Produced on 27/01/2020 with Xpress Selection V8.6.7 - database DIL 13.8.

Project name ALMACEN SUNARP


Project address Peru
Reference SUNARP
Client name Emilio De Rutte
Revision B_GCM_01

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RXQ10TATL 1 Cooling only VRV IV(TATL)
RXQ12TATL 1 Cooling only VRV IV(TATL)
RXQ18TATL 3 Cooling only VRV IV(TATL)
FXTQ48TAVJUA 4 VRV T - Vertical AHU
FXTQ60TAVJUA 10 VRV T - Vertical AHU
KHRP26A33T 2 Refnet branch piping kit
KHRP26A72T 7 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 2 Refnet branch piping kit
BRC1E73 14 Navigation remote controller
BHFP22P100 2 Kit de conexión de tuberías para unidades exteriores múltiples
R410A 74.3kg Extra refrigerant charge
Piping ⅜" 257.5m
Piping ½" 45.3m
Piping ⅝" 252.1m
Piping ¾" 64.1m
Piping ⅞" 96.5m
Piping 1⅛" 57.8m
Piping 1¼" 59.3m
Piping 1⅜" 4.8m
Piping 1⅝" 78.6m

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
▼ indicates a model size down due to tolerance
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Applied indoor capacity safety factor or tolerance
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 2
2.2. VRV - 1 - RXQ36TATL
Capacity data at conditions and connection ratio (107%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C cfm
UMA-01 FXTQ60TAVJUA 23.6 / 16.8 61873 57392 46405 43542 Auto 11.4 1801
UMA-02 FXTQ60TAVJUA 23.6 / 16.8 61873 57392 46405 43542 Auto 11.4 1801
UMA-03 FXTQ60TAVJUA 23.6 / 16.8 61873 57392 46405 43542 Auto 11.4 1801
UMA-04 FXTQ60TAVJUA 23.6 / 16.8 61873 57392 46405 43542 Auto 11.4 1801
UMA-05 FXTQ60TAVJUA 23.6 / 16.8 61873 57392 46405 43542 Auto 11.4 1801
UMA-06 FXTQ60TAVJUA 23.6 / 16.8 61873 57392 46405 43542 Auto 11.4 1801

Required cooling capacity towards the outdoor unit: 344353BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UMA-01 43.6-50.2 208V 1ph 8.6 622×1473×533 76
UMA-02 43.6-50.2 208V 1ph 8.6 622×1473×533 76
UMA-03 43.6-50.2 208V 1ph 8.6 622×1473×533 76
UMA-04 43.6-50.2 208V 1ph 8.6 622×1473×533 76
UMA-05 43.6-50.2 208V 1ph 8.6 622×1473×533 76
UMA-06 43.6-50.2 208V 1ph 8.6 622×1473×533 76

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 3
2.3. VRV - 2 - RXQ18TATL
Capacity data at conditions and connection ratio (111%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C cfm
UMA-07 FXTQ48TAVJUA 23.6 / 16.8 44131 45859 33098 34289 Auto 12.2 1519
UMA-08 FXTQ48TAVJUA 23.6 / 16.8 44131 45859 33098 34289 Auto 12.2 1519
UMA-09 FXTQ48TAVJUA 23.6 / 16.8 44131 45859 33098 34289 Auto 12.2 1519
UMA-10 FXTQ48TAVJUA 23.6 / 16.8 44131 45859 33098 34289 Auto 12.2 1519

Required cooling capacity towards the outdoor unit: 176523BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UMA-07 45.6-53.8 208V 1ph 6.5 533×1357×533 68
UMA-08 45.6-53.8 208V 1ph 6.5 533×1357×533 68
UMA-09 45.6-53.8 208V 1ph 6.5 533×1357×533 68
UMA-10 45.6-53.8 208V 1ph 6.5 533×1357×533 68

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 4
2.4. VRV - 3 - RXQ22TATL
Capacity data at conditions and connection ratio (116%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C cfm
UMA-11 FXTQ60TAVJUA 23.6 / 16.8 54595 57392 40946 43542 Auto 11.4 1801
UMA-12 FXTQ60TAVJUA 23.6 / 16.8 54595 57392 40946 43542 Auto 11.4 1801
UMA-13 FXTQ60TAVJUA 23.6 / 16.8 54595 57392 40946 43542 Auto 11.4 1801
UMA-14 FXTQ60TAVJUA 23.6 / 16.8 54595 57392 40946 43542 Auto 11.4 1801

Required cooling capacity towards the outdoor unit: 218379BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UMA-11 43.6-50.2 208V 1ph 8.6 622×1473×533 76
UMA-12 43.6-50.2 208V 1ph 8.6 622×1473×533 76
UMA-13 43.6-50.2 208V 1ph 8.6 622×1473×533 76
UMA-14 43.6-50.2 208V 1ph 8.6 622×1473×533 76

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 5
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
▼ Optimized selection: Smaller outdoor model selected than standard proposed model
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 6
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C BTU/h BTU/h °C BTU/h BTU/h
VRV - 1 RXQ36TATL ▼ 107 31.0 294121 (-14.6%) 344353
VRV - 2 RXQ18TATL ▼ 111 31.0 152708 (-13.5%) 176523
VRV - 3 RXQ22TATL ▼ 116 31.0 193352 (-11.5%) 218379

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
VRV - 1 RXQ36TATL 123.1 R410A 21.0 42.0
VRV - 2 RXQ18TATL 96.4 R410A 10.5 21.5
VRV - 3 RXQ22TATL 54.5 R410A 12.3 10.8

Name Model PS MCA WxHxD Wght


A mm kg
VRV - 1 RXQ36TATL 220V 3ph
× RXQ18TATL 55 1240×1657×765 285
× RXQ18TATL 55 1240×1657×765 285
VRV - 2 RXQ18TATL 220V 3ph 55 1240×1657×765 285
VRV - 3 RXQ22TATL 220V 3ph
× RXQ12TATL 43.1 930×1657×765 195
× RXQ10TATL 38.1 930×1657×765 195

Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 7
3.2.1. VRV - 1 - RXQ36TATL

Model Qty Description


RXQ18TATL 2 Cooling only VRV IV(TATL)
FXTQ60TAVJUA 6 VRV T - Vertical AHU
KHRP26A72T 3 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 2 Refnet branch piping kit
BRC1E73 6 Navigation remote controller
BHFP22P100 1 Kit de conexión de tuberías para unidades exteriores múltiples
R410A 42.0kg Extra refrigerant charge
Piping ⅜" 96.6m
Piping ½" 35.7m
Piping ⅝" 96.6m
Piping ¾" 4.8m
Piping ⅞" 78.6m
Piping 1⅛" 35.7m
Piping 1⅜" 4.8m
Piping 1⅝" 78.6m

Standard factory refrigerant charge (5m actual piping length) = 21.0kg


Extra refrigerant charge = 78.6m(ø⅞") × 0.36 + 96.6m(ø⅜") × 0.057 + 35.7m(ø½") × 0.11 + 4.8m(ø¾") × 0.26 + A
+ B = 42.0kg
A [ CR 107%, actual length 118.6m ] = 3.0kg
B [ 36HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 8
3.2.2. VRV - 2 - RXQ18TATL

Model Qty Description


RXQ18TATL 1 Cooling only VRV IV(TATL)
FXTQ48TAVJUA 4 VRV T - Vertical AHU
KHRP26A33T 2 Refnet branch piping kit
KHRP26A72T 1 Refnet branch piping kit
BRC1E73 4 Navigation remote controller
R410A 21.5kg Extra refrigerant charge
Piping ⅜" 80.3m
Piping ⅝" 62.4m
Piping ¾" 59.3m
Piping ⅞" 17.9m
Piping 1¼" 59.3m

Standard factory refrigerant charge (5m actual piping length) = 10.5kg


Extra refrigerant charge = 59.3m(ø¾") × 0.26 + 80.3m(ø⅜") × 0.057 + A + B = 21.5kg
A [ CR 111%, actual length 93.0m ] = 1.5kg
B [ 18HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 9
3.2.3. VRV - 3 - RXQ22TATL

Model Qty Description


RXQ10TATL 1 Cooling only VRV IV(TATL)
RXQ12TATL 1 Cooling only VRV IV(TATL)
FXTQ60TAVJUA 4 VRV T - Vertical AHU
KHRP26A72T 3 Refnet branch piping kit
BRC1E73 4 Navigation remote controller
BHFP22P100 1 Kit de conexión de tuberías para unidades exteriores múltiples
R410A 10.8kg Extra refrigerant charge
Piping ⅜" 80.6m
Piping ½" 9.6m
Piping ⅝" 93.1m
Piping 1⅛" 22.1m

Standard factory refrigerant charge (5m actual piping length) = 12.3kg


Extra refrigerant charge = 12.5m(ø⅝") × 0.17 + 80.6m(ø⅜") × 0.057 + 9.6m(ø½") × 0.11 + A + B = 10.8kg
A [ CR 116%, actual length 50.0m ] = 3.0kg
B [ 22HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 10
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping VRV - 1


VRV - 1
RXQ36TATL
RXQ18TATL RXQ18TATL

⅝"×1⅛" ⅝"×1⅛"

BHFP22P100

78.6m [2] 4.8m 17.3m [1] 14.8m [4]


⅞"×1⅝" * ¾"×1⅜" ½"×1⅛" ⅜"×⅝"
KHRP26A73T + KHRP26A73T + KHRP26A72T
KHRP26M73TP KHRP26M73TP
UMA-01
FXTQ60TAVJUA
15.5m [4]
⅜"×⅝"

UMA-02
FXTQ60TAVJUA
8.7m [1] 6.0m [2]
½"×1⅛" ⅜"×⅝"
KHRP26A72T

UMA-03
FXTQ60TAVJUA
26.5m [4]
⅜"×⅝"

UMA-04
FXTQ60TAVJUA
9.7m [2] 27.1m [5]
½"×1⅛" ⅜"×⅝"
KHRP26A72T

UMA-06
FXTQ60TAVJUA
6.7m [3]
⅜"×⅝"

UMA-05
FXTQ60TAVJUA

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 11
4.2. Piping VRV - 2
VRV - 2
RXQ18TATL

59.3m [2] 9.2m 7.6m [3]


¾"×1¼" * ⅜"×⅞" ⅜"×⅝"
KHRP26A72T KHRP26A33T

UMA-07
FXTQ48TAVJUA
24.5m [5]
⅜"×⅝"

UMA-08
FXTQ48TAVJUA
8.7m [2] 6.7m [3]
⅜"×⅞" ⅜"×⅝"
KHRP26A33T

UMA-09
FXTQ48TAVJUA
23.6m [5]
⅜"×⅝"

UMA-10
FXTQ48TAVJUA

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 12
4.3. Piping VRV - 3
VRV - 3
RXQ22TATL
RXQ12TATL RXQ10TATL

½"×1⅛" ⅜"×⅞"

BHFP22P100

12.5m [2] 7.0m 14.3m [4]


⅝"×1⅛" ½"×1⅛" ⅜"×⅝"
KHRP26A72T KHRP26A72T

UMA-11
FXTQ60TAVJUA
27.5m [4]
⅜"×⅝"

UMA-12
FXTQ60TAVJUA
2.6m [2] 3.9m [4]
½"×1⅛" ⅜"×⅝"
KHRP26A72T

UMA-13
FXTQ60TAVJUA
34.9m [6]
⅜"×⅝"

UMA-14
FXTQ60TAVJUA

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 13
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring VRV - 1


P1,P2
VRV - 1 UMA-01 BRC1E73
RXQ36TATL FXTQ60TAVJUA
IN F1,F2 F1,F2 L,N 8.6A 1ph
RXQ18TATL
Q1,Q2 L1,L2,L3 P1,P2
UMA-02 BRC1E73
55A 3ph
FXTQ60TAVJUA
RXQ18TATL F1,F2 L,N 8.6A 1ph
Q1,Q2 L1,L2,L3
55A 3ph P1,P2
UMA-03 BRC1E73
FXTQ60TAVJUA
F1,F2 L,N 8.6A 1ph

P1,P2
UMA-04 BRC1E73
FXTQ60TAVJUA
F1,F2 L,N 8.6A 1ph

P1,P2
UMA-06 BRC1E73
FXTQ60TAVJUA
F1,F2 L,N 8.6A 1ph

P1,P2
UMA-05 BRC1E73
FXTQ60TAVJUA
F1,F2 L,N 8.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 14
5.2. Wiring VRV - 2
P1,P2
VRV - 2 UMA-07 BRC1E73
RXQ18TATL FXTQ48TAVJUA
IN F1,F2 F1,F2 L,N 6.5A 1ph

L1,L2,L3 55A 3ph


P1,P2
UMA-08 BRC1E73
FXTQ48TAVJUA
F1,F2 L,N 6.5A 1ph

P1,P2
UMA-09 BRC1E73
FXTQ48TAVJUA
F1,F2 L,N 6.5A 1ph

P1,P2
UMA-10 BRC1E73
FXTQ48TAVJUA
F1,F2 L,N 6.5A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 15
5.3. Wiring VRV - 3
P1,P2
VRV - 3 UMA-11 BRC1E73
RXQ22TATL FXTQ60TAVJUA
IN F1,F2 F1,F2 L,N 8.6A 1ph
RXQ12TATL
Q1,Q2 L1,L2,L3 P1,P2
UMA-12 BRC1E73
43.1A 3ph
FXTQ60TAVJUA
RXQ10TATL F1,F2 L,N 8.6A 1ph
Q1,Q2 L1,L2,L3
38.1A 3ph P1,P2
UMA-13 BRC1E73
FXTQ60TAVJUA
F1,F2 L,N 8.6A 1ph

P1,P2
UMA-14 BRC1E73
FXTQ60TAVJUA
F1,F2 L,N 8.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 16
6. Device Options
6.1. Outdoor Unit Options
Model Description Used by
BHFP22P100 Kit de conexión de tuberías para unidades exteriores múltiples VRV - 3 [RXQ22TATL] VRV - 1 [RXQ36TATL]

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 17