REQUIREMENTS FOR 69kV TRANSMISSION LINE


(Wood/Concrete/Steel Poles)

SINGLE CIRCUIT
Pole Insulator String Assembly Ground String Assembly Guying Arrangement
Type S D J SWS SWT Special Case Normal Special Case
1-1SG if w/ def. angle.

1-2SG for every 7th Pole.


B 3 1 n/a n/a
1-2SG & 1-SG when the
7th Pole happened to be
w/ def. angle.

C1 3 1 n/a 1-SG & 1-DG

D 6 2 n/a 2-SG & 2-DG


1-3SG & 1-SG if w/ def.
Plus one (1) when
angle.
preceded or
E 6 2 succeeded by an 1-4SG
1-SG & 1-4SG when
H-Frame or 3-
preceded or succeeded
Pole
by an H-frame or 3-Pole
2-1SG if w/ def. angle
HS 3 2 n/a n/a
2-3SG for every 7th Pole
1-3SG & 1-2SG if w/ def.
HT 6 3 4 n/a 2-3SG
angle.
2-2SG & 1-3SG if w/ def.
3T 6 3 4 n/a 2-3SG &1-2SG
angle.

3D 6 4 n/a 3-2SG & 1-SG

REQUIRED NUMBER OF VIBRATION DAMPERS


For CONDUCTOR SINGLE POLE H-FRAME / 3-POLE

0 – 306 Meters 6 -do-

More than 306 Meters 12 -do-

For OHGW SINGLE POLE H-FRAME / 3-POLE

100 – 250 Meters 2 4

More than 251 Meters 4 8

Note: Type “B” to “B” and “HS” to “HS” Structures does not need VD

Parameter Characterizing:
VS

Where: VS = Distance between lowest sags


WS = S1+S2 / 2

If: VS/WS < 0.6 (Tension)


VS/WS > 0.6 (Suspension)

S1 S2

Structure A Structure B Structure C

1
Suspension clamp with socket connector type is to be used for conductor string assembly, and suspension clamp with anchor
shackle is to be used for ground string assembly.