DEFAULT
Software Version V4.2013
Enter Code 0002
Direct Parameterisation NO
Generator Number 1-8
Service Display Yes/No YES
Check Event List Yes/No NO
Configure Measuring Yes/No YES
Generator Freq. Fset 50Hz
Rated System frequency 50Hz
Gen. Volt Transformer Secondary 400V
Gen Volt Transformer Primary 0.40kV
Bus Volt Transformer Secondary 400V
Bus Volt Transformer Primary 0.40kV
Mains Volt Transformer Secondary 400V
Mains Volt Transformer Primary 0.40kV
Gen Volt Uset 400V
Voltage Systems Phase Neutral
Current Transformer Gen 2000/5
Power Measuring Gen Phase/Phase
Rated power Gen 1000kW
Rated Current Gen 1804A
Analog in Pmains T1-T8 T1
Analog in Pmains 0-20/4-20mA 4-20mA
Analog in Pmains 0% 0kW
Analog in Pmains 100% -6000kW
Current Transformer Mains 400/5
CONTROLLER CONFIGURATION
Configure Controller Yes
Power Controller Pset1 I100kW
Power Controller Pset2 I100kW
Initial State Freq 50Hz
Freq Controller ON
F-contr active at 30Hz
delay time for f-contr 5s
Freq Controller Ramp Hz/s
Freq Controller gain Kpr 5
Freq Controller reset Tn 1s
Freq Controller derivat. Tv 0s
Starting point voltage 50V
Volt Controller ON
Start Voltage U control 300V
delay time for U-contr 3s
Volt Controller gain Kpr 5
Volt Controller reset Tn 1s
Volt Controller derivat. Tv 0s
Power Factor Controller ON
Power Factor Controller setpoint i0.8
Power Factor Controller gain Kpr 5
Power Factor Controller reset Tn 1s
Power Factor Controller deviation Tv 0s
Power Controller ON
Power Controller ramp 2%/s
Power Limit Pmax 100%
Power Limit Pmin 0%
Power Setpoint External OFF
Power Controller gain Kpr 20
Power Controller reset Tn 1s
Power Controller deviation Tv 0s
Warm up Load limit value 20%
Warm up Load time 20s
Active Power load-share ON
Act. Load Share factor 50%
ReActive Power load-share ON
ReAct. Load Share factor 50%
LOAD MANAGEMENT CONFIGURATION
Configure Automatic ON
Load start/stop at term 3 OFF
Load start/stop at term 5 ON
Minimum Load gen 350kW
Add on delay mains op. 10s
Shed off delay mains op. 30s
Hysteresis add on/off op. 50kW
Reserve power mains op. 200kW
Priority of generators 1
Reserve power isol op. 500kW
Add on delay isol op. 1s
Shed off delay isol op. 4s
Control via COM X1-X5 OFF
ENGINE CONFIGURATION
Configure engine YES
Aux services pre-run 0s
Aux services post-run 0s
Start-Stop logic Diesel Diesel
preglow time 0s
Max attempts to start 3
Max number of unintended stops 0
Starter time 70s
Start pause time 10s
Fuel relay logic Open to stop Open to stop
Cooldown time 180s
Delayed engine monitoring 15s
Firing speed reached f>15Hz
Pick-up input ON
Gen rated speed 1500rpm
Number of pick-up teeth 156
Configure Eng Bus YES
CCM ECM+
Configure pointers yes
Service interval in 0300hr
Set oper. Hours counter 0000hr
Set Start Counter 00000
kWh counter set in kWH
kWh counter set 00000kWH
Time ??:??
Year/Month ??:??
Day/Weekday ??:??