FAULT LEVEL CALCULATION-MV SYSTEM

GRID - INTERCONNECTION POINT


System kV 110 BASE MVA: 1000
Fault kA 33.01 PUR PUX
Fault MVA 6,289 PUZUTILITY= (kVABASE)/SC kVAUTILITY 0.000000 0.1590061
PUZ = √(R2+X2) = 0.159006 ------[1]
kVATRANS= 158
kVPRI= 110 PURTRANS= (%R)(kVABASE)/(100)(kVATRANS) 0.0569620 -
kVSEC.= 33 PUXTRANS= (%X)(kVABASE)/(100)(kVATRANS) 1.0744405
%Z= 17.00 PUZ = √(R2+X2) = 1.075949 ------[2]
%R= 0.90 PUZTOTAL (1+2) = 1.234956
%X= 16.98
IFL(TRANS.)= 2.764 Fault MVA=Base MVA/PU Impedance 809.75 MVA
POWER TRANSFORMER ISC(Sym RMS)= kVABASE/(1.732xkVSEC.x PUZTOTAL) 14.167 kA

MV CABLE 3-CORE
630 PURCABLE= (ROHM)(kVABASE)/(1000)(kV2) 0.0002603 -
Length in meters = 50 PUXCABLE= (XOHM)(kVABASE)/(1000)(kV2) - 0.0004339
No.of Runs= 1 PUZ = √(R2+X2) = 0.0005060 ------[6]
ROHM = 0.003150 PUZTOTAL (1+2+3+4+5+6) = 1.2355
XOHM = 0.005250
Fault MVA=Base MVA/PU Impedance 809.41 MVA
INV TRAFO - INV, STATION ISC(Sym RMS)= kVABASE/(1.732xkVPRI.x PUZTOTAL) 14.161 kA
Actual S/C in kA = S/C from Grid + S/C from PV
Actual S/C in kA = 16.926 ( We have consdiered 20kA RMU)

460269166.xls 14
FAULT LEVEL CALCULATION-MV SYSTEM

GRID - INTERCONNECTION POINT


System kV 110 BASE MVA: 1000
Fault kA 12.78 PUR PUX
Fault MVA 2,435 PUZUTILITY= (kVABASE)/SC kVAUTILITY 0.000000 0.4107037
PUZ = √(R2+X2) = 0.410704 ------[1]
kVATRANS= 160
kVPRI= 110 PURTRANS= (%R)(kVABASE)/(100)(kVATRANS) 0.0562500 -
kVSEC.= 33 PUXTRANS= (%X)(kVABASE)/(100)(kVATRANS) 0.9358110
%Z= 15.00 PUZ = √(R2+X2) = 0.937500 ------[2]
%R= 0.90 PUZTOTAL (1+2) = 1.348204
%X= 14.97
IFL(TRANS.)= 2.799 Fault MVA=Base MVA/PU Impedance 741.73 MVA
POWER TRANSFORMER ISC(Sym RMS)= kVABASE/(1.732xkVSEC.x PUZTOTAL) 12.977 kA

MV CABLE 3-CORE
630 PURCABLE= (ROHM)(kVABASE)/(1000)(kV2) 0.0002603 -
Length in meters = 50 PUXCABLE= (XOHM)(kVABASE)/(1000)(kV2) - 0.0004339
No.of Runs= 1 PUZ = √(R2+X2) = 0.0005060 ------[6]
ROHM = 0.003150 PUZTOTAL (1+2+3+4+5+6) = 1.3487
XOHM = 0.005250
Fault MVA=Base MVA/PU Impedance 741.45 MVA
INV TRAFO - INV, STATION ISC(Sym RMS)= kVABASE/(1.732xkVPRI.x PUZTOTAL) 12.972 kA
Actual S/C in kA = S/C from Grid + S/C from PV
Actual S/C in kA = 15.772 ( We have consdiered 20kA RMU)

460269166.xls 24
FAULT LEVEL CALCULATION-MV SYSTEM

GRID - INTERCONNECTION POINT


System kV 110 BASE MVA: 1000
Fault kA 17.07 PUR PUX
Fault MVA 3,252 PUZUTILITY= (kVABASE)/SC kVAUTILITY 0.000000 0.3074864
PUZ = √(R2+X2) = 0.307486 ------[1]
kVATRANS= 160
kVPRI= 110 PURTRANS= (%R)(kVABASE)/(100)(kVATRANS) 0.0562500 -
kVSEC.= 33 PUXTRANS= (%X)(kVABASE)/(100)(kVATRANS) 0.9358110
%Z= 15.00 PUZ = √(R2+X2) = 0.937500 ------[2]
%R= 0.90 PUZTOTAL (1+2) = 1.244986
%X= 14.97
IFL(TRANS.)= 2.799 Fault MVA=Base MVA/PU Impedance 803.22 MVA
POWER TRANSFORMER ISC(Sym RMS)= kVABASE/(1.732xkVSEC.x PUZTOTAL) 14.053 kA

MV CABLE 3-CORE
630 PURCABLE= (ROHM)(kVABASE)/(1000)(kV2) 0.0002603 -
Length in meters = 50 PUXCABLE= (XOHM)(kVABASE)/(1000)(kV2) - 0.0004339
No.of Runs= 1 PUZ = √(R2+X2) = 0.0005060 ------[6]
ROHM = 0.003150 PUZTOTAL (1+2+3+4+5+6) = 1.2455
XOHM = 0.005250
Fault MVA=Base MVA/PU Impedance 802.90 MVA
INV TRAFO - INV, STATION ISC(Sym RMS)= kVABASE/(1.732xkVPRI.x PUZTOTAL) 14.047 kA
Actual S/C in kA = S/C from Grid + S/C from PV
Actual S/C in kA = 16.847 ( We have consdiered 20kA RMU)

460269166.xls 34
FAULT LEVEL CALCULATION-MV SYSTEM

GRID - INTERCONNECTION POINT


System kV 132 BASE MVA: 1000
Fault kA 18.00 PUR PUX
Fault MVA 4,115 PUZUTILITY= (kVABASE)/SC kVAUTILITY 0.000000 0.2429997
PUZ = √(R2+X2) = 0.243000 ------[1]
kVATRANS= 105
kVPRI= 132 PURTRANS= (%R)(kVABASE)/(100)(kVATRANS) 0.0857143 -
kVSEC.= 33 PUXTRANS= (%X)(kVABASE)/(100)(kVATRANS) 1.1396383
%Z= 12.00 PUZ = √(R2+X2) = 1.142857 ------[2]
%R= 0.90 PUZTOTAL (1+2) = 1.385857
%X= 11.97
IFL(TRANS.)= 1.837 Fault MVA=Base MVA/PU Impedance 721.58 MVA
POWER TRANSFORMER ISC(Sym RMS)= kVABASE/(1.732xkVSEC.x PUZTOTAL) 12.625 kA

MV CABLE 3-CORE
630 PURCABLE= (ROHM)(kVABASE)/(1000)(kV2) 0.0001808 -
Length in meters = 50 PUXCABLE= (XOHM)(kVABASE)/(1000)(kV2) - 0.0003013
No.of Runs= 1 PUZ = √(R2+X2) = 0.0003514 ------[6]
ROHM = 0.003150 PUZTOTAL (1+2+3+4+5+6) = 1.3862
XOHM = 0.005250
Fault MVA=Base MVA/PU Impedance 721.39 MVA
INV TRAFO - INV, STATION ISC(Sym RMS)= kVABASE/(1.732xkVPRI.x PUZTOTAL) 12.621 kA
Actual S/C in kA = S/C from Grid + S/C from PV
Actual S/C in kA = 14.459 ( We have consdiered 20kA RMU)