The Zero-Sequence Harmonic Problem – In 1985, computers and their peripherals, might cause data
Power Quality International’s engineers discovered corruption in their communication network. This is an
high levels of zero-sequence harmonic current in Ohm’s Law problem. The circuits’ neutrals are
several 2000kVA, 208/120-volt electrical subsystems grounded at the source transformer, but the neutral
at an IBM research, testing and manufacturing facility conductors’ impedances generate voltage between
in Toronto, Canada. neutral and ground at the load-end of the circuits
(EH = IH x ZH).
When checking phase current balance at the main
secondary switchboards, we were surprised to find The Zero-Sequence Solution – After reporting these
high neutral currents, since the three phases were problems to IBM’s facility engineers, we were
well balanced. In analyzing this current, we found that challenged to find a solution. We’d had extensive
it was predominantly 180 Hz., with diminishing levels experience designing and applying large tuned L-C
of 540 Hz. and 900 Hz; the first three zero-sequence filters for industrial applications. L-C filters provide an
‘triplen’ harmonic currents. Although previously ideal harmonic current shunt, when the nonlinear
described mathematically, we were unable to find any loads and their harmonic profiles, are steady-state.
information, including a search of IEEE papers, on the The problem is that in an office environment, the loads
discovery of zero-sequence ‘triplen’ harmonics in and their harmonic profiles are dynamic.
electrical distribution systems.
In looking for a solution, it occurred to us that a three-
On further investigation and analysis, we concluded phase, four-wire zigzag configured autotransformer
that zero-sequence harmonic currents can only occur may provide a satisfactory solution, since, if properly
when nonlinear loads are connected phase-to-neutral configured, it would have an ultra-low zero-sequence
in a three-phase, four-wire distribution system. impedance. If applied as-close-as-possible to the
Although positive- and negative-sequence harmonic single phase nonlinear loads (i.e. at the branch-
currents have always existed in industrial power circuits’ subpanel), it would shunt all zero-sequence
conversion systems, these nonlinear loads are always harmonic currents, including the zero-sequence
connected phase-to-phase. components of the fundamental and all positive- and
negative-sequences that result from phase current
In 1985, IBM was developing and testing their first
imbalance under nonlinear loading. In addition to
personal computers. During their test cycle, we
acting as a ‘triplen’ harmonic current shunt, the filter
learned they had hundreds, if not thousands, of PCs
would also provide phase current balancing.
supplied by these two subsystems.
Our original filter provided zero-sequence impedance
In addition to the fire and safety issues created by
that was approximately 100 times lower than the
excessively high neutral current, we also discovered
source transformer and its feeder and branch circuit’s
very high zero-sequence voltages between the branch
combined source impedance. With this result, in 1986
circuits’ shared neutrals and their ground conductors
we applied these zero-sequence shunt filters at every
at the 120-volt receptacle loads. We discovered that
remote power panel supplied by the two 2000kVA
above 5-volts, many of the PCs’ switch-mode power
subsystems. All identified power quality problems
supplies would fail prematurely. We also found that a
were resolved.
voltage difference of more than 5-volts, between
POWER QUALITY INTERNATIONAL, LLC
2404 Merchant Avenue, Odessa, Florida 33556 USA
888‐539‐7712 ⦁ www.powerquality.net
The Measurement of ‘Penalty Losses’ – Power factoring in the cost of each kilowatt hour it’s possible
Quality International has recently undertaken field to calculate the cost of waste energy over a week, a
measurements using a Fluke Model 435, Series 2 month, or a year.
Analyzer. The instrument’s Unified Power
The screen capture below identifies Unbalance load
measurement system uses a combination of classical
and Neutral current losses as accounting for most of
methods (IEEE 1458-2010) and the University of
the circuit’s ‘penalty losses’. The Effective kW power
Valencia’s mathematical calculations to express
losses are due to the circuit’s resistance. In a
power and energy measurements that directly quantify
nonlinear environment, with unbalanced loading,
the wasted energy or ‘penalty losses’ in electrical
‘penalty losses’ may exceed the circuit’s resistance
circuits. Unified Power measures harmonics and
losses
unbalance waste in terms of kilowatts, and by
POWER QUALITY INTERNATIONAL, LLC
The Loads – With a 95% reduction in zero-sequence communication network, a common problem in
phase currents, the distortion of voltage at the circuit’s computer and gaming machine networks.
loads will substantially reduce their internal ‘penalty
The Source Transformer – A reduction in zero-
losses’. With the application of zero-sequence
sequence phase and neutral harmonic current, THDI
harmonic filters, experience has taught us that the
and K-factor will reduce the Impedance (Load) Losses
reduction of load ‘penalty losses’ often exceeds circuit
in the transformer that supplies the circuit.
’penalty losses’.
Notes:
With a reduction in neutral current of almost 98%, [1] The application of the I0Filters™ increases the circuit’s
inductive reactance from 4.7W to 6.4W.
phase-to-neutral voltage at the loads, which may
[2] ITIC – Information Technology Industry Council.
otherwise exceed the ITIC [3] 5V maximum or the [3] IGT – International Gaming Technologies
IGT [4] requirement, will be brought close to zero. This [4] It is important to understand that neither load nor source
transformer losses are measured by Fluke’s Energy Loss
outcome will eliminate corruption of data in the Calculator.