Other parts: Other parts should be kept in stock to cope with repair: fuses,
lightning arrestors, PCB’s, terminals & connectors, fused input switch,
circuit breaker, power module and others.
Orders All spare parts orders shall be addressed to ADB or our local representative.
n.v. ADB s.a.
585, LEUVENSESTEENWEG
B - 1930 ZAVENTEM, BELGIUM
Tel. 32/2/722.17.11
Fax : 32/2/722.17.64
72
AM 06.350e-MW Edition 3.2
Remark 1 The PCB 1441 (NC 1593.11.700) replaces the PCB 1377 (NC 1590.03.250)
in the MCR versions where the last digit of the code number is “1” or above.
Anyway, in older versions (with last digit = 0), the PCB 1441 can also be
used as spare parts. The terminals 3 and 4 of the counter-connector X5,
which is delivered with the PCB, have to be shortened.
Remark 2 To replace the old contactor on the KSR110 (NC 6148.45.530) by the new
one (NC 6148.45.600) the current transformer on the KSR110 has to be
repositioned!
73
AM 06.350e-MW Edition 3.2
74
AM 06.350e-MW Edition 3.2
75
AM 06.350e-MW Edition 3.2
76
AM 06.350e-MW Edition 3.2
77
AM 06.350e-MW Edition 3.2
Table 5-4 Table 5-4: Spare parts for EFD option (see Fig 1-5 and 1-8).
Table 5-5 Table 5-5: Spare parts for LFD option (see Fig 1-5 and 1-8).
78
AM 06.350e-MW Edition 3.2
79
AM 06.350e-MW Edition 3.2
6 Section 6
Drawings
Introduction In the table below, you will find the list of drawings:
80
AM 06.350e-MW Edition 3.2
DS1
81
AM 06.350e-MW Edition 3.2
DS1-DS2-DS3-DS4
F1
RAM
P1 Params
EPROM
P3 Rem. control
ST2 F2-F3
P4 LFD
Serial
EPROM
P6
P8
F4
82
AM 06.350e-MW Edition 3.2
Flat cable
connector
R17
F1
83
AM 06.350e-MW Edition 3.2
84
AM 06.350e-MW Edition 3.2
F1 - F2
85
AM 06.350e-MW Edition 3.2
86
AM 06.350e-MW Edition 3.2
87
AM 06.350e-MW Edition 3.2
88
AM 06.350e-MW Edition 3.2
89
AM 06.350e-MW Edition 3.2
7 Section 7
Use The PC with the dedicated ADB software is required to modify parameters, in
particular for the adjustment of the lamp fault detection module and for the
circuit selector CSM (see catalogue leaflet A.06.412e).
It can also be used to control the regulator.
Caution! The PC can control the regulator or change parameters only if the front
panel drum selector of the regulator is in OFF position (ref. 4 on Fig 1-
15).
When the regulator is in the REM or LOCAL position, the software can
display parameters and status but it is impossible to modify them.
Hardware The program requires at least a 386 PC with at least 4 Mb of RAM to be able
to run. At least 1 COM port is necessary for communication with the MCR.
No mouse is required.
DOS The PC software is written in PROTECTED (or 386) mode i.e. it uses
protected memory above the standard 1 Mbytes DOS limit.
mode Therefore the DOS extender program DOS4GW.EXE must either be present
in the same directory or it must be found in one of the directories specified in
the path.
Software This description is only valid for the MCR PC software version 2.00
version If the delivered software version differs from the above versions, refer to the
manual delivered with that software.
90
AM 06.350e-MW Edition 3.2
7.1.1 Overview
Introduction In this chapter you will find all the information about the connection of the PC
to the regulator and about the installation of the software on the PC.
Connection One side of the communication cable MCR – PC is connected with the DB 9-
male connector on the front plate of the Control Module and the other side
with the COM1 or COM2 serial port of the PC.
DB9 connector
Communica- The communication cable needs 4 wires and a separate ground, which can
tion cable be the cable-screen.
As with all RS232 connection, the maximum length is limited to 15 meters.
The cable layout is listed in the following table.
91
AM 06.350e-MW Edition 3.2
Software Copy the files from the floppy to the hard disk.
installation The program can be installed anywhere on the hard disk and is independent
of a particular directory structure; nevertheless, it is a good practice to create
a new subdirectory for this particular application.
Before running the program, check that the used serial port, which is used on
Communica-
the PC, corresponds with the serial port set in the CONFIG.DAT file.
tion port
The CONFIG.DAT file is an ASCII text file, which can be read and modified with
any simple text editor (e.g. EDIT delivered with DOS). Care must be taken to
use an editor who adds no header to the file because this header makes it
illegible to the main program (no Word, no WordPerfect...).
Procedure to follow :
- Unlock the file CONFIG.DAT by the DOS command attrib -r config.dat
- Edit the file CONFIG.DAT by the DOS command edit config.dat
- In the paragraph “Communications Port”, check the parameter
"mcr_com_num".
Change the number if it doesn't correspond with the serial port of the PC.
- Press both the keys “ALT” and “F” on the keyboard of the PC.
A menu appears in the left corner of the screen.
The edition of the CONFIG.DAT file will be left after having pressed on the
key "X" on the keyboard.
Note: When the parameter has been changed, a submenu will appear. The
key “ENTER” has to be pressed to confirm the change.
- Lock the file by the DOS command attrib +r config.dat
92
AM 06.350e-MW Edition 3.2
The other important parameter is “LANG”. It selects the language you want
Language file
to use.
By default all the text strings in the program are in English and embedded in
the code. For any other language, the parameter LANG = "xxx" must be
added in CONFIG.DAT. At the same time a language file with the name
LANG_XXX.DAT must exist in the same directory (see below).
93
AM 06.350e-MW Edition 3.2
For other languages you can create your own file by translating all the
Creation of
strings. Therefore a reference language file LANG_REF.DAT holds all the
language file
strings in English and some useful comments for the translator. Care must be
taken not to exceed the maximum length of each string as is mentioned in
the language file. The language files must have the r-attribute set too (see
above).
94
AM 06.350e-MW Edition 3.2
For a language XXX you can modify this file for corrections. Care must be
Modification
taken not to exceed the maximum length of each string as is mentioned in
of language
the language file. The language files must have the r-attribute set too (see
file XXX
above).
95
AM 06.350e-MW Edition 3.2
7.2.1 Overview
Introduction All the setting parameters of the MCR are read from the MCR EEPROM of
the control module and stored in the database of the PC. Where necessary,
they are displayed.
In this chapter you will find all the information about the running of the
program and its environment.
MCR control The MCR control module is identifiable by its unique serial number, which is
module burned in the EEPROM and which cannot be changed on site.
identification
Serial number The serial number (S/N) of an MCR control module identifies this module. It
is a 6-digit number in the format “yy-xxxx” where yy stands for the year of
production and xxxx is a 4-digit sequential number.
Config file The Config-file is a file that stores the settings of the MCR (except the S/N of
the control module and some MCR dependant parameters).
Config-file The Config-file name is yy-xxxx.CFG, where yy-xxxx is the S/N number of the
name control module.
There is an individual Config-file for each MCR control module.
96
AM 06.350e-MW Edition 3.2
Log file The Log-file is a file that stores the events occurred to the MCR when
connected to a PC.
Log-file name The Log-file name is yy-xxxx.LOG, where yy-xxxx is the S/N number.
There is an individual Log-file for each MCR control module.
Type of entry All log entries consist of the date and time of the event followed by a
message string.
If a new event occurs, a new message is added to the Log-file and replaces
the oldest message in the PC memory.
Data stored • A message each time the PC connects to or disconnects from an MCR;
• A message each time a step command was issued to the MCR from the
PC or from the control tower;
• Any error detected by the MCR (burnt lamps, isolation error, regulation
error, ...) and which generates a message on the PC screen;
• Any communication error between PC and MCR;
• Any erroneous password entry by the user;
• Each change in position of the local selector switch on the MCR control
module front panel;
• A message each time the EFD or LFD is calibrated.
To print the If you exit the program, you can print the log files by a simple DOS “copy”
Log-file command to the printer port.
97
AM 06.350e-MW Edition 3.2
Database The MCR has a double database: one in EEPROM and the other in RAM.
After a power-down, when starting up again, all-important parameters are
fetched from a local EEPROM and copied to RAM. During normal operation
only the copy in RAM is used.
When connected, the PC reads the parameters in RAM and displays them on
the screen. When you modify a parameter, only the copy in the MCR RAM
gets changed.
After changing one or more parameters, you have three alternatives:
• To keep the changes and select the "Save to EEPROM" menu;
This automatically supersedes a binary file on the PC disk with the name
"yy-xxxx.CNF", where yy-xxxx is the serial number of the control module.
• To reject the changes and select the "Restore from EEPROM" menu. This
destroys all the RAM modifications and returns to the last EEPROM
contents;
• To read a set-up from disk. This is useful if several MCRs have to receive
the same set-up. The operator only needs to do the set-up on the first
one, then save the set-up to EEPROM at the same time creating a file on
disk. For the next MCRs, all he has to do is to select the menu "Restore
from file" and then enter the serial number of the previous MCR. The
settings are then restored from file to RAM (except the S/N of course and
the calibration parameters which are MCR-dependent), after this, the
"Save to EEPROM" menu must be selected to burn the data into the
EEPROM.
Each time data is written to the EEPROM, the date and time found on the PC
are copied with it. The next time the PC connects to that MCR, this time-
stamp is read back and put on the display; you know then immediately when
the last update occurred.
98
AM 06.350e-MW Edition 3.2
Start up After a successful connection, the machine enters an infinite loop during
which 2 tasks are performed:
• a regular and automatic data exchange with the MCR (STATUS);
• a check on the keyboard to capture operator commands.
Structure of
The screen is divided in “windows” with a “menu” bar at the top.
the screen
To the left, the status window (1) is always present and shows:
• the output current (as a thermometer-like vertical bargraph and as a value)
• the mains voltage
• the currently active step
• the number of burnt lamps (if LFD option is installed)
• the insulation resistance of the series circuit (if EFD option is installed)
The right window (top - 2) can be selected by the user via the menu bar (3) on
the top of the screen. 8 different dialogue screens are provided: Help, Log, PC
control, CCR Set-up, EFD, LFD, Power Monitor and Exit.
On the bottom right (4) the “prompt” window gives information such as:
• how to go into another window
• error messages or communication error messages
Picture
In the figure below the view of the first screen is shown.
99
AM 06.350e-MW Edition 3.2
Modification If you want to modify a parameter, you should select the correct window,
scroll into it with the UP/DOWN arrows until the cursor is on top of the
parameter and then hit <ENTER> to modify the parameter. For menus which
are larger than the window, there is an automatic window scrolling when the
cursor reaches the first (respective last) line.
Parameters are always organised in blocks with a header on top. To scroll
faster, use the PgUp and PgDw keys: they position the window on the
previous (respective next) header.
The cursor positions itself only on the lines that hold a parameter, never on a
header.
Parameters can only be selected and modified in the top right window.
Conditions to Access is only allowed if the drum selector on the MCR control module is in
modify the OFF position.
parameters
100
AM 06.350e-MW Edition 3.2
Passwords The purpose of the passwords is to protect the MCRs against any accidental
erroneous operations.
Depending on its importance, the parameter is protected by a USER- or by
an INSTALLATION-password.
By default the passwords are:
• user password: "ADB user"
• installation password: consult ADB
Note the upper and lower case characters!
There is a hierarchy between passwords: entering a correct installation
password also opens the user-password, but the reverse is not true.
It is almost impossible to provide an absolute tamper-proof barrier against
any intended sabotage. Nevertheless, it is our aim that you do not know the
installation password. This avoids the possibility that you could erroneously
reconfigure certain parameters with an eventual fatal result for the lamps or
the MCR.
It is then the responsibility of the installation engineer to set-up the MCR’s,
then to modify the INSTALLATION-password and to note it for future
interventions.
It is possible to change these passwords via the menu but of course only
after the correct corresponding password has been entered.
How long does a password allow access to the parameters? You can choose
between 3 alternatives via a menu:
• Re-entry of the password is required prior to each operation; this is
tedious but very safe.
• The password remains "open" during 10 minutes after the entry of the
correct password. During that 10-min interval the operator can continue
changing parameters without having to enter the password each time.
• The password remains open during 24 hours. This is useful when a
complete set-up of the MCR is necessary and the operator remains within
sight of the PC.
In any case, you can inhibit access to the MCR by an immediate recall of the
password via menu. If e.g. the password was opened for a 24-hour period,
but you have to leave the MCR unsupervised for an extended period, access
can be recalled. At the next attempt to modify a parameter, the password
must then be re-entered.
101
AM 06.350e-MW Edition 3.2
Type of Depending on the type of parameter which you want to modify, the program
parameters can react in different ways:
• Some parameters are READ-ONLY (e.g. the mains frequency) and cannot
be modified. When selected, they generate an overlay, which tells the
user that his demand cannot be complied with.
• Other parameters can only accept certain predefined values (E.g. the
output current can only be 4.15, 6.6, 8.33, 9.2, 12 or 20 A and nothing in-
between).
To select another value, just hit the <SPACE> bar until the correct value
appears in the overlay and then hit <ENTER> to validate the new value.
This erases the overlay, puts the new value in the correct window and
transmits the new value to the MCR.
This message is interleaved with the normal STATUS messages.
If you do not want to change the value, just hit <ESC> instead of <ENTER>;
the overlay disappears, but the value remains unchanged and there is no
message to the MCR.
For example, all "flag" parameters are of this type. They accept 2 values e.g.
on/off or enabled/disabled.
• Other parameters accept any value. You must enter the new value via the
keyboard. Hitting <ENTER> performs a value check and if it is outside
one of the predefined bounds, it is rejected and you receive an error
message in the bottom-right window. If it is accepted, the window is
updated and a message is sent to the MCR.
To exit an overlay without changing anything, just hit <ESC>.
Invalid If the program requires the entry of a value, the input routines will reject any
characters invalid characters and lock all keyboard entries until a <BACKSPACE> is
entered which clears the erroneous character.
Example: a parameter expects a number, but you enter an alphabetic
character by mistake.
Instead of seeing the normal underscore indicating the cursor position, you
will see a white square. The only way-out is to hit a <BACKSPACE> to
remove the last character. The square then disappears and the normal
cursor appears again. You can then proceed to enter the correct value.
In this way, the user is guaranteed that when he hits the final <RETURN> at
the end of his input, the string passed for analysis to the program contains
only valid characters.
102
AM 06.350e-MW Edition 3.2
To leave the To leave the program, go to the EXIT menu and enter the character
program displayed in the window (For English this is 'y' or 'Y');
To avoid losing data, you are warned when you try to leave the program and
some parameters were changed but not saved to EEPROM. You can then
force an exit and accept the consequences if there is a power down on the
MCR, or remain in the program and do a "save to EEPROM".
Trying to leave the program with Ctrl-C generates an error, but does not
interrupt the program. <Alt-Ctrl-Del> however is active and reboots the
machine.
103
AM 06.350e-MW Edition 3.2
7.4.1 Overview
Introduction In this chapter you will find all the information about the parameters and the
menus to use and modify them.
104
AM 06.350e-MW Edition 3.2
7.4.2 F1 Help
Description This menu displays a short help describing the different menus.
Description This menu display the last 50 events stored in the log-file. All the events are
numbered with the most recent on top.
2 operations are allowed: scrolling and deleting. The delete function only
removes the 50 lines in the program log.
The true log file on disk remains untouched, but that too can be deleted
using the normal DOS delete function.
105
AM 06.350e-MW Edition 3.2
7.4.4 F3 PC Control
Introduction The purpose of this menu is to allow you to take over control of the MCR with
the PC.
PC Control
1. If the number of brightness steps is set to 255 (stepless mode), the range is 69 to 255;
If the parameter “Separate ON/ OFF” is set to “YES”, the value “0” is also possible.
2. When a multiwire interface is installed, a step can be selected either by activating the
brightness step wire alone or together with a separate ON/OFF line (see also menu
F5). If the MCR is programmed for the last case, the ON/OFF line can be simulated by
this parameter.
3. This simulates the shutdown i.e. the action, which switches off the thyristors without
opening the power contactor. Under normal operation the shut-down is used in
conjunction with a circuit selector. If the MCR with Multiwire is programmed for a
circuit selector shut-down control through this menu will not be possible
Save/ Restore
Software version
106
AM 06.350e-MW Edition 3.2
MCR identification
Output current
Hardware
107
AM 06.350e-MW Edition 3.2
Submenu
Multiwire
108
AM 06.350e-MW Edition 3.2
(1) Controls the level at which an overcurrent alarm will be given if the error
persists for the time defined by delay 1.
(2) This level must be higher than the preceding one but with a shorter delay.
(3) If an overload occurs, the MCR cannot guarantee the level of the output
current. It will in any case generate a regulation error; moreover with this flag
the MCR can be forced to switch-off under those conditions.
(4) If the positive and negative half-waves of the output current do not have
the same value during the time specified by the delay parameter, an error is
generated. An asymmetry error is a sign for the existence of a DC
component on the output current, which is harmful to the power transformer
of the MCR.
(5) If the MCR cannot maintain the programmed output current, an alarm
appears after this delay
1
AM 06.350e-MW Edition 3.2
Mode of operation
Step settling Custom 0/ 0.5/ 1 / When you switch from one step to 0
speed 1.5/ 2 / 2.5 another, the MCR can either react
sec instantaneously or move to the
new step in the time defined here
(for a current variation from 0 to the
maximum value).
Back indication Custom YES / NO When this flag is set, the control YES
in local mode tower receives all back indication
signals. If this parameter is set to
NO there will be no back indication
signals to the tower when the MCR
operates in Local control.
ON-OFF-ON Custom 0/ 0.2/ 0.4/ When the MCR is rapidly switched 0
delay 0.6/ 0.8/ OFF and ON again, this parameter
1 sec defines the minimum delay during
which the MCR will remain OFF
regardless of the switching speed.
Local display
2
AM 06.350e-MW Edition 3.2
3
AM 06.350e-MW Edition 3.2
Calibration First, read carefully the WARNINGS in the paragraph “Calibration” (par
7.5.4). Calibration of the output current directly influences the output current
at Bmax.
The other calibrations act on the values displayed in the F8 Power Monitor
menu and the back indication values with the multiplexed remote control.
Change passwords
Error simulation
Only possible if the MCR is operational and delivers current into the
series circuit.
4
AM 06.350e-MW Edition 3.2
Control commands
Alarms If either of the next two parameters is exceeded, the MCR creates an alarm
(indicated by the led “Earth fault” on the front panel of the control module)
and also logged on disk
5
AM 06.350e-MW Edition 3.2
Setup
Calibration
6
AM 06.350e-MW Edition 3.2
Error simulation
7
AM 06.350e-MW Edition 3.2
Status
Control commands
Alarms For both “Number of lamps” and “VA-drop”, 2 levels can be defined. The
second level must be larger than the first one.
The delay is a time-out which retards the generation of an alarm to filter-out
spurious errors and which allows the series circuit to warm-up.
8
AM 06.350e-MW Edition 3.2
Hardware
9
AM 06.350e-MW Edition 3.2
Error simulation
If one of these errors is simulated, the MCR responds with the corresponding
back-indication. The Led Lamp fault on the front panel will light up.
10
AM 06.350e-MW Edition 3.2
Introduction None of the parameters displayed in this window are modifiable. All are
updated in real time from data read by the PC in the MCR database. If the
LFD module is not present, the output voltage and power measurements and
their derived parameters are not available and will not be shown.
Primary parameters
Power parameters
To exit the For the English language, enter 'y' to exit. For other languages it is always
program the first letter of the equivalent "YES" string. If you changed some
parameters and did not save the data to EEPROM, a supplementary warning
is generated. You can then select the "PC Control" menu, do a "Save to
EEPROM" and then come back to the EXIT menu and leave the program.
It is also possible to disregard this warning and exit without saving. You must
then be aware that the modified parameters exist only in the MCR RAM and
that they will be overwritten by the EEPROM data at the next power-down,
power-up sequence.
7.5 Calibration
11
AM 06.350e-MW Edition 3.2
7.5.1 Overview
Calibration A calibration requires instruments, which have a high precision class (0.5%),
instruments and which have been calibrated recently. Since most of the measured values
are phase-controlled sine waves, all instruments must be of the TRUE-RMS
type and certainly not of the moving coil and rectifier type.
The use of amperemeter clamps, although easy to use, is not advisable for
calibration for the following reasons:
• they are sensitive to magnetic fields in the environment. Due to the
proximity of the MCR, outside influence cannot be avoided;
• measurements are dependent on the position of the cable in the clamp;
• because clamps are mechanical devices, the closure of the magnetic
circuit can change for each measurement;
• clamps must be calibrated before use because of remanent magnetism;
• their precision is generally less than that of a good Ammeter.
We advise the use of a measuring transformer. Although it requires the
circuit to be opened, it guarantees a consistently high quality measurement.
Warning You must be aware that the following operations are potentially dangerous
and must be executed with the utmost care for the safety of the personnel.
12
AM 06.350e-MW Edition 3.2
Preliminary Before starting an LFD calibration, check the hardware settings, the series
circuit and the output power transformer tap setting.
Warming-up In order to perform exact measurements of the output voltage, the series
loop must warm up to a stable temperature. This temperature depends on
the ambient temperature.
You can verify the warming-up by monitoring the output voltage on the MCR
or the PC display. If the loop is cold, its resistance is low and the output
voltage for a given current is low. When the loop warms-up, its resistance will
increase and hence the output voltage will rise (for the same current). After a
time, the output voltage will level out when the final temperature is reached.
You must enter the required warm-up time as a parameter in the LFD menu.
"reference" The reference calibration is a series of measurements while all lamps are
calibration functional.
Erase the previous LFD calibration before starting the calibration!
Before doing this calibration, you must visually check that all lamps are
indeed working, that the correct output tap is wired and that the correct
selection is made in the LFD-menu for the primary voltage of the voltage
measuring transformer and the total loop length.
When you select the reference calibration, a secondary menu, in which you
can see the status of the measurements, appears.
By pushing button “D” on the keyboard you can toggle on or off the VDLV-
factor which, in case of a correct reference calibration, should stay lower
than 5, 10 or 15 (depending on the precision selected by the LFD during the
calibration).
During the warm-up phase, the output current is forced to the nominal output
current and the warm-up time is down-counted in this display.
During the measurements, the output current slowly decreases while the
measurements are made. At the end of this calibration you are prompted to
save the results in EEPROM. Answering “NO” gives the same result as
pushing the <ESC> key. The measurements will not be saved.
13
AM 06.350e-MW Edition 3.2
"lamps
This calibration is only possible after execution and saving of the reference
removed" calibration.
calibration
For the "lamps removed" calibration, you must remove a known number of
lamps and start the calibration. You are then prompted to enter this number
into the system. The MCR then measures again a series of parameters.
During the calibration, by pushing button “D” on the keyboard, you can toggle
on or off the VDLV-factor which, in case of a correct “lamps removed”
calibration should stay 128, 64, 32 or 16 (depending on the reactive power,
due to the unloaded transformers, in regards to the total loop power during
this calibration).
At the end you are prompted to save the results to EEPROM.
Answering “NO” gives the same result as pushing <ESC> key. The
measurements will not be saved.
When at a later date one or more lamps blow, the system can compute the
exact number of defective lamps by interpolating between both sets of
values.
Minimum Nr
To obtain an accurate calibration measurements, there are a minimum
of lamps to number of lamps, which must be removed depending on the system
remove configuration. In most cases 4 lamps will be sufficiently to perform the
calibration, otherwise some more lamps have to be removed.
(If the detected VDLV-factor does not reach the minimum value of 16, it will
be necessary to increase the number of unloaded transformers or to
increase the loop length (Menu F7) to perform the calibration.
14
AM 06.350e-MW Edition 3.2
EFD mode EFD calibration is only allowed if the module is in “continuous” mode.
EFD To calibrate the EFD module completely, activate in the F6 menu the
calibration calibration parameter “Full calibration”.
Proceed as follow :
- open the fused input switch of the MCR.
- earth the series circuit.
- disconnect the EFD module from the series circuit by disconnecting the
HV wire on the PCB1381 and PCB1384.
- close the fused input switch.
- follow the instructions written on the screen
It is a fully automatic operation and terminates with a message if an error
occurs
- save this parameterisation in the EEprom.
- open the fused input switch of the MCR
- reconnect the EFD to the series circuit.
- close the fused input switch
15
AM 06.350e-MW Edition 3.2
Introduction
When the MCR leaves the factory, it is fully calibrated. Moreover there are no
potentiometers, which can change their value because of ageing.
Still, if on site some components have to be exchanged, it may become
necessary to recalibrate the MCR.
Parameters to
There are 6 parameters to be calibrated:
be calibrated
• Output voltage,
• Output current,
• Output power,
• Input voltage,
• Input current,
• Input power.
MCR load All of the above parameters except the mains voltage can only be calibrated
if the MCR is sufficiently loaded. Indeed it is worse than useless to try and
calibrate e.g. the output voltage with only a small load connected.
Warning When you select a calibration parameter a Warning message appears onto
message the display to caution you. You can then abort the operation by hitting ESC or
continue by hitting any other key.
MCR Except for the output current, the normal sequence of events is that the PC
calibration forces the MCR to the maximum step, waits a bit, then prompts you to read
the value displayed on whatever instrument connected and then type this
value on the PC keyboard.
When the <ENTER> key is hit, all necessary correction factors are computed
and transmitted to the MCR. The MCR then returns to the step that was
previously selected.
16
N.V. ADB S.A.
Leuvensesteenweg, 585 – B 1930 Zaventem – Belgium
Tel. : 32/2/722.17.11 – Fax : 32/2/722.17.64
Companies in France, U.K. and U.S.A. – Agents all over the world