Sunteți pe pagina 1din 1

NEPCO Protection and Metering Dept.

Definite Time Voltage Relays (Over Voltage, Under Voltage)

1. General
Site: City Center Circuit: Capacitor 3AK0 Phase(s): R,Y,B
Type / Model No.: ABB REU523 Serial No.: 588511
Rating Voltage: (V): 110 V Rating Freq.: 50 (Hz)

2. Mechanical Inspection: OK
3. Tap Continuity Check: Ok

4. Pick Up/Drop off test


Existing Setting Pick Up Voltage Drop Off Voltage
Function V Percent R-Y Y-B B-R R-Y Y-B B-R
OV1 154 140% 155 156 156 147 146 147
OV2 176 160% 175 176 177 163 162 164
UV1 77 70% 74 75 75 79 80 79
UV2 44 40% 43 42 42 47 47 46

5. Timing test (Timing Check at Existing Tap Value


Voltage)
Timing Setting (s) Injected Operating Time (s)
Value
Stage Settings Stage Time (V) R-Y Y-B B-R
OV1 154 1 Sec 160 1.04 1.06 1.03
OV2 176 0.1 Sec 180 0.106 0.104 0.105
UV1 77 1 Sec 70 1.07 1.07 1.05
UV2 44 0.1 Sec 40 0.104 0.106 0.106

6. Operation Test
Alarm contact : OK Flag : OK
Trip Contact : OK

8. Remarks:      
Foreman Name : TAMER ALSHELLEH Eng. Name : MOHD ALGHUNIMAT
Foreman Sign. : Eng. Sign. :
Date : 04/02/2020 Date : 04/02/2020

Form #: QP44/01/F04 Page 1 of 1 Issue/Rev.: 1/a