Sunteți pe pagina 1din 8

SE350EL

Generator Automatic
Voltage Regulator
Operation Manual

A Regal Brand
1. SPECIFICATION Burden
Sensing & Power Input 500VA MAX
Voltage 85 ~ 120 VAC /190 ~ 240 VAC
Frequency 50 / 60 Hz, Jumper selectable External Volts Adjustment
± 5% with 1K ohm 1 watt trimmer
Output ± 10% with 2K ohm 1 watt trimmer
Voltage Max. 73 VDC @ 220 VAC input
Current Continuous 3.5A EMI Suppression
Intermittent 7A for 10 sec Internal electromagnetic interference filtering
(52 / 105VDC)
Resistance Min. 15 ohm Max. 100 ohm Unit Power Dissipation
Max. 8 watt
Voltage Regulation
< ± 1% ( with 4% engine governing ) Under Frequency Protection (Factory Setting)
60 Hz system presets knee point at 54 ~ 61 Hz
Voltage Build-up 50 Hz system presets knee point at 45 ~ 51 Hz
Residual voltage at AVR terminal > 5 VAC
Dimensions
Operating Temperature 99.5mm L * 67mm W * 47.5mm H
- 40°C to + 60°C
Weight
Storage Temperature 205g ± 2%
- 65°C to + 85°C
Fuse
T6.3AH250V Part# A-527066-2

OUT P UT 73 V dc max C urrent, max 3.5A

INP UT 85-120 / 190-240 V ac , 50/60 HZ

V OL T A G E R E G UL A T OR
P ower,max 700V A

MODE L S E 350E L

UNIT: mm
Figure 1 - Outline and Drilling Diagram

2
J umper
F requency

Hz Hz
60 50

OUT P UT 73 V dc max C urrent, max 3.5A

INP UT 85-120 / 190-240 V ac , 50/60 HZ

V OL T A G E R E G UL A T OR
4

P ower,max 700V A

MODE L S E 350E L
6
R ed
J2

J umper
R heos tat

7
F-
J1

F+
3
OF F

ON

DIP S W F US E 4A /250V
Figure 2 - Jumper and Potentiometer Control Locations

2. WIRING ±5% voltage range, use a 1000 ohm 1/2 watt rheo-
stat). See Figure 6, 7 and 8.
2.1 Exciter Field Power Circuit
• Connect terminal “F+” and “F-“ to field “+” and 2.4 Stability Adjustment (STAB)
“–”. • Stability is the ability of the generator to respond
to load changes. Decreasing the stability makes
• See Figure 6, 7 and 8 for connection diagrams. the generator less sluggish and faster to respond
to load changes. If the stability is decreased too
CAUTION much, the generator will tend to hunt under
The exciter field dc resistance should be between steady state conditions.
15 and 100 ohms.
2.5 V/HZ Roll-Off Frequency Selection (U/F)
If the exciter field dc resistance is less than 15 ohms • The roll off point is the frequency where the
and the full load field current does not exceed the generator voltage starts to decrease. This reduces
maximum continuous current rating of the AVR, add the load to the engine, which allows the engine
a resistor in series of sufficient wattage to increase to recover. Use jumper to select 50 HZ or 60 Hz.
the total resistance to 15 ohms. The screwdriver adjustable potentiometer sets the
roll-off frequency from 54~61 Hz in the 60 Hz
2.2 Sensing & Power Input Circuit 120/240V setting or from 45~51 Hz in the 50 Hz setting. We
Use terminals 3 and 4 for input power and also use the Roll-Off to disconnect the regulator
sensing. The voltage input can be either 120 or 240 when you shut off the engine.
VAC selectable via DIP switch.
• The SE350EL has the roll-off point preset to 58 Hz
See Figure 4 . at 60 Hz and 48 Hz at 50 Hz. To change the roll-off
point, adjust engine speed to the preferred Hz (50
2.3 Voltage Adjustment (VOLT) or 60 Hz).
The screwdriver adjustable potentiometer adjusts
the generator output voltage. Adjustment clockwise • Set the voltage to the preferred setting at rated
increases the generator voltage. Hz. Adjust engine speed to the new roll-off point.
Turn the potentiometer counterclockwise until the
Remove the jumper wire across terminals 6 and 7 voltage starts to drop off. Then adjust the potenti-
when installing the remote voltage adjust rheostat, ometer clockwise until the voltage returns to rated
and install a 2000 ohm 1/2 watt rheostat. This gives voltage. Re-adjust engine speed to rated speed.
±10% voltage adjustment from the nominal. (For a

3
FREQUENCY COMPENSATION (See Figure 3) 3. OPERATION PROCEDURE
1. The frequency compensation characteristic of
Figure 1 used to improve system load pickup 3.1 Static AVR bench test
performance by restraining voltage recovery Complete before starting test.
until frequency has also started to recover.
1. Connect the AVR as shown in Figure 5
2. The regulator is shipped from the factory set at Operational Test Diagram. Do not apply power.
a 45 Hz “corner frequency” for 50 Hz systems. Ensure that the light bulbs are rated for 120
For 60 Hz systems, a 55 Hz corner frequency is volts and less than 100 watts.
achieved by removing the “50-50” external link.
2. Adjust the voltage potentiometer / external
voltage adjustment rheostat (if used) fully
counterclockwise.

3. Connect 240 VAC, 60 Hz power to the control-


ler. The light bulbs should flash momentarily.

4. Slow adjust the AVR voltage potentiometer


clockwise.

RESULT :

1. Before minimum luminance is reached, the light


bulbs should attain maximum luminance to
signify the regulation point.
Figure 3 - Frequency Compensation Curves
2. At the regulation point, a small change in the
voltage adjustment potentiometer or rheostat
2.6 120 / 240 VAC Input Power Selection position should turn the light bulbs on or off.
Switch DIP select ON for 120VAC and OFF for 240
VAC according to the generator system voltage.

Figure 4 - Sensing & Power Input Voltage Selection

2.7 Stability Selection


When excitation under voltage, it can result in insuf-
ficient adjustment range for stability adjustment and
when excitation over voltage, the response from the
AVR becomes sluggish. The AVR is equipped with
2 bridging wires J1 and J2 to help improve this
problem. See Figure 2.

• If the unloaded excitation voltage is less than 7


VDC, please cut open the J2 red bridging wires.

• If the unloaded excitation voltage is greater than


25 VDC, please cut open the J1 white bridging
wires.

4
3.2 Preliminary Setup 2. Check the stability of the governor system.

• Confirm the regulator matches the requirements • Check regulation under normal operating condi-
of the generator. tions. If the regulation is poor:
• Ensure all connection and leads from voltage 1. Ensure the prime mover is operating at rated
regulator to generator are correctly connected. speed.
• Ensure all jumpers and DIP SW are correctly 2. Verify that the voltmeter is connected to the
installed and positioned. same lead as the Regulator sensing.
• Ensure terminal 6 & 7 is bridged if external voltage 3. Use an average-sensing voltmeter (not an RMS
adjustment rheostat is not in use. sensing voltmeter).
• Set VOLT voltage control potentiometer fully • If under frequency adjustment is required.
counter-clockwise and the external voltage Slowly reduce the generator frequency until the
adjustment rheostat (if used) to the center generator output voltage begins to drop:
position.
1. Rotate the under frequency potentiometer fully
• Set STAB stability control potentiometer fully counterclockwise.
clockwise (Maximum stability level with sluggish
2. Reduce the generator frequency from nominal
response).
(either 50Hz or 60Hz) to the desired corner
• If adjustment of the under frequency control frequency.
potentiometer is required, start with the
3. Slowly adjust the under frequency control clock-
potentiometer adjusted fully counterclockwise,
wise until the generator output voltage just
then, slowly adjust the potentiometer clockwise
starts to decrease.
to set.
CAUTION
3.3 System Start-Up
All voltage readings are to be taken with an
average-reading voltmeter. Meggers and high-
NOTE : All AC voltage readings are to be taken with
potential test equipment are not be used.
an “average” reading voltmeter.
Use of such equipment could damage the
semiconductors inside the voltage regulator.
• Start prime-mover and bring up to rated speed.
• If generator voltage does not build up, per-
form field flashing. Please reference from 4. Field 4. FIELD FLASHING
Flashing. When regulator is operated with the generator for
the first time, the polarity of residual magnetism may
• Slowly adjust the regulator voltage control poten-
be reversed or too small to achieve the necessary
tiometer (or remote voltage adjust rheostat) until
build-up voltage for the regulator. If reversing the
the generator voltage reaches the nominal level. If
field connections does not induce build-up, and the
the voltage does not build up to the rated level:
residual voltage is less than the specified value of 5
1. Check the generator output for excessive load VAC, shut down the Prime-mover and proceed with
or possible short circuit. the following steps :
2. Residual voltage under 5 volts. Perform field A. With the Prime-mover at rest and the
flashing. regulator’s field output wires disconnected,
• Apply and remove the generator load to verify sta- apply a DC source ( Not grounded ) of not more
bility If the generator responds too slowly or hunts than 6~12 VDC with Positive to F+ and Negative
(oscillates): to F-, in series with a current-limiting resistor of
3~5 ohms 20 watt. (The set battery is a suitable
1. Check the generator output for excessive load source.)
or a short circuit. Adjust the Regulator stability
control with no load applied. B. Allow approximately 3 seconds before removing
the DC source.

5
3. With the regulator disconnected (wires 3 and
4), start the prime mover and measure the
“residual” voltage available at the auxiliary This Automatic Voltage Regulator is not
winding. If this voltage is greater than 5 VAC, equipped with loss-Sensing Protection
reconnect regulator and restart prime mover. function / Over Excitation Protection. An
If less than 5 VAC is measured, repeat field additional Over-Voltage Protection device
flashing procedure. for load may be required to avoid possible
damage to the equipment or severe personal
4. If repeating step A. and B. does not result injury or death.
in generator voltage build-up, and residual
is greater than 5 VAC, replace with a new
regulator.

Figure 5 - Operational Test Diagram Figure 6 - 1Ø 110 / 220VAC Diagram

Figure 7 - 3Ø 220VAC Diagram Figure 8 - 3Ø 380VAC Diagram

6
7
100 E. Randolph Street (54401) A Regal Brand
PO Box 8003
Wausau, WI 54402-8003 U.S.A.
PH: 715-675-3359
FAX: 715-675-8026

www.marathonelectric.com

©2013 Regal-Beloit Corporation MANUAL GPN051 7344J/250/06-13/BH/FS Printed in the U.S.A.

S-ar putea să vă placă și