This Environmental Monitoring Report for area that covered by AHU 15116 has been reviewed
and approved by Quality Assurance.
Name Sign Date
Prepared by :
Reviewed by :
Reviewed by :
Approved by :
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
2. Physical Parameter
Physical parameter is consist of Temperature (⁰C), Relative Humidity (%) and Differential
Pressure (Pa). Data has been collected by Environment Monitoring System (EMS) that using
RTHx sensor to read the room temperature (⁰C) and Relative Humidity (%), and RPx
sensor to read the room Differential Pressure (Pa).
In the following table is a list of RTHx and RPx sensors that used to read the physical
parameters of the environment.
RTHx
RPx
Page 2 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
Page 3 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
Based on the graph above, it can be stated that the temperature trend
in this room still meets the requirements.
Based on the graph above, it can be stated that the temperature trend
in this room still meets the requirements.
Based on the graph above, it can be stated that the temperature trend
in this room still meets the requirements.
Page 4 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
2.1.1.4 Desinfectan-1
Based on the graph above, it can be stated that the temperature trend
in this room still meets the requirements.
Based on the graph above, it can be stated that the Temperature trend
in this room is not met the specification. It mean that the value are out
of specification, for this room there is a problem with the temperature
sensor so that the temperature reading does not match the actual
conditions.
Based on the graph above, it can be stated that the temperature trend
in this room still meets the requirements.
Page 5 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
Based on the graph above, it can be stated that the Relative Humidity
trend in this room still meets the requirements.
Based on the graph above, it can be stated that the Relative Humidity
trend in this room still meets the requirements.
Based on the graph above, it can be stated that the Relative Humidity
trend in this room still meets the requirements.
Page 6 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
2.1.2.4 Desinfectan-1
Based on the graph above, it can be stated that the Relative Humidity
trend in this room still meets the requirements.
Based on the graph above, it can be stated that the Relative Humidity
trend in this room still meets the requirements.
Based on the graph above, it can be stated that the Difference Pressure
trend in this room meets the requirements. Except for 08.00 – 16.00
Page 7 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
WIB, the mean value are out of specification, but there is no production
or analytical activity in the room so it can be justified.
Based on the graph above, it can be stated that the Differential Pressure
trend in this room is not met the specification. It mean that the value
are out of specification, for this room there is a problem with the
temperature sensor so that the temperature reading does not match
the actual conditions.
Based on the graph above, it can be stated that the Difference Pressure
trend in this room meets the requirements. Except for 08.00 – 16.00
WIB, the mean value are out of specification, but there is no production
or analytical activity in the room so it can be justified.
Based on the graph above, it can be stated that the Difference Pressure
trend in this room meets the requirements. Except for 08.00 – 16.00
Page 8 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
WIB, the mean value are out of specification, but there is no production
or analytical activity in the room so it can be justified.
Based on the graph above, it can be stated that the Difference Pressure
trend in this room still meets the requirements.
Page 9 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
3. Particulate Parameter
This test was not carried out because the processing time was not yet due.
Page 10 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
Page 11 of 12
Attachment-4
Doc Number : F-I-EM-05-037-04/02
Date of Issue : 20th May, 2019
5. Attachment List
No. Attachment Name Number of Pages
1 Raw Data Temperature, Relative Humidity and XX
Differential Pressure
2 Calibration Certificate of RTHx XX
3 Calibration Certificate of RPx XX
Page 12 of 12