Sunteți pe pagina 1din 11

Control Valve Handbook | Chapter 4: Control Valve Accessories

Today, modern control systems use vibration may require sturdy instrument
electronic signaling to command the mounting, rugged internal mechanisms,
control valve to open, close, or throttle. or remote mounting capability.
Additionally, these systems use position High levels of humidity can lead to
feedback signals and diagnostic corrosion, so protection of electronic
information to validate the operation components may be necessary.
of the control valve. Furthermore, the Hazardous locations containing gaseous
performance expectations of control or dusty atmospheres may require
valves in terms of speed of response, instrumentation that is designed using
accuracy, stability, reliability, and safety protection concepts, such as flameproof,
vary based on the process control needs. explosion proof, intrinsic safety, or
Because control valves are installed in non-incendive. These environmental
many different and unique applications, and application conditions should be
control valve accessories are necessary. considered when selecting the proper
Accessories are the broad category of control valve accessories. 
instruments that are directly connected
to a control valve assembly.
There are five basic reasons that 4.2 Positioners
instrumentation and accessories are A common control valve accessory is
added to a control valve: the valve position controller, also called
 Improve process control a positioner. The fundamental function
of a positioner is to deliver pressurized
 Improve safety for the process or
air to the valve actuator, such that
personnel
the position of the valve stem or shaft
 Improve valve performance or speed corresponds to the set point from the
of response control system. Positioners are typically
 Monitor or verify the valve used when a valve requires throttling
responsiveness action. A positioner requires position
 Diagnose potential valve issues feedback from the valve stem or shaft
and delivers pneumatic pressure to the
actuator to open and close the valve.
4.1 Environmental & The positioner must be mounted on or
near the control valve assembly. There
Application Considerations are three main categories of positioners,
Industrial plants, factories, mines, and depending on the type of control signal,
mills experience tough environmental the diagnostic capability, and the
conditions due to their geographical communication protocol.
location and the processes involved
in manufacturing their products. As a 4.2.1 Pneumatic Positioners
result, valves and instruments in these The first category of positioners
facilities must be rugged and reliable. are pneumatic positioners. Legacy
Ambient temperatures for processing units may use pneumatic
instrumentation can range from -60 pressure signaling as the control set
to 125°C (-76 to 257°F). Corrosive point to the control valves. Pressure is
atmospheres, such as salt water and typically modulated between 20.7 to
chemical exposure, may require 103 kPa (3 to 15 psig) to move the valve
stainless steel or engineered resin from 0 to 100% position.
materials of construction. Intense In a common pneumatic positioner

See Additional Resources » 75


Control Valve Handbook | Chapter 4: Control Valve Accessories

Output to
Diaphragm

Relay

Instrument

Bellows

Supply Feedback Axis

Pivot
Nozzle

Flapper Assembly

Direct Action
Quadrant
Input Axis
Cam

Reverse Action
Beam Quadrant

Figure 4.1 Typical Pneumatic, Single-Acting Positioner Design

design (Figure 4.1), the position of the about the input axis to move the flapper
valve stem or shaft is compared with the away from the nozzle. Nozzle pressure
position of a bellows that receives the decreases and the relay permits the
pneumatic control signal. When the release of diaphragm casing pressure
input signal increases, the bellows to the atmosphere, which allows the
expands and moves a beam. The beam actuator stem to move upward. Through
pivots about an input axis, which moves the cam, stem movement is fed back
a flapper closer to the nozzle. The nozzle to the beam to reposition the flapper
pressure increases, which increases the closer to the nozzle. When equilibrium
output pressure to the actuator through conditions are obtained, stem movement
a pneumatic amplifier relay. The stops and the flapper is positioned to
increased output pressure to the prevent any further decrease in actuator
actuator causes the valve stem to move. pressure. See Figure 4.1.
Stem movement is fed back to the beam
4.2.2 Analog I/P Positioners
by means of a cam. As the cam rotates,
the beam pivots about the feedback axis The second type of positioner is an
to move the flapper slightly away from analog I/P positioner. Most modern
the nozzle. The nozzle pressure processing units use a 4 to 20 mA DC
decreases and reduces the output signal to modulate the control valves.
pressure to the actuator. Stem This introduces electronics into the
movement continues, backing the positioner design and requires that the
flapper away from the nozzle until positioner convert the electronic current
equilibrium is reached. signal into a pneumatic pressure signal
(current-to-pneumatic or I/P).
When the input signal decreases, the
bellows contracts (aided by an internal In a typical analog I/P positioner (see
range spring) and the beam pivots Figure 4.2), the converter receives a DC

76
Control Valve Handbook | Chapter 4: Control Valve Accessories

input signal and provides a proportional increasing control signal, one output
pneumatic output signal through pressure always increases and the other
a nozzle/flapper arrangement. The output pressure decreases.
pneumatic output signal provides the
input signal to the pneumatic positioner.
Otherwise, the design is the same as the
pneumatic positioner.

-
4-20 mA +
Input Signal

Pneumatic Signal
from Converter
Bellows
Converter

Feedback Axis
Supply
Output to Nozzle
Actuator
Beam
Relay
Direct-Acting
Quadrant
Rotary
Shaft Arm
Input Axis

Cam
Pivot
Reverse-Acting
Flapper Assembly Quadrant

Figure 4.2 Typical Single-Acting Analog I/P


Positioner Design
Figure 4.3 Digital Valve Controller Mounted on a
Control Valve
4.2.3 Digital Valve Controllers
Double-acting actuators use both
While pneumatic positioners and analog
outputs, whereas single-acting actuators
I/P positioners provide basic valve
use only one output. The changing
position control, digital valve controllers
output pressure causes the actuator
add another dimension to positioner
stem or shaft to move. Valve position
capabilities. This type of positioner is a
is fed back to the microprocessor.
microprocessor-based instrument. The
The stem continues to move until the
microprocessor enables diagnostics and
correct position is attained. At this
two-way communication to simplify
point, the microprocessor stabilizes the
setup and troubleshooting.
drive signal to the I/P converter until
In a typical digital valve controller, equilibrium is obtained.
the control signal is read by the
In addition to the function of controlling
microprocessor, processed by a digital
the position of the valve, a digital
algorithm, and converted into a drive
valve controller has two additional
current signal to the I/P converter.
capabilities: diagnostics and two-way
The microprocessor performs the
digital communication.
position control algorithm rather
than a mechanical beam, cam, and 4.2.3.1 Diagnostics
flapper assembly. As the control signal
increases, the drive signal to the I/P The microprocessor inside the digital
converter increases, increasing the valve controller allows the positioner to
output pressure from the I/P converter. run, analyze, and store diagnostic tests.
This pressure is routed to a pneumatic Diagnostic information is useful in
amplifier relay and provides two determining the health of the entire
output pressures to the actuator. With control valve assembly. Through the

See Additional Resources » 77


Control Valve Handbook | Chapter 4: Control Valve Accessories

use of pressure sensors, temperature information between the control


sensors, travel sensors, and internal system and the digital valve controller.
readings, graphical representations of For positioners outfitted with wireless
control valve performance and health are capability, digital information can be
created and recommended actions are transmitted independent of the control
presented. This information is then used system wiring. 
to identify elements of the control valve
assembly that may require maintenance.
4.3 I/P Transducers
4.2.3.2 Two-Way Digital
Communication In some applications, the high level of
postioning accuracy that a positioner
The microprocessor inside the digital provides is not required. In these
valve controller also allows the applications, an electro-pneumatic (I/P)
positioner to communicate with the transducer can be used. An I/P transducer
control system via a digital signal. This (Figure 4.4) uses a converter module that
enables the digital valve controller to converts a 4 to 20 mA current input to a
provide additional feedback, such as proportional pressure output. An internal
actual valve travel and diagnostic alerts pneumatic amplifier relay provides the
back to the control system. capacity necessary to deliver output
One widely used protocol is HART® pressure to the control valve actuator.
communication. HART communication There is no valve position feedback and
uses a digital signal superimposed over responsiveness is very quick. 
the traditional 4 to 20 mA DC control
signal. This communication protocol
allows the host system to be used
to configure, calibrate, and monitor
the health of the positioner. HART
communication offers the benefits
of digital communication with the
familiarity of a 4 to 20 mA control system.
FOUNDATION™ fieldbus is another
industry standard protocol. This protocol
is all digital, which means that the
control signal (set point) is digital, rather
than a 4 to 20 mA DC current. Similar to
HART communication, the host system
can also be used to configure, calibrate,
and monitor the positioner.
PROFIBUS is also a common industry
protocol that provides all digital Figure 4.4 Transducer Mounted on a Control Valve
communication. The physical layer
for PROFIBUS and FOUNDATION
fieldbus is the same; however, the 4.4 Volume Boosters
communication protocols differ and Positioners and I/P transducers are
offer their own advantages. designed to provide enough pneumatic
Wireless technology offers an output capacity to drive a typical
additional method to communicate throttling control valve. However, some

78
Control Valve Handbook | Chapter 4: Control Valve Accessories

applications require faster stroking between the input signal and the
speeds. When the actuator volume is output of the booster. When this
large, the positioning speed of response occurs, the diaphragms move to open
can become more of a concern. the supply port or the exhaust port,
whichever action is required to reduce
Volume boosters are used to provide
the differential. The port remains open
additional pneumatic output capacity
until the difference between the booster
to a valve assembly (Figure 4.5). A
input and output pressure is within the
large, sudden change in input signal
deadband limit of the booster.
(output pressure from the positioner)
causes a pressure differential to exist With the bypass restriction adjusted

Signal Input
Diaphragms Bypass Restriction
Adjusting Screw

Bypass Restriction

Exhaust

Exhaust Port

Supply Supply Port

Output to Actuator

Figure 4.5 Volume Booster Sectional View

Volume
Booster
Pipe Tee
Pipe Bushing
Body
Body Pipe Nipple
Protector

Positioner
Optional Output
Diagnostic
Connection

Signal

Positioner Supply
Actuator Pressure
Regulator

Figure 4.6 Typical Booster Installation with a Single-Acting Actuator

See Additional Resources » 79


Control Valve Handbook | Chapter 4: Control Valve Accessories

for stable operation, signals having typically on/off valves that are used
small magnitude and rate changes to take the process loop to a safe
pass through the bypass restriction state in the event of a process control
and into the actuator without initiating emergency (Figure 4.7). A separate
booster operation. Both the supply and safety system, often controlled by a
exhaust ports remain closed, preventing logic solver, controls these valves.
unnecessary air consumption and
possible saturation of positioner relays. 4.5.1 Partial Stroke Testing
Single-acting actuators typically use Because safety valves are static and do
one volume booster (Figure 4.6). not modulate under normal conditions,
Double-acting actuators require at they are prone to sticking. When an
least two volume boosters, one to feed emergency demand occurs, there is a
each side of the actuator piston. Some risk that the valves will not move when
applications, such as compressor anti- commanded. To mitigate this risk, the
surge or turbine bypass, may require digital valve controller can be used as a
additional volume boosters to provide partial stroke testing device.
the needed pneumatic volume for fast An important function of the instrument
valve response.  is periodically exercising the valve. This is
performed with a valve partial stroke test
(PST). The PST slowly moves the valve
4.5 Safety Instrumented a portion of the total valve travel and
Systems (SIS) then returns to the normal state. This
exercises the mechanical components of
The primary purpose of a control valve
the safety valve with minimal disruption
is to modulate the flow of liquid or
to the process loop. Furthermore,
gas in a pipe within a process control
the digital valve controller has the
loop. Within these same process loops,
ability to diagnose potential issues and
there are also emergency vent, block,
communicate any alerts if the test fails.
or isolation valves. These valves are

Figure 4.7 SIS Digital Valve Controller on a Safety Valve

80
Control Valve Handbook | Chapter 4: Control Valve Accessories

4.5.2 Safety Function and liquid displacement lever assembly, or


Product Certification temperature bulb.

A spring-return, single-acting actuator


provides an inherent fail mode for the
valve assembly. During an emergency
demand, the typical method to move the
valve to the safe state is to remove the
air pressure to the actuator and allow the
spring to position the valve. A solenoid
valve and/or digital valve controller can
be used to perform this function. There
may be additional instrumentation
on the safety valve, such as boosters,
position transmitters, and trip systems.
All of these elements must be evaluated
for their effect on the safety system.
These elements can fail by causing
an unplanned trip or by not getting
the safety valve to the safe state. The
Failure Modes, Effects, and Diagnostics
Analysis (FMEDA) provides metrics
for each component. This allows a
safety engineer to design the safety
Figure 4.8 Pneumatic Controller on a Control Valve
instrumented system to the desired
level of risk reduction. See Chapter The input element is connected to the
12 for more information about safety process pointer (set point adjustment)
instrumented systems.  and to the flapper by connecting links.
As the process input increases (in a
direct-acting controller), the flapper
4.6 Controllers moves toward the nozzle, which restricts
In some applications, control of the flow through the nozzle and increases
process is performed locally without nozzle pressure. When this occurs, relay
the need for a large scale distributed action increases the output pressure to
control system (DCS) or programmable the actuator, which modulates the
logic controller (PLC). Local controllers control valve. Output pressure is fed
are used to measure process conditions, back to the proportional bellows. The
such as pressure, temperature, or level action of the proportional bellows
and directly drive the pneumatic output counters the flapper movement that
pressure to a control valve (Figure 4.8). resulted from the process input change.
It then moves the flapper away from the
The input to the local controller is nozzle until the controller reaches a
typically pressure, differential pressure, point of equilibrium. The set point
temperature, or level displacement. adjustment changes the proximity of the
The process measurement is translated nozzle and flapper, as does a change in
into a beam-flapper assembly process input. However, when the set
movement, which is connected to an point is changed, the nozzle moves with
input element. The input element can respect to the flapper.
be a Bourdon tube, bellows assembly,

See Additional Resources » 81


Control Valve Handbook | Chapter 4: Control Valve Accessories

The proportional band adjustment and proportional bellows. In operation,


knob positions the nozzle on the flapper. proportional-plus-reset controllers
Increasing or widening the proportional minimize the offset between the process
band moves the nozzle to a position on variable and the set point.
the flapper where less flapper motion Controllers with proportional-plus-reset-
occurs, decreasing the gain of the plus-rate have a rate valve, an adjustable
controller. Decreasing or narrowing the restriction that briefly maintains
proportional band moves the nozzle the controller gain to accelerate the
toward a position where more flapper corrective action for slow systems
motion occurs, increasing the gain. (Figure 4.10). The rate action delays the
Controller action is changed from direct gain reduction just long enough to allow
to reverse by turning the proportional the system to respond to the change,
band adjustment knob to position the but not long enough for the system to
nozzle to a point on the flapper where become unstable. Then, the low gain
the direction of the flapper motion provided by the proportional action
versus the input motion is reversed. keeps the system stable. Finally, the reset
With the controller in the reverse-acting action slowly increases the gain and
mode, an increase in process input returns the process toward the set point.
causes a decrease in output pressure
to the actuator. Supply pressure bleeds Anti-reset windup reduces overshoot
through a fixed orifice in the relay and of the process input that can result
exits through the nozzle. The nozzle from large or prolonged deviation
pressure registers on the large relay from the set point. This option can be
diaphragm and modulates loading adjusted to operate on either increasing
pressure on the small relay diaphragm. or decreasing output pressure. The
This also modulates the controller output differential relief valve operates when the
pressure to the actuator (Figure 4.9). difference between proportional bellows
pressure and reset bellows pressure
Controllers with proportional-plus- reaches a predetermined value. 
reset operation are similar to that of
proportional-only controllers, except that
output pressure is fed back to the reset

Manual Set Point Reset Bellows (Vented) Reverse-Action Quadrant


Adjustment Proportional
Bellows Proportional
Process Pointer
Band Adjustment Feedback
Remote Set Point Link
Connected Here
Feedback
Motion Flapper
Input Element Pivot
Connected Here Input
Direct-Action
Quadrant Motion
Connecting
Link
Beam Output Pressure
to Final Control Element
Flapper
Supply Pressure
Nozzle
Output Pressure Relay
Nozzle Pressure Supply Pressure
Reset Pressure
Proportional Pressure Proportional-Only Control

Figure 4.9 Pneumatic Controller Schematic

82
Control Valve Handbook | Chapter 4: Control Valve Accessories

To Reset
Bellows To Nozzle
To Proporitional
Bellows
Output

Relay

Supply Pressure Differential Supply Pressure

Output Pressure Relief Valve Reset Valve

Nozzle Pressure Rate Valve

Reset Pressure
Proportional + Reset + Rate Control
Proportional Pressure
With Anti-Reset Windup

Figure 4.10 Pneumatic Controller Schematic

4.7 Position Transmitters 4.8 Limit Switches


The purpose of a position transmitter is The purpose of a limit switch is to
to provide independent valve position provide a discrete open or close signal
feedback to the control system. to the control system when the valve
Position feedback is often used for reaches a specific position within its
process monitoring, troubleshooting, range of travel. Limit switches are
or startup/shutdown verification. also used for process monitoring,
The position transmitter is mounted troubleshooting, or startup/shutdown
directly to the valve and measures the verification. The limit switch receives
position of the valve stem or shaft. position feedback from the valve stem
In a wired installation, the position or shaft and will send either a wired
transmitter provides a 4 to 20 mA signal or a wireless signal to the control
that corresponds with the throttling system. There are many different
range of the control valve. In a wireless switch technologies available, such as
installation, the position transmitter proximity, solid state, magnetic, and
provides a 0 to 100% digital signal contact closure. 
(Figure 4.11). 

4.9 Solenoid Valves


A solenoid valve is installed in the
pneumatic tubing path to the actuator.
In some applications, the solenoid valve
will vent the air from the actuator to
allow the valve to move to its no air, fail
state. In other applications, the solenoid
valve will trap air in the actuator to
lock the valve in its current position.
Three-way solenoids are generally used
to operate spring-return actuators and
four-way solenoids are generally used for
Figure 4.11 Wireless Position Monitor Mounted on
double-acting actuators. The solenoid
an Actuator valve is activated by making or breaking

See Additional Resources » 83


Control Valve Handbook | Chapter 4: Control Valve Accessories

a discrete electrical signal from the system to return to normal operation. 


control system. See Chapter 11 for more
information about solenoid valves. 
4.11 Handwheels
Handwheels for diaphragm actuators
4.10 Trip Systems are often used as adjustable travel
Trip systems are used in control stops. They also provide a ready means
applications where a specific actuator of positioning the control valve in an
action is required in the event that supply emergency.
pressure is lost (Figure 4.12). These Side-mounted handwheels can be used
are used with double-acting actuators to stroke the valve in either direction
that do not have an inherent no air, fail at any point in the actuator stem
state or with single- or double-acting travel (Figure 4.13). The side-mounted
actuators to provide pneumatic lock-up. handwheel can be positioned to limit
When supply pressure falls below the trip travel in either direction, but not both
point, the trip valve causes the actuator at the same time. With the handwheel
to fail up, lock in the last position, or fail in the neutral position, automatic
down. For double-acting applications, operation is possible throughout full
a volume tank provides the reserve valve travel. In any other position, valve
pneumatic air capacity to operate travel will be restricted.
the valve until the supply pressure is Top-mounted handwheels are used for
restored. When the supply pressure infrequent service to manually stroke
rises above the trip point, the trip valve the valve (Figure 4.14). 
automatically resets, allowing the

Spring
Main
Valve Plug Spring Actuator

Upper Diaphragm
Vent

Exhaust Port

Supply Pressure Control


Device

Lower Diaphragm
Port D
Port A
Port E
Port B

Upper Ports
Lower Plug
Ports Port C Assemblies
Port F Volume
Tank

Pressure to Top of Cylinder


Supply Pressure (from Volume Tank)
Control Pressure to Top of Pressure from Bottom of Cylinder
Cylinder (Blocked) (Venting)
Control Pressure to Bottom Lower Diaphragm Loading Pressure
of Cylinder (Blocked) (Being Vented)

Figure 4.12 Trip Valve Shown in Tripped Condition

84
Control Valve Handbook | Chapter 4: Control Valve Accessories

Figure 4.13 Actuator with Side-Mounted Handwheel Figure 4.14 Actuator with Top-Mounted Handwheel

See Additional Resources » 85

S-ar putea să vă placă și