Sunteți pe pagina 1din 4

Project : BW Opportunity

System : Heating, Ventilating, Air Conditioning and Refrigeration ( HVAC & R ) Package

Doc. No. : N / A

Subject : 3 Way Hand Valve Arrangement for Pneumatic F&G Damper ( Option I )

Date : 17 - 02 - 2020

3 Way Hand Valve @ Air


Dimension ( mm ) Closing Power Casing Casing IP Fire
Sr. No Tag. No. Location / Served Type Mode Consumption Haz. Rating Remark
(WxHxD) Time Supply Material Thickness Rating Rating
Location 1 Location 2 ( liter / cycle )

House Top

HT.1 97GE5607 67BAVxxxx Exhaust Air Duct Riser - Port 600 x 600 x 300 Pneumatic Fire & Gas 1.46 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
HT.2 97GE5610 67BAVxxxx Exhaust Air Duct - Lift Shaft 350 x 350 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3 Size to be confirmed.

HT.3 97GE5608 67BAVxxxx 67BAVxxxx Exhaust Air Duct Riser - Stbd. 900 x 900 x 300 Pneumatic Fire & Gas 1.46 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

"E" Deck

E.1 97GE5600 67BAVxxxx Supply Air Duct ( Port ) - Telecom Room 600 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
E.2 97GE5601 67BAVxxxx Return Air Duct ( Port ) - Telecom Room 450 x 450 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

E.3 97GE5603 67BAVxxxx 67BAVxxxx Natural Exhaust Air Duct - Staircase 600 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 2, IIB, T3

E.4 97GE5604 67BAVxxxx Supply Air Duct ( Stbd. ) - PB Telecom Room 300 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
E.5 97GE5605 67BAVxxxx Return Air Duct ( Stbd. ) - PB Telecom Room 350 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

"D" Deck

D.1 97GE5598 67BAVxxxx 67BAVxxxx Natural Exhaust Air Duct - Corridor ( Port ) 150 x 150 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

D.2 97GE5599 67BAVxxxx 67BAVxxxx Natural Exhaust Air Duct - Corridor ( Stbd. ) 150 x 150 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

"C" Deck

C.1 97GE5590 67BAVxxxx 67BAVxxxx Natural Exhaust Air Duct - Corridor ( Port ) 150 x 150 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 56 A0 Zone 2, IIB, T3

C.2 97GE5591 67BAVxxxx Supply Air Duct - UPS Room A 650 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
C.3 97GE5592 67BAVxxxx Return Air Duct - UPS Room A 700 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

C.4 97GE5593 67BAVxxxx Supply Air Duct from Riser ( Port ) to Fwd. Area 450 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

C.5 97GE5594 67BAVxxxx Supply Air Duct from Riser ( Port ) to Aft. Area 650 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe
67BAVxxxx
C.6 97GE5595 67BAVxxxx Return Air Duct to Riser ( Port ) 700 x 275 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe Size to be confirmed.

C.7 97GE5597 67BAVxxxx Exhaust Air Duct to Riser ( Port ) 430 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

C.8 97GE5596 67BAVxxxx 67BAVxxxx Natural Exhaust Air Duct - Corridor ( Stbd. ) 150 x 150 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 56 A0 Zone 2, IIB, T3

C.9 97GE5510 67BAVxxxx Supply Air Duct - Battery Room A 500 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A60 Zone 1, IIC, T3
67BAVxxxx
C.10 97GE5511 67BAVxxxx Exhaust Air Duct - Battery Room A 520 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 1, IIC, T3

"B" Deck

B.1 97GE5581 67BAVxxxx 67BAVxxxx Exhaust Air Duct - Hospital 300 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 2, IIB, T3

B.2 97GE5584 67BAVxxxx Supply Air Duct from Riser ( Port ) to Aft. Area 550 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

B.3 97GE5585 67BAVxxxx 67BAVxxxx Supply Air Duct from Riser ( Port ) to Fwd. Area 500 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

B.4 97GE5586 67BAVxxxx Return Air Duct to Riser ( Port ) 600 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

B.5 97GE5587 67BAVxxxx 67BAVxxxx Supply Air Duct - Staircase 300 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

B.6 97GE5588 67BAVxxxx 67BAVxxxx Supply Air Duct from Riser ( Stbd. ) to Fwd. Area 400 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

B.7 97GE5589 67BAVxxxx 67BAVxxxx Natural Exhaust Air Duct - Corridor ( Stbd. ) 200 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 2, IIB, T3
Project : BW Opportunity

System : Heating, Ventilating, Air Conditioning and Refrigeration ( HVAC & R ) Package

Doc. No. : N / A

Subject : 3 Way Hand Valve Arrangement for Pneumatic F&G Damper ( Option I )

Date : 17 - 02 - 2020

3 Way Hand Valve @ Air


Dimension ( mm ) Closing Power Casing Casing IP Fire
Sr. No Tag. No. Location / Served Type Mode Consumption Haz. Rating Remark
(WxHxD) Time Supply Material Thickness Rating Rating
Location 1 Location 2 ( liter / cycle )

"A" Deck

A.1 97GE5565 67BAVxxxx Return Air Duct - CCR 750 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
A.2 97GE5570 67BAVxxxx Supply Air Duct - CCR + Offshore Collaboration Room 750 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

A.3 97GE5567 67BAVxxxx Supply Air Duct from Riser ( Port ) to Aft. Area 350 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

A.4 97GE5568 67BAVxxxx 67BAVxxxx Supply Air Duct from Riser ( Port ) to Fwd. Area 750 x 275 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe Size to be confirmed.

A.5 97GE5569 67BAVxxxx Return Air Duct to Riser ( Port ) 750 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

A.6 97GE5571 67BAVxxxx Supply Air Duct - Secondary Fire Locker 250 x 175 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe Size to be confirmed.
67BAVxxxx
A.7 97GE5572 67BAVxxxx Retrurn Air Duct - Secondary Fire Locker 200 x 150 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

A.8 97GE5573 67BAVxxxx Supply Air Duct from Riser ( Stbd. ) to Fwd. Area 500 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

A.9 97GE5574 67BAVxxxx 67BAVxxxx Return Air Duct to Riser ( Stbd. ) 1,100 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

A.10 97GE5575 67BAVxxxx Supply Air Duct from Riser ( Stbd. ) to Aft. Area 800 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

A.11 97GE5576 67BAVxxxx Supply Air Duct - UPS Room B 700 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
A.12 97GE5577 67BAVxxxx Return Air Duct - UPS Room B 650 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

A.13 97GE5578 67BAVxxxx Supply Air Duct - Secondary Control Room 200 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
A.14 97GE5579 67BAVxxxx Return Air Duct - Secondary Control Room 325 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe Size to be confirmed.

A.15 97GE5512 67BAVxxxx Supply Air Duct - Battery Room B 400 x 350 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 1, IIC, T3
67BAVxxxx
A.16 97GE5513 67BAVxxxx Exhaust Air Duct - Battery Room B 430 x 350 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 1, IIC, T3

1st Poop Deck


1P.1 97GE5559 67BAVxxxx 67BAVxxxx Supply Air Duct from Riser ( Port ) to Fwd. Area 600 x 450 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

1P.2 97GE5560 67BAVxxxx Supply Air Duct - CER 900 x 400 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
1P.3 97GE5561 67BAVxxxx Return Air Duct - CER 1,250 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

1P.4 97GE5562 67BAVxxxx Supply Air Duct - Mess Room 840 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe
67BAVxxxx
1P.5 97GE5563 67BAVxxxx Exhaust Air Duct - Mess Room 900 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

1P.6 97GE5501 67BAVxxxx Supply Air Duct - Galley 500 x 500 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

1P.7 97GE5502 67BAVxxxx Exhaust Air Duct - Galley 800 x 400 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A60 Zone 2, IIB, T3

1P.8 97GE5503 67BAVxxxx 67BAVxxxx Exhaust Air Duct - Galley Hood 800 x 400 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

1P.9 97GE5505 67BAVxxxx Supply Air Duct - Dishwash Area 250 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

1P.10 97GE5506 67BAVxxxx Exhaust Air Duct - Dishwash Area 250 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A60 Zone 2, IIB, T3

Main Deck

M.1 97GE5522 67BAVxxxx Fresh Air Duct - Foam Room 300 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 2, IIB, T3
67BAVxxxx
M.2 97GE5523 67BAVxxxx Exhaust Air Duct - Foam Room 450 x 450 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 2, IIB, T3

M.3 97GE5525 67BAVxxxx 67BAVxxxx Exhaust Air Duct to Riser ( Port ) 550 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

M.4 97GE5526 67BAVxxxx Exhaust Air Duct - Fire Locker 300 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
M.5 97GE5527 67BAVxxxx Supply Air Duct - Fire Locker 250 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

M.6 97GE5528 67BAVxxxx 67BAVxxxx Supply Air Duct from Riser ( Port ) to Fwd. Area 750 x 350 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

M.7 97GE5529 67BAVxxxx Supply Air Duct - Laundry 600 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

M.8 97GE5534 67BAVxxxx 67BAVxxxx Exhaust Air Duct - Laundry 600 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

M.9 97GE5535 67BAVxxxx Exhaust Air Duct - Laundry 600 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe
Project : BW Opportunity

System : Heating, Ventilating, Air Conditioning and Refrigeration ( HVAC & R ) Package

Doc. No. : N / A

Subject : 3 Way Hand Valve Arrangement for Pneumatic F&G Damper ( Option I )

Date : 17 - 02 - 2020

3 Way Hand Valve @ Air


Dimension ( mm ) Closing Power Casing Casing IP Fire
Sr. No Tag. No. Location / Served Type Mode Consumption Haz. Rating Remark
(WxHxD) Time Supply Material Thickness Rating Rating
Location 1 Location 2 ( liter / cycle )

M.10 97GE5530 67BAVxxxx Fresh Air Duct - Oxygen and Acetylene Room 350 x 350 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 1, IIC, T3

M.11 97GE5531 67BAVxxxx Fresh Air Duct - Oxygen and Acetylene Room 300 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 1, IIC, T3
67BAVxxxx
M.12 97GE5532 67BAVxxxx Exhaust Air Duct - Oxygen and Acetylene Room 200 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 1, IIC, T3

M.13 97GE5533 67BAVxxxx Exhaust Air Duct - Oxygen and Acetylene Room 300 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 1, IIC, T3

M.14 97GE5536 67BAVxxxx 67BAVxxxx Supply Air Duct from Riser ( Stbd. ) to Fwd. Area 450 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

M.15 97GE5537 67BAVxxxx 67BAVxxxx Exhaust Air Duct to Riser ( Stbd. ) 400 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

M.16 97GE5538 67BAVxxxx Exhaust Air Duct - Paint Store 200 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 1, IIB, T3
67BAVxxxx
M.17 97GE5539 67BAVxxxx Fresh Air Duct - Paint Store 200 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 1, IIB, T3

M.18 97GE5540 67BAVxxxx Exhaust Air Duct - Smoking Room 200 x 150 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
M.19 97GE5541 67BAVxxxx Supply Air Duct - Smoking Room 250 x 175 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe Size to be confirmed.

M.20 97GE5542 67BAVxxxx 67BAVxxxx Supply Air Duct - Male Changing Room + Smoking Room 400 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

M.21 97GE5544 67BAVxxxx 67BAVxxxx Supply Air Duct - Staircase 300 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

M.22 97GE5553 67BAVxxxx Supply Air Duct Riser ( Port ) - Accommodation 1,000 x 1,150 x 300 Pneumatic Fire & Gas 1.46 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
M.23 97GE5554 67BAVxxxx Return Air Duct Riser ( Port ) - Accommodation 1,000 x 1,000 x 300 Pneumatic Fire & Gas 1.46 1s 24 VDC GSS 3 mm 55 A60 Safe

M.24 97GE5555 67BAVxxxx 67BAVxxxx Supply Air Duct Riser ( Port ) - Galley 500 x 500 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

M.25 97GE5556 67BAVxxxx Supply Air Duct Riser ( Stbd. ) - Accommodation 900 x 900 x 300 Pneumatic Fire & Gas 1.46 1s 24 VDC GSS 3 mm 55 A60 Safe
67BAVxxxx
M.26 97GE5557 67BAVxxxx Return Air Duct Riser ( Stbd. ) - Accommodation 700 x 600 x 300 Pneumatic Fire & Gas 1.46 1s 24 VDC GSS 3 mm 55 A60 Safe

M.27 97GE5508 67BAVxxxx Exhaust Air Duct - Laboratory 300 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A60 Zone 2, IIB, T3
67BAVxxxx
M.28 97GE5509 67BAVxxxx Fresh Air Duct - Laboratory 400 x 150 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A60 Zone 2, IIB, T3

M.29 97GE5609 67BAVxxxx 67BAVxxxx Fresh Air Duct - Lift Shaft 300 x 240 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 2, IIB, T3

M.30 97GE5524 Fresh Air Duct - Staircase 500 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 55 A0 Zone 2, IIB, T3
67BAVxxxx 67BAVxxxx
M.31 97GE5602 Fresh Air Duct - Staircase 500 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

M.32 97GE5613 67BAVxxxx Fresh Air Duct - Deck Store 400 x 200 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
M.33 97GE5614 67BAVxxxx Exhaust Air Duct - Deck Store 350 x 350 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

M.34 97GE5615 67BAVxxxx Fresh Air Duct - Pipe Workshop 250 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
M.35 97GE5616 67BAVxxxx Exhaust Air Duct - Pipe Workshop 250 x 250 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

1st Platform Deck


1PL.1 97GE5611 67BAVxxxx 67BAVxxxx Fresh Air Duct Riser - Galley AHU 500 x 1,200 x 300 Pneumatic Fire & Gas 2.35 1s 24 VDC SS 316 L 3 mm 56 A60 Zone 2, IIB, T3

1PL.2 97GE5543 67BAVxxxx 67BAVxxxx Fresh Air Duct Riser - Accommodation AHU 950 x 1,550 x 300 Pneumatic Fire & Gas 2.35 1s 24 VDC SS 316 L 3 mm 56 A60 Zone 2, IIB, T3

1PL.3 97GE5612 67BAVxxxx 67BAVxxxx Pressure Relief Duct - AHU Room 700 x 700 x 300 Pneumatic Fire & Gas 1.46 1s 24 VDC SS 316 L 3 mm 56 A60 Zone 2, IIB, T3
Project : BW Opportunity

System : Heating, Ventilating, Air Conditioning and Refrigeration ( HVAC & R ) Package

Doc. No. : N / A

Subject : 3 Way Hand Valve Arrangement for Pneumatic F&G Damper ( Option I )

Date : 17 - 02 - 2020

3 Way Hand Valve @ Air


Dimension ( mm ) Closing Power Casing Casing IP Fire
Sr. No Tag. No. Location / Served Type Mode Consumption Haz. Rating Remark
(WxHxD) Time Supply Material Thickness Rating Rating
Location 1 Location 2 ( liter / cycle )

Emergency Generator Room

EDG.1 97GE5617 67BAVxxxx Fresh Air Duct - Emergency Generator Room ( Normal ) 350 x 350 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
EDG.2 97GE5618 67BAVxxxx Exhaust Air Duct - Emergency Generator Room ( Normal ) 350 x 350 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

EDG.3 97GE5619 67BAVxxxx Fresh Air Duct - Emergency Generator Room ( Emergency ) 1,200 x 1,200 x 300 Pneumatic Fire & Gas 2.35 1s 24 VDC HDG / SS 316 L 10 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
EDG.4 97GE5620 67BAVxxxx Radiator Exhaust Air Outlet - Emergency Generator Room 2,500 x 2,800 x 300 Pneumatic Fire & Gas 8.64 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

Machinery Space

MS.1 97GE5629 67BAVxxxx Fresh Air Duct - Ventilation Fan A ( Aft. Port ) 1,500 x 1,500 x 300 Pneumatic Fire & Gas 4.32 1s 24 VDC HDG / SS 316 L 10 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
MS.2 97GE5630 67BAVxxxx Fresh Air Duct - Ventilation Fan C ( Fwd. Port ) 1,500 x 1,500 x 300 Pneumatic Fire & Gas 4.32 1s 24 VDC HDG / SS 316 L 10 mm 56 A0 Zone 2, IIB, T3

MS.3 97GE5631 67BAVxxxx Fresh Air Duct - Ventilation Fan B ( Aft. Stbd. ) 1,500 x 1,500 x 300 Pneumatic Fire & Gas 4.32 1s 24 VDC HDG / SS 316 L 10 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
MS.4 97GE5632 67BAVxxxx Fresh Air Duct - Ventilation Fan D ( Fwd. Stbd. ) 1,500 x 1,500 x 300 Pneumatic Fire & Gas 4.32 1s 24 VDC HDG / SS 316 L 10 mm 56 A0 Zone 2, IIB, T3

MS.5 97GE5633 67BAVxxxx Natural Exhaust Air Outlet ( Outboard Port ) 2,200 x 3,250 x 300 Pneumatic Fire & Gas 8.64 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
MS.6 97GE5634 67BAVxxxx Natural Exhaust Air Outlet ( Aft. Port ) 2,700 x 3,250 x 300 Pneumatic Fire & Gas 17.28 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

MS.7 97GE5635 67BAVxxxx 67BAVxxxx Natural Exhaust Air Outlet ( Funnel's Top Port ) 450 x 450 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

MS.8 97GE5636 67BAVxxxx Natural Exhaust Air Outlet ( Fwd. Stbd. ) 2,800 x 2,500 x 300 Pneumatic Fire & Gas 17.28 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3
67BAVxxxx
MS.9 97GE5637 67BAVxxxx Natural Exhaust Air Outlet ( Aft. Stbd. ) 1,800 x 3,200 x 300 Pneumatic Fire & Gas 8.64 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

MS.10 97GE5638 67BAVxxxx Fresh Air Duct - Purifier Room 530 x 400 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe
67BAVxxxx
MS.11 97GE5639 67BAVxxxx Exhaust Air Duct - Purifier Room 500 x 500 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A0 Safe

MS.12 97GE5640 67BAVxxxx Exhaust Air Duct - Purifier Room 500 x 500 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

MS.13 97GE5642 67BAVxxxx Natural Exhaust Air Duct - HPU Room 1,800 x 1,250 x 300 Pneumatic Fire & Gas 4.32 1s 24 VDC GSS 3 mm 55 A0 Safe
67BAVxxxx
MS.14 97GE5642 67BAVxxxx Supply Air Duct - HPU Room ( Port ) 1,000 x 500 x 300 Pneumatic Fire & Gas 2.35 1s 24 VDC GSS 3 mm 55 A0 Safe

Mechanical and E&I Workshop

E&I.1 97GE5621 67BAVxxxx 67BAVxxxx Exhaust Air Duct - Welding Area 450 x 450 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC SS 316 L 3 mm 56 A0 Zone 2, IIB, T3

440V Main Switchboard Room

SWBD.1 97GE5623 67BAVxxxx Supply Air Duct - SWBD Room 1,050 x 450 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

SWBD.2 97GE5624 67BAVxxxx 67BAVxxxx Return Air Duct - SWBD Room 650 x 650 x 300 Pneumatic Fire & Gas 1.46 1s 24 VDC GSS 3 mm 55 A60 Safe

SWBD.3 97GE5622 67BAVxxxx Pressure Relief Duct - SWBD Room 500 x 300 x 300 Pneumatic Fire & Gas 1.08 1s 24 VDC GSS 3 mm 55 A60 Safe

Note.
1. Dimension, material, thickness of casing, IP rating, fire rating, hazardous rating, etc,. shall be confirmed prior to procurement.