Sunteți pe pagina 1din 18

© Siemens AG 2009

SIRIUS Monitoring and Controlling


Overview of safety relays

Safety Integrated
Answers for industry.
© Siemens AG 2009

Simpler, faster and more cost-effective to implement

a seamless safety chain


Today, one of the key success factors is for machines and plants to achieve the highest possible pro-

ductivity. Standardized automation is playing a decisive role in achieving this goal as a result of the

higher degree of flexibility and openness. Now if safety technology would follow this trend, your

automation processes would become even more efficient. Siemens can offer you the optimum solu-

tion with our extensive safety portfolio – Safety Integrated: This safety system can be seamlessly

integrated into standardized automation therefore creating the ability for machines and plants to

operate more cost-effectively. And it doesn’t matter if it’s a new design or a retrofit. SIRIUS ® safety

relays are an essential component in our seamless safety system portfolio. Practice-oriented and

user-friendly, they meet all specified safety technology requirements and offer numerous additional

advantages.

2
© Siemens AG 2009
SIRIUS safety relays

Standard devices ■ Electronic enable circuits


– 3TK2840-42 basic units
■ Relay enable circuits
– 3TK282. basic units
– 3TK2830 expansion devices
■ Contactor relay enable circuits
– 3TK2850-53 basic units
– 3TK2856/57 expansion devices
■ Multi-function
– 3TK2845
Special functions ■ Movement monitoring
– 3TK2810-0 standstill monitors
■ Press control
– 3TK2834 two-hand control device
– 3TK2835 overtravel distance tester
Accessories Cover cap
Fixing straps
Screwdrivers
Further information Simulations
Trailer
Insertion plate

The seamless safety portfolio: Experts for each and every case: High performance across the board
Safety Integrated SIRIUS safety relays
• Using well-proven relay technology with
More than 20 years of experience in safety SIRIUS safety relays are the essential ele- positively driven contacts up to Category 4
research and technology is reflected in ments of an integrated, seamless and according to EN 954-1.
our extensive Safety Integrated product cost-effective safety chain. Whether in-
• With redundant and diverse safety electronics
portfolio. Whether for production or proc- volving EMERGENCY STOP shutdown,
up to Category 4 according to EN 954-1 and
ess industries – our program includes all protective door monitoring or the opti-
SIL 3 (Safety Integrity Level) according to
elements essential for a seamless safety mum protection of presses or punches
IEC 61508
chain: From sensors through the evalua- – our extensive range extends from cost-
tion equipment and up to safe shutdown. effective standard devices up to innova- • With safety electronics and integrated
Today, this means that we are the only tive, multi-function devices, all with an contactor relays
supplier that offers total solutions in the extremely high degree of flexibility. This
• With expanded functionality
areas of detecting, evaluating and shut- is why we can really offer you a seamless
down. All Safety Integrated products and portfolio that can tackle almost any ap- • With special functions
systems are based on standard compo- plication.
nents, custom-tailored for the world of Our product set combines well-proven
Totally Integrated Automation®, and can technology with innovative components
be seamlessly integrated into your stand- and a high degree of functionality. The
ard automation environment. This means philosophy is clear: A maximum degree
that we can solve any safety application of safety with a maximum degree of cost-
– simple or complex – quickly and cost- effectiveness. For example: Integrated
effectively. diagnostics functionality and monitoring
Our SIRIUS Safety Integrated industrial systems allow faults to be quickly detect-
controls are the specialists when it comes ed, reduce undesirable downtimes and
to seamless, integrated safety tasks on ensure a higher degree of availability for
small or large scales. Whether for fail-safe your machines and plants. In summary:
detecting, commanding and signaling, Using SIRIUS safety relays not only reli-
monitoring and evaluating or starting and ably configures the complete safety chain
safe shutdown – our complete product but it does it quickly, simply and cost-eff-
range masters every challenge. This is ectively.
true for basic up to more complex tasks
that can be solved using standard filedbus
systems such as AS-Interface and PROFIBUS.

3
© Siemens AG 2009

The optimum solution for every task:

The range at a glance

Safety relays with basic functions


Safety relays with
electronic enable circuits

Fast, safe and wear-free switching Highlights:


Evaluation units with electronic components are ■ Permanent function monitoring
clearly establishing themselves in safety-related ■ No wear as they switch
applications. It’s natural – the advantages are electronically
quite clear: Due to permanent function moni- ■ High switching frequency
toring and wear-free operation, a significantly ■ Long electrical lifetime
higher switching frequency and longer electrical ■ Electronic sensors can be
lifetime are achieved. The compact and light de- evaluated
vices also permit a series circuit to be configured ■ Sensor cables up to max.
and even operational switching – e. g. using a 2000 m
PLC. The devices can be supplemented by the ■ Cascading possible
3TK2830 expansion units if several or electrically ■ Insensitive to vibration and dirt
isolated enable circuits are required in your ap- ■ Compact design, low weight
plication. ■ Certified for the global market

Safety relays with


relay enable circuits

Safety with electrically isolated contacts Highlights:


SIRIUS safety relays with relay enable circuits ■ Compact design
are not just space-saving due to their compact ■ Electrically isolated safety
design, but with pairs of positively driven NO outputs
contacts and feedback contacts offer a real plus ■ Also suitable for presses and
when it comes to safety. This is how it works: If punch controls
one of the contacts welds, then the other contact ■ Can be used up to an ambient
is used to shut down the circuit. A positively driv- temperature of max. 70 °C
en feedback signal contact (NC contact) detects
the fault of the defective NO contact. Expansion
units are available to increase the number of en-
able circuits. The 3TK2834 press control unit as
safety-relevant evaluation unit is used for 2-hand
operator consoles in press control systems.

4
© Siemens AG 2009

Safety relays with


contactor relay enable circuits

The complete 3-in-1 device Highlights:


We offer the perfect combination of electronic ■ Electrically isolated enable circuits
safety functionality and two redundant SIRIUS ■ AC-15/DC-13 switching capacity
contactor relays with contacts. Pre-mounted, ■ Safe separation
wired up, tested and certified as a unit. The only ■ High mechanical and electrical
thing that you have to do is snap the complete endurance
devices onto the mounting rail. Simple, safe and ■ Certified as complete unit
quick. ■ Faults are minimized and cost
reduced as they are pre-wired
in the factory
■ Low mounting and installation
costs
Safety relays with expanded functionality

3TK2845 multi-function device Highlights:


■ 2 sensor inputs (e.g. EMERGENCY
Several safety functions combined in just one STOP, protective door)
enclosure ■ Also suitable for protective door
Conventional safety applications – such as tumbler mechanisms (locks) and
EMERGENCY STOP and protective door monitor- agreement button
ing – could, up until now, only be implemented ■ 2 electronic and 2 relay enable
by using several individual safety relays. Our circuits
3TK2845 multi-function devices now combine
several functions in just one device. Two elec-
tronic and two relay enable circuits enable safe-
ty-relevant shutdown – with just few manual
operations, fast and favorably priced.

Safety relays with special functions

3TK2810-0 standstill monitor Highlights:


■ No additional sensors required
Increased safety in hazardous areas ■ Fault signaling via diagnostic
The standstill monitor detects motor standstills display
without the need for sensors via the residual ■ Settable standstill time
magnetization of the rotating motor. Once an ■ Suitable for application with
adjustable threshold value is fallen underrun, frequency converters
it enables access to the hazardous areas via its
outputs, e.g. by unlocking a protective door.

5
© Siemens AG 2009

Description of the

basic functions

Detecting (sensors) Evaluating (safety relay) Shutting down (actuators)

Device type
CAS/ FKel Actuator
Sensor OS (S) interface
interface (outputs,
(inputs) S1 FKel
(S) enable circuits)

Safety logic

Device parameter

SIRIUS safety relays and the Functionality at a glance


safety chain
Time is money. In order for you to quickly
A safety chain generally comprises understand the specific functionality of
detecting, evaluating and shutting down the individual device types, we have il-
functions. lustrated the safety-related functions in a
standard schematic layout. This is how it
Detecting = works: At a glance you can see the inputs
identifying a safety-relevant request, e.g. in the sensor interface, the outputs and
if an EMERGENCY STOP button is pressed enable circuits in the actuator interface
or a hazardous area, protected by sensors, and the special safety logic.
light grids or laser scanners, is entered.
Evaluating = In order to keep everything simple, the
identifying a safety-relevant request and schematics only show the inputs and
safely initiating the response, e.g. shut- outputs that are required to explain the
ting down the enable circuits. safety function. The power supply inputs
Shutting down = and the sensors as well as actuators that
shutting down the potential danger, e.g. can be connected to the interface have
a power supply using the downstream not be taken into account as they are not
contactor. relevant for explaining the function.

SIRIUS safety relays operate in the evalu-


ating and responding area within this
safety chain.

6
© Siemens AG 2009

Sensor interface
Sx Sensor input
CAS/OS Cascading input or operational switching
(operational switching: Connected, e.g. to a PLC output. This means
that the machine control can switch the enable circuits and therefore
the connected loads. The safety-related function is a higher-level function)

A1 Power supply input as sensor input or cascading input


(the cascading input: This is used to cascade/switch several safety
relays with one another)

Key-operated Bypasses the sensor connected to S2 (3TK2845)


switch (standard/service operation)

Safety logic
AS Automatic start: The device automatically starts after the enable conditions are fulfilled.
A manual start is also possible by incorporating a START button in the feedback circuit
(up to Category 3 according to EN 954-1)

MS Monitored start: The device only starts after the enable conditions have
been fulfilled and a start signal has been issued

AS/MS Automatic/monitored start – depending on what has been parameterized

td
Time delay

Parameters
AS/MS Automatic/monitored start
1/2 channel Single-/two-channel sensor connection
CC With/without cross-circuit fault monitoring

Actuator interface
ECXX XX = el: Enable circuit, electronic (not electrically isolated)
(Y) rel: Enable circuit, relay contact (electrically isolated)
cr: Enable circuit, contactor relay (electrically isolated)
L1/L2/L3: Main current paths
Y= NO: NO contact
NOtb: NO contact, delayed
SCXX XX = el: Signaling circuit, electronic (not electrically isolated)
(Y) rel: Signaling circuit, relay contact (electrically isolated)
cr: Signaling circuit, contactor relay (electrically isolated)
Y= NO: contact
NC: contact

7
© Siemens AG 2009

3TK2840-42 electronic enable circuits


3TK2840 bacic unit

S1 ECel
AS (NO)

ECel
(NO)

1/2 channel

3TK2841 bacic unit

CAS/ ECel
OS & AS/MS (NO)

S1 ECel 3TK2840
(NO)

CC AS/MS
Type Max. Max. Rated control Autostart/ Delay time Electronic
achievable achievable supply voltage monitored (s) sensors
Category SIL acc. to (V) start
3TK2842 bacic unit
acc. to IEC 61508
KAS/ ECel EN 954-1
BS & AS/MS (NO)

td
ECel 3TK2840- BB40 3 2 24 DC AS – Yes
S1 (NOtd)
3TK2841- BB40 4 3 24 DC AS/MS – Yes
CC AS/MS 3TK2842- BB41 4 3 24 DC AS/MS 0.05...3 Yes
3TK2842- BB42 4 3 24 DC AS/MS 0.5...30 Yes
3TK2842- BB44 4 3 24 DC AS/MS 5...300 Yes
1 Screw terminal
2 Spring terminal

8
© Siemens AG 2009

3TK282. relay enable circuits

3TK2821 basic unit


ECrel
S1 AS (NO)

ECrel
(NO)
ECrel
(NO)

SCrel
(NC)

3TK2822/24 basic unit

ECrel
S1 3TK2820 3TK2821 3TK2826 3TK2826 with opened front cover
AS (NO)

ECrel
(NO)
Type Max. Max. Rated control Autostart/ Delay Electronic
achievable achievable supply voltage monitored time (s) sensors
3TK2823 basic unit Category SIL acc. to (V) start
acc. to IEC 61508
ECrel
S1 (NO)
EN 954-1
MS
ECrel 3TK2821- CB30 3 2 24 AC/DC AS – –
(NO)
3TK2822- CB30 4 3 24 AC/DC AS – –
3TK2823- CB30 4 3 24 AC/DC MS – –
3TK2825 basic unit
3TK2824- CB30 3 2 24 AC/DC AS – –
ECrel
S1 AS/MS (NO) 3TK2824- BB40 3 2 24 DC AS – –
ECrel 3TK2824- AJ20 3 2 115 AC AS – –
(NO)
3TK2824- AL20 3 2 230 AC AS – –
ECrel
(NO) 3TK2825- BB40 4 3 24 DC AS/MS – –
SCrel
(NC)
3TK2825- AB20 4 3 24 AC AS/MS – –

SCrel 3TK2825- AJ20 4 3 115 AC AS/MS – –


(NC)
3TK2825- AL20 4 3 230 AC AS/MS – –
3TK2826- BB40 4 3 24 DC AS/MS – yes
1/2 channel AS/MS
3TK2826- CW30 4 3 24...240 AC/DC AS/MS – yes
3TK2826- BB41 4 3 24 DC AS/MS 0.05...3 yes
3TK2826- CW31 4 3 24...240 AC/DC AS/MS 0.05...3 yes
3TK2826- BB42 4 3 24 DC AS/MS 0.5...30 yes
3TK2826- CW32 4 3 24...240 AC/DC AS/MS 0.5...30 yes
3TK2826- BB44 4 3 24 DC AS/MS 5...300 yes
3TK2826- CW34 4 3 24...240 AC/DC AS/MS 5...300 yes
3TK2820- CB30 4 3 24 AC/DC AS/MS – yes
3TK2820- AJ20 4 3 115 AC AS/MS – yes
3TK2820- AL20 4 3 230 AC AS/MS – yes
1 Screw terminal
2 Spring terminal

9
© Siemens AG 2009

3TK2826 DC 24 V instantaneous 3TK2826 AC/DC 24 V ... 240 V instantaneous

CAS/ ECrel CAS/ ECrel


OS AS/MS & (NO) OS AS/MS & (NO)

S1 ECrel ECrel
AS/MS S1 AS/MS
(NO) (NO)
ECrel ECrel
(NO) (NO)

ECrel ECrel
(NO) (NO)

SCrel SCrel
(NC) (NC)

SCel SCrel
(NO) (NO)
SCel
(NO)
1 With/without cross-circuit fault detection 1 With/without cross-circuit fault detection
2 2NO/1NC+1NC evaluation 2 2NO/1NC+1NC evaluation
3 1x2/2x1 channel 3 1x2/2x1 channel
4 10 ms/50 MS debounce time for cascading and 4 10 ms/50 MS debounce time for cascading and
sensor input sensor input
5 Sensor input, monitored/automatic start 5 Sensor input, monitored/automatic start
6 Cascading input, monitored/automatic start 6 Cascading input, monitored/automatic start
7 Without/with testing at start 7 Without/with testing at start
8 Without/with automatic start after power failure 8 Without/with automatic start after power failure

3TK2826 DC 24 V delayed 3TK2826 AC/DC 24 V ... 240 V delayed

CAS/ ECrel CAS/ ECrel


OS AS/MS & (NO) OS AS/MS & (NO)

S1 AS/MS ECrel S1 AS/MS ECrel


(NO) (NO)
ECrel ECrel
td td
(NOtd) (NOtd)
ECrel ECrel
td td
(NOtd) (NOtd)

SCrel SCrel
(NC) (NC)
SCrel SCrel
(NCtd) (NCtd)

SCel SCrel
(NO) (NO)
1 With/without cross-circuit fault detection 1 With/without cross-circuit fault detection
SCel
2 2NC/1NC+1NO evaluation 2 2NC/1NC+1NO evaluation
(NO)
3 1x2/2x1 channel 3 1x2/2x1 channel
4 10 ms/50 MS debounce time for cascading and 4 10 ms/50 MS debounce time for cascading and
sensor input sensor input
5 Sensor input, monitored/automatic start 5 Sensor input, monitored/automatic start
6 Cascading input, monitored/automatic start 6 Cascading input, monitored/automatic start
7 Without/with testing at start 7 Without/with testing at start
8 Without/with automatic start after power failure 8 Without/with automatic start after power failure
1 on, 2 off, 3 off = safety shut-off mat operation. 1 on, 2 off, 3 off = safety shut-off mat operation.
Functions 4-8 same as above. Functions 4-8 same as above.

Detailed information on the functional principle and parameterization options of the 3TK2826 safety relays is provided by the
online simulation at www.siemens.com/safety-relays.

10
© Siemens AG 2009

3TK282. / 3TK283. relay enable circuits

3TK2827 basic unit

ECrel
S1 (NO)
MS
ECrel
(NO)

td
td
ECrel
(NOtd)
td ECrel
td
(NOtd)

SCrel
(NC)

1/2 channel
3TK2827 3TK2830

3TK2828 basic unit Type Max. Max. Rated control Autostart/ Delay time Electronic
ECrel achievable achievable supply voltage monitored (s) sensors
S1 Category SIL acc. to (V) start
AS (NO)
acc. IEC 61508
ECrel to EN 954-1
(NO) instantane-
ous/delayed
ECrel
td
(NOtd) 3TK2827- BB40 4/3 – 24 DV MS 0.5...30 –
ECrel 3TK2827- AB20 4/3 – 24 AC MS 0.5...30 –
td
(NOtd)
3TK2827- AJ20 4/3 – 115 AC MS 0.5...30 –
SCrel 3TK2827- AL20 4/3 – 230 AC MS 0.5...30 –
(NC)
3TK2827- BB41 4/3 – 24 DC MS 0.05...3 –
3TK2827- AB21 4/3 – 24 AC MS 0.05...3 –
1-/2-kanalig
3TK2827- AJ21 4/3 – 115 AC MS 0.05...3 –
3TK2827- AL21 4/3 – 230 AC MS 0.05...3 –
3TK2830 expansion unit 3TK2828- BB40 4/3 – 24 DC AS 0.5...30 –
FKrel 3TK2828- AB20 4/3 – 24 AC AS 0.5...30 –
A1
(S) 3TK2828- AJ20 4/3 – 115 AC AS 0.5...30 –
FKrel 3TK2828- AL20 4/3 – 230 AC AS 0.5...30 –
(S)
3TK2828- BB41 4/3 – 24 DC AS 0.05...3 –
FKrel
(S) 3TK2828- AB21 4/3 – 24 AC AS 0.05...3 –
FKrel 3TK2828- AJ21 4/3 – 115 AC AS 0.05...3 –
(S) 3TK2828- AL21 4/3 – 230 AC AS 0.05...3 –
3TK2830- CB30 as for the basic unit – 24 AC/DC – – –
3TK2830- AJ20 as for the basic unit – 115 AC – – –
3TK2830- AL20 as for the basic unit – 230 AC – – –
Press control units
3TK2834- BB40 4/– – 24 DC – – –
3TK2834- AB20 4/– – 24 AC – – –
3TK2834- AJ20 4/– – 115 AC – – –
3TK2834- AL20 4/– – 230 AC – – –
3TK2835- BB40 – – 24 DC – – –
3TK2835- AB20 – – 24 AC – – –
3TK2835- AJ20 – – 115 AC – – –
3TK2835- AL20 – – 230 AC – – –
1 Screw terminal
2 Spring terminal

11
© Siemens AG 2009

3TK285. contactor relay enable circuits/basic units

3TK2850 basic unit

ECcr
S1 (NO)
AS
ECcr
(NO)

ECcr
(NO)

1/2 channel

3TK2851 basic unit

ECcr
S1 (NO) 3TK2850
AS
ECcr
(NO)
Type Max. Max. Rated control Autostart/ Delay time Electronic
SCcr achievable achievable supply voltage monitored (s) sensors
(NC)
Category SIL acc. to (V) start
acc. to IEC 61508
1/2 channel EN 954-1

3TK2850- BB40 3 2 24 DC AS/MS – Yes


3TK2852 basic unit
3TK2850- AJ20 3 2 115 AC AS/MS – Yes
ECcr
S1 (NO)
AS 3TK2850- AL20 3 2 230 AC AS/MS – Yes
ECcr
(NO)
3TK2851- BB40 3 2 24 DC AS/MS – Yes

ECcr
3TK2851- AJ20 3 2 115 AC AS/MS – Yes
(NO)
3TK2851- AL20 3 2 230 AC AS/MS – Yes
ECcr
(NO) 3TK2852- BB40 3 2 24 DC AS/MS – Yes

ECcr 3TK2852- AL20 3 2 230 AC AS/MS – Yes


(NO)
3TK2853- BB40 4 3 24 DC AS/MS – Yes
ECcr
(NO) 1 Screw terminal
2 Spring terminal
SCcr
(NC)

1/2 channel

3TK2852 basic unit

BS ECcr
AS (NO)

KAS AS/MS ECcr


(NO)
AS/MS
S1 ECcr
(NO)

ECcr
(NO)

CC AS/MS

12
© Siemens AG 2009

3TK285. contactor relay enable circuits/expansion units

3TK2856 expansion unit, instantaneous Type Max. Max. Rated control Autostart/ Delay time (s)
achievable achievable supply voltage monitored
BS ECcr
& (NO) Category acc. SIL acc. to (V) start
to EN 954-1 IEC 61508
ECcr
KAS
(NO)

ECcr 3TK2856- BB40 as for the basic unit 3 DC 24 – –


(NO)

ECcr
3TK2857- BB41 as for the basic unit 3 DC 24 – 0.05...3
(NO)
3TK2857- BB42 as for the basic unit 3 DC 24 – 0.5...30
ECcr
(NO)
3TK2857- BB44 as for the basic unit 3 DC 24 – 5...300

ECcr 1 Screw terminal


(NO) 2 Spring terminal
ECel
(NO)

SCcr
(NC)

3TK2857 expansion unit, delayed


ECcr
BS td
(NOtd)
&
ECcr
KAS td
(NOtd)

td
ECcr
(NOtd)

ECel
(NO)

13
© Siemens AG 2009

Function description for

expanded functions

3TK2845 multi-function device

3TK2845 3TK2845 (delayed)

Type Max. Max. Rated control Autostart / Delay time Electronic


achievable achievable supply voltage monitored (s) sensors
Category SIL acc. to (V) start
acc. to IEC 61508
EN 954-1

3TK2845- HB40 4 3 24 DC AS/MS – yes


3TK2845- HB41 4 3 24 DC AS/MS 0.05...3 yes
3TK2845- HB42 4 3 24 DC AS/MS 0.5...30 yes
3TK2845- HB44 4 3 24 DC AS/MS 5...300 yes
3TK2845- DB40 4 3 24 DC MS – yes
3TK2845- DB41 4 3 24 DC MS 0.05...3 yes
3TK2845- DB42 4 3 24 DC MS 0.5...30 yes
3TK2845- DB44 4 3 24 DC MS 5...300 yes
3TK2845- EB40 4 3 24 DC AS/MS – yes
3TK2845- EB41 4 3 24 DC AS/MS 0.05...3 yes
3TK2845- EB42 4 3 24 DC AS/MS 0.5...30 yes
3TK2845- EB44 4 3 24 DC AS/MS 5...300 yes
3TK2845- FB41 4 3 24 DC MS 0.05...3 yes
3TK2845- FB42 4 3 24 DC MS 0.5...30 yes
3TK2845- FB44 4 3 24 DC MS 5...300 yes
3TK2845- GB41 4 3 24 DC MS 0.05...3 yes
3TK2845- GB42 4 3 24 DC MS 0.5...30 yes
3TK2845- GB44 4 3 24 DC MS 5...300 yes
1 Screw terminal
2 Spring terminal

14
© Siemens AG 2009

3TK2845-.HB4. multi-function device “monitored and automatic start”

3TK2845 monitored and automatic start (instantaneous)

KAS/ ECrel
BS Safety logic (NO)

S1 ECrel
(NO)

S2 ECrel
(NO)
Key-
operated ECrel
switch OFF (NO)

SCel
QS S1 QS S2 (NO)

3TK2845 monitored and automatic start (delayed) Example 3TK2845-.HB4.


Processing station with protective
KAS/ ECrel
(NO) hood and EMERGENCY STOP
BS Safety logic
ECrel
S1 (NO)

ECrel
S2 td
(NOtd)
Key-
operated td ECel
switch OFF (NOtd)

SCel
QS S1 QS S2 (NO)

3TK2845-.DB4. multi-function device “monitored start”

3TK2845 monitored start (instantaneous)

KAS/ ECrel
BS Safety logic (NO)

ECrel
S1
(NO)

ECrel
S2 (NO)
Key-
operated
ECrel
switch OFF (NO)

SCel
QS S1 QS S2 (NO)

Example 3TK2845-.DB4.
3TK2845 monitored start (delayed) Robot cell with protective door and
EMERGENCY STOP
KAS/ ECrel
BS Safety logic (NO)
ECrel
S1 (NO)

ECrel
S2 (NOtd)
Key-
operated
ECel
switch OFF (NOtd)

SCel
QS S1 QS S2 (NO)

If required, these devices can be switched over from normal to service operation via a switch.
Detailed information on the functional principle and parameterization options of the 3TK2826 safety relays is provided by the
online simulation at www.simens.com/safety-relays.

15
© Siemens AG 2009

3TK2845-.EB4. multi-function device “agreement button“

3TK2845 agreement button (instantaneous)

KAS/ ECrel
BS Safety logic (NO)
S1 ECrel
Agreement
button (NO)
S2 ECrel
Protective
door (NO)
Key-
operated
ECrel
switch OFF (NO)

SCel
QS S1 QS S2 (NO)

3TK2845 agreement button (instantaneous) Example 3TK2845-.EB4.


Robot cell with protective door
KAS/ ECrel
Safety logic (NO) and agreement button
BS
S1 ECrel
Agreement
button (NO)
S2 ECrel
Protective td
door (NO)
Key-
operated td ECel
switch OFF (NO)

SCel
QS S1 QS S2 (NO)

3TK2845-.FB4./.GB4. multi-function device “protective door tumbler mechanism spring force/magnetic force interlocked“

3TK2845 protective door tumbler mechanism spring force interlocked

KAS/ ECrel
BS Safety logic (NO)
S1 ECel
EMERGENCY
STOP (NO)
S2
Protective door ECrel
with tumbler Solenoid
mechanism control

Door ECel
release
(NO)
SCel
QS S1 QS S2 (NO)

3TK2845 protective door tumbler mechanism magnetic force interlocked Example 3TK2845-.FB4. /.GB4.
ECrel Robot cell with protective door
KAS/
BS Safety logic (NO) with tumbler mechanism and
EMERGENCY STOP
S1 ECel
EMERGENCY (NO)
STOP
S2 ECrel
Protective door
with tumbler Solenoid
mechanism control

Door ECel
release (NO)
SCel
QS S1 QS S2 (NO)

If required, these devices can be switched over from normal to service operation via a switch.
Detailed information on the functional principle and parameterization options of the 3TK2845 safety relays
is provided by the online simulation at www.simens.com/safety-relays.

16
© Siemens AG 2009

Standstill monitor 3TK2810.

3TK2810-0 standstill monitor


ECrel
(NO)
Uan
S1 ECrel
(NO)

ECrel
(NO)

ECrel
(NC)

SCel
(NO)

SCel
(NO)
3TK2810
SCrel
(W)
Type Max. Max. Rated Auto- Delay Electronic
achievable achievable control matic/ time (s) sensors
Category SIL acc. to supply monitored
acc. to IEC 61508 voltage (V) start
EN 954-1

3TK2810-0BA0. 4 3 24 DC – – –
3TK2810-0GA0. 4 3 230 AC – 0.05...3 –
3TK2810-0JA0. 4 3 230 AC – 0.5...30 –

17
© Siemens AG 2009

The information provided in this brochure contains merely


Siemens AG Subject to change without prior notice 06/09 general descriptions or characteristics of performance
which in actual case of use do not always apply as
Industry Sector Order No. E20001-A470-P305-V6-7600
described or which may change as a result of further
Low-Voltage Controls and Distribution DISPO 27602 development of the products. An obligation to provide the
P.O. Box 48 48 21/14128 FGSI.52.8.05 PA 0609 PDF respective characteristics shall only exist if expressly
90026 NÜRNBERG Printed in Germany agreed in the terms of contract.
GERMANY © Siemens AG 2009
All product designations may be trademarks or product
www.siemens.com/sirius names of Siemens AG or supplier companies whose use by
third parties for their own purposes could violate the rights
of the owners.

S-ar putea să vă placă și