PRODUCT-
Soot cleaning of Fuel Fir ed Heater using UPY-G01002-02PO
Fauch-400 cleaning liquid.
Document Title: Date Fir st I ssue: Revision:
Heat Generator Fuel Fired Heater 26.11.2018
Author :
Roger Amdam -
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
Document Type: Document Name:
PRODUCT-
Oper ator Guidelines UPY-H01001-01PO
Document Title: Date Fir st I ssue: Revision:
Exhaust Gas Economiser 06.11.2013
Author : L
Arne Skotte
Revision Histor y
Revision: Descr iption: Date: Sign:
A First Issue 06.11.2013 ASK
B Revised to fit software version 1.0.1 07.10.2014 TS
C Safety alarm separated, SW version 1.1.0 24.10.2014 TS
D Add soot cleaning 24.11.2014 ASK
E Changed settings exhaust pressure sensor, New SW version 01.12.2014 TS
F Changed settings exhaust pressure sensor 09.01.2015 TS
G New process pictures 13.02.2015 TS
H ModBus control & Recipes 04.03.2014 TS
I Changed 3.5.2.6 SETTINGS FOR EACH ECONOMISER A-D 13.10.2015 TS
J Changed alarm description 10.02.2016 TS
K Added battery maintenance 11.05.2016 TS
L Added information for HMI, Removed Spare parts 05.10.2016 TS
Document Summar y
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
1
The touch screen surface on the panel withstands exposure to the following
solvents without visible change:
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
2
2.1 Choice of Exhaust Gas Economiser
Ulmatec Pyro exhaust gas economiser is delivered in various sizes and capacities according to the heat
requirement available waste heat. The choice of the exhaust economiser is based on engine rating, exhaust gas
temperatures, exhaust gas flow, exhaust pipe diameter and the heating capacity. Important control parameter is
pressure drop and the lower exhaust gas temperature limit to avoid acid formation and the resultant corrosion
problems. Each project is calculated with all main parameters at various engine load levels.
2.2 Design
Ulmatec Pyro exhaust gas economiser is welded gas tube hot water boiler designed for marine use.
The water temperature is automatically controlled by a specially designed valve which diverts eshaust gas flow
through a bypass when the water temperature reaches the temperature selected by the operator. By using a
This design is also used to control the pressure drop across the exhaust gas economiser. The exhaust economiser
is delivered with control system, sensors and safety function. In case of a system failure the exhaust gas
economiser will automatically go to a bypass position. The exhaust gas economiser are insulated with 50mm
mineral wool and covered with galvanized sheet steel.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
CONTENTS
Note: The system is configurable and all pictures in this guideline are showing max
configuration. Actual displays may differ due to specific configuration.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.1.1 SUB-MENU DESCRIPTION
OPERATING MENU
Allow the operator to control the exhaust gas economizers, the pumps and view the alarm list.
SETTING MENU
Allow the operator to adjust set-point for the exhaust gas economiser, pumps.
Service Settings
Settings at comissioning
These settings are done at Harbour Acceptance Test (HAT).
Reset CANBUS
CANBUS must be reset after program load.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.1.2 MENU OVERVIEW
MAIN MENU OPERATING MENU ALARMS
SETTING MENU
SERVICE CONFIGURATION
SERVICE SETTING
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.2 OPERATING MENU
-
Allow the user to set the economiser Off and On.
1
EGE operates according to the temperature settings specified.
0
The economiser is set to full bypass
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.2.2 OTHER INFORMATION
-
Allow the user to set the circulation pumps in Manual or Auto.
M AN
Pumps can be started and stopped by pushing the pump symbol.
AUTO
Pumps starts according to pump pressure, and other pump settings.
- Pressure indication:
Water pressure is indicated on each side of the circulation pump.
- Operation and status indication for each circulation pump:
Grey=Off, Blue=Standby, Green=On, Red=Alarm
-
Allow the user to set the dumping pumps in Manual or Auto.
- Operation and status indication for each dumping pump:
Grey=Off, Blue=Standby, Green=On, Red=Alarm
3.2.3 ALARM
Shows the two most recent alarms / warnings.
Push the button to display the alarm list and to acknowledge or clear alarms.
Press the to acknowledge
the alarm list.
Press the to clear the list.
When clearing the list, active alarms
will remain on the list.
The following lines show the different status in the alarm list
Active Alarms:
Inactive Alarms:
Acknowledged Active Alarms:
Acknowledged Inactive Alarms:
Active Warning:
Inactive Warning:
Acknowledged Active Warning:
Acknowledged Inactive Warning:
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.2.3.1 AL ARM L I ST
Alarm Safety Circuit EGE A-D (Only shown when separated safety alarms are not selected)
Alarm High Differential Pressure Pumps
Alarm Low Differential Pressure Pumps
Alarm Power Failure
Alarm PLC
Alarm Circulation Pump No.: 1, 2 & 3
Alarm Dumping Pump EGE A, B, C & D
Alarm Exhaust damper valve EGE A, B, C & D
Alarm Damper clutch released EGE A, B, C & D
Alarm emergency stop EGE A, B, C & D (Only shown when separated safety alarms are selected)
Alarm low water level EGE A, B, C & D (Only shown when separated safety alarms are selected)
Alarm high water temp. EGE A, B, C & D (Only shown when separated safety alarms are selected)
Alarm Sensors
Alarm CANBUS off
Alarm CANBUS passive state
Warning high exhaust pressure EGE A, B, C & D
Warning stand by pump started
Warning low exhaust temperature EGE A, B, C & D
3.2.4 HELP
3.2.5 MAIN
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.3 SETTING MENU
Changes to the settings must be loaded to the PLC. Unloaded status are indicated by yellow
background. The black button loads the changes.
Pump j og:
The pump jog functionality is used to prevent that the sealing of the pump shall harden. The pump will
start and run for a short time. Both the run time and the time between each jog can be set from the
service menu.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.3.4 EXPORT USER RECIPES TO USB MEMORY STICK
- Select recipe you want to save, or make a new by typing in recipe name.
- All settings will be saved in a report and a recipe in the USB memory stick.
- Put the memory stick with the new recipe into the back of the panel (see picture 1)
- The recipe you want to replace, must be removed from the internal memory in the panel.
- Then the recipe can be imported from the memory stick by pressing the import button.
- After importing recipe, you must load the recipe from the internal memory in the panel to your system.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.3.6 ENABLE / DISABLE MODBUS REMOTE CONTROL
Press button to enable/disable MODBUS remote control
When enabled, the button is yellow, and these values can be controlled from MODBUS
- Setpoint operating water temperature
- Heater OFF/AUTO
When remote control is enabled, the text is shown
on the local control panel.
3.3.8 HELP
3.3.9 MAIN
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.4 OPERATIONAL INFO MENU
3.4.4 HELP
3.4.5 MAIN
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.5 SERVICE MENU
3.5.1 CONFIGURATION
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.5.1.3 RESET TO DEFAUL T CONFI GURATI ON
Resets all configuration to factory settings
3.5.1.5 HEL P
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.5.2 SERVICE SETTINGS
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.5.2.6 SETTI NGS FOR EACH ECONOM I SER A-D
3.5.2.8 HEL P
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.5.4 EXPORT FAT CONFIGURATION AND SERVICE SETTINGS TO USB
MEMORY STICK
All configurations and service settings will be saved to a USB memory stick connected at the back of
the panel. (pictur e 1, page 10). Press yes to replace the recipes
- Put the memory stick with the new recipes into the back of the panel. (pictur e 1, page 10)
- Press delete old recipes
- Press yes to delete
- Press Import, and all deleted recipes will be replaced by the new recipes from the memory stick to the
internal memory in the panel
- Next popup appears
- Press load FAT service setting and configuration recipe
- Put the memory stick with the new recipes into the back of the panel. (pictur e 1, page 10)
- Press delete old recipes
- Press yes to delete
- Press Import, and all deleted recipes will be replaced by the new recipes from the memory stick to the
internal memory in the panel
- Next popup appears
- Press load HAT service setting and configuration recipe
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
3.6 DOWNLOAD NEW SOFTWARE FROM USB MEMORY STICK
Program updates can be downloaded to the PLC and the Control Panel from an USB Memory Stick.
Load files sent from Ulmatec Pyro to an USB Memory Stick.
These files must be on the memory stick. The file fcu.fx may have a different name (*.fx)
Put the memory stick into the USB-port at the back of the control panel, and disconnect the power.
Reconnect the power, and the menus below will appear.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
4
Exhaust gas pressure sensor with pressure sensor type IFM PN2028
must be calibrated for measure rang -12,5mBar to 250mBar .
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
4.2 CLEANING WITH SOOT CLEANING LIQUID
Ulmatec Pyro exhaust gas economiser is delivered with removable plugs and inspection holes for cleaning and
inspection access. To simplify cleaning equipment for dosage of special chemicals while the exhaust gas
economiser in use is also installed to the unit as an option.
Checkpoints:
Descr iption Per sonal r equir ement
Owner
Mixing of the FAUCH400 liquid.
- Check that the air valve on the soot cleaning tank is closed.
- Check that the cleaning liquid valve on the soot cleaning tank is closed.
- Check that the soot cleaning tank is empty.
- Fill 0.5 litres of Fauch400 liquid on the tank.
- Fill 12.5 litres with water on the tank.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
4.3 WEEKLY MAINTENANCE
Checkpoints:
Descr iption Per sonal r equir ement
Functionality test, Verify reading from exhaust gas temperature sensor Owner
Functionality test, Verify reading from exhaust gas pressure sensor Owner
Inspection, The water level shall be checked. If necessary, refill water. Owner
Check that the water pressure from the filling source is higher than the system pressure.
Functionality test, Circulation pump (Optional) Owner
Functionality test, Dumping pump (Optional) Owner
Clean the exhaust gas economizer (with cleaning liquid) Owner
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
4.6 MAINTENANCE EVERY YEAR
Checkpoints:
Descr iption Per sonal r equir ement
Safety function, Exhaust damper safety position Ulmatec service engineer
Safety function, Safety temperature switch Ulmatec service engineer
Safety function, Water Low level switch Ulmatec service engineer
Safety function, Safety pressure valve Ulmatec service engineer
Failure modes, power supply Ulmatec service engineer
Failure modes, Interfaces Ulmatec service engineer
Failure modes, Protection circuits Ulmatec service engineer
Inspection, Expansion tank (air pressure) Ulmatec service engineer
Inspection, Circulation pump (Optional) Ulmatec service engineer
Inspection, Dumping Pump (Optional) Ulmatec service engineer
Inspection, Exhaust gas pressure sensors Ulmatec service engineer
Inspection, Exhaust gas temperature sensors Ulmatec service engineer
Inspection, Common alarm exhaust gas economisers Ulmatec service engineer
Control system, SW updates Ulmatec service engineer
Control system, Verify system setting Ulmatec service engineer
Control system, Electrical Installation Ulmatec service engineer