Sunteți pe pagina 1din 12

ATiCS Change Over

2-pole AC 230 V / up to 80 A

Functions

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 1


Principle use in Group-2-Rooms

 For all Variants of Change-Over


 SAFE / MAIN t ≤ 15 s
 SAFE / UPS t ≤ 0,5 s
 UPS / SAFE t ≤ 0,5 s
 Free selection of the
main line

 For the OR
 In addition with a separate Isometer
IR426-D47 to monitor the insulation-
level of the OR-lamp

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 2


Principle use in Group-2-Rooms

MAIN / SAFE – change-over

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 3


Principle use in Group-2-Rooms – ICU – with fault location

 For all Variants of Change-Over


 SAFE / MAIN t ≤ 15 s
 SAFE / UPS t ≤ 0,5 s
 UPS / SAFE t ≤ 0,5 s
 Free selection of the
main line

 For ICU
 Additional Earth fault-Detection-
System EDS
 With optional Bypass-Switch for
uninterruptable power supply in case
of tests and repairs

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 4


Function of the Bypass-Switch

 Exchange without power interruption


e.G. for ICU
 Auxiliary switch for positioning
indication

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 5


Power supply of Remote Alarm Units MK or TM

 The power supply 410 is


responsible for the safe supply
of power to the remote alarm
units MK and TM
 The supply of power is
guaranteed even in case one
supplying line fails

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 6


Catalog for ATiCS !

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 7


Pictures of ATiCS !

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 8


The worldwide first „All-in-one“ Change-Over- and Monitoring-Module
with functional safety for Group-2-Rooms and more …

Incoming side Positioning


indication

Protective cover Mechanical


padlock

Mech. switch
I – 0 - II
alarm-LEDs

Graphical display Allen-key


for manual
change over
User interface

jumper Plug-in terminals

Load side

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 9


Completely plugable

Colour-coded
Plug-in for
plug-in terminals for
incoming side
electronics

Plug-in for
load side

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 10


The internal technology

 Quick change-over: ≤ 350 ms


 Mechanical interlock
 Stabile switching-positions

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 11


Manual - / Auto - Mode

 Activation Manual Mode  Selection of switch-mode with  Protection against


through opening the cover the help of the allen-key illegal use through
 There will a signalization with a integrated padlock
buzzer and in the display

© Bender · Germany · www.bender-de.com · Fxxx (ATICS)_PPT_de_201011176 _Draft Sellner · Nr. 12

S-ar putea să vă placă și