Model FS-3 MANUAL HEAD OFFICE


40-11 2-ga, Mullae-dong, Youngdeungpo-gu,
Seoul, Korea
TEL: (82-2)2679-4697 FAX:(82-2)2633-3332
■MAIN PRODUCTS
INSTRUCTION MANUAL □DIGITAL:Temperature Controller,
Counter/Timer,
This manual primarily describes precautions Tachometer/Panel Meter
required in installing and wiring the temperature □SENSOR: Proximity Switch/Photo Electric Sensor,
controller. When using the temperature controller, Rotary Encoder/Optical Fiber Sensor,
please refer to the pertinet catalog for detailed R.T.D/Thermo Couple
information. □ANALOG:Timer/Temperature Controller

1 RATING AND CAPACITY


CLASSIFICATION FOR LOW SENSITIVITY FOR HIGH SENSITIVITY ● EXAMPLE
Power supply 220VAC, 50/60Hz
① Case of water supply
Operation voltage ±10% of power supply
The pump is stop when the surface of the water arrive at E1.
Secondary voltage 8VAC 24VAC
And, the pump is play when the surface of the water make less
Power consumption Approx. 3.2VA than E2.
WORKING : The less than 80ms
Response time R S T
RESET : The less than 160ms
Interelectrode 0~Approx.7KΩ 0~Approx.27KΩ
operating resistance 4 5
3 6
Interelectrode
Approx.15KΩ~∞Ω Approx.38KΩ~∞Ω 2 7
release resistance 1 8

Control output 250VAC 5A(Resistance load)

Output relay life Electronical: The more than 500,000 times (Resistance load)
E1 OFF
Mechanical: The more than 5,000,000 times
E2
Insulation resistance The more than 100MΩ(500VDC M) E3 ON
Withstand voltage 2,000VAC 50/60Hz for a minute M P
Ambient temperature -10~+50°
C (Without ice condensation)
Ambient humidity 35~85%RH

2 CONNECTION DIAGRAM
● EXTERNAL CONNECTION DIAGRAM ② Case of draining
Opposite to the above
220 VAC
4 5 50/60Hz
CONTACT
RATING 3 6
250 VAC 5A 2 7
R S T

1 8

ELECTRODE
4 5
※(NOTE) Please connect to the E3 3 6
2 7
E1
1 8
E2
E3
● INTERNAL CONNECTION DIAGRAM
① High sensitivity ② Low sensitivity
24V 24V

220 VAC Control circuit 220 VAC Control circuit M P


24V 8V

E1
ON
NO NC NO NC E2
OFF
C C
E3

5 6 3 4 2 1 8 7 5 6 3 4 2 1 8 7
E3 E2 E1 E3 E2 E1
3 EXTERNAL DIMENSION

91
49
82.5

ON
FS-3
FLOATLESS LEVEL SWITCH

AC 220V
4 5 50/60Hz
3 6 62 77
2 7
77 60.5
1 8
CONTACT
RATING
E3 E2 E1 ELECTRODE
AC 250V 5A

SECONDARY VOLTAGE : AC 24V MADE IN KOREA

3
20

( Unit : mm )

4 ARTICLES UNDER SUSPICION


● Please connect to the assigned terminal after confirm to input power.
● Do not use a overload of the more than rating in the consist of output relay contact.
● Please make shorter as possible the wiring length of between electrode and instrument.
● The wiring of between electrode and instrument should be used a thick wiring as possible.
● Do not establish at a place that temperature or humity are high.