Total Full Load Line Current, Ampere 337.87 Total Line Current with application of demand factor, Ampere 174.64 Size and Type of Service Entrance conductor 2 - 100.0 mm2 THHN + 1 - 14.0 mm2 GW Copper Conductor in 35 mmφ IMC Service Equipment Protection 250 Ampere, 230 V, 2 pole