THE USE OF HEAT PUMP SYSTEMS IN DISTRICT


HEATING

Anatolii JURAVLEOV, Mikhail SIT, Boris SIT, Olga POPONOVA,


Alexandr ZUBATAI, Dmitrii TIMCENCO
Institute of Power Engineering of the Academy of Sciences of Moldova,
ieasm@cc.acad.md

Abstract One of the schemes of heat pump system This problem requires the additional research and
usage for the decrease of return delivery water will be discussed in the next papers. When the
temperature after district heating systems is considered. evaporator of HPS is installed at the outlet of the
Transcritical HPS cycles which use CO2 (R744) as a delivery water of CHSS of district heating system
working agent are examined as well.
(DHS) and the gas cooler is installed at the mixing
DHS pipe line it becomes possible to decrease the
Keywords: heat pump systems, transcritical cycle,
district heat systems. temperature schedule of heating. Water temperature
decrease on the inlet of DHS allows of trunk
pipelines capital intensity reducing (during their
1. INTRODUCTION maintenance or reconstruction).
The decrease of the return water temperature coming
Introduction of integrated heat supply systems to CHP plants leads to the reduction of the low-
consisting from CHP plants and distributed power potential heat used for CHP plant auxiliaries and it
generation sources, for example, heat pumps systems, becomes possible to produce additional electricity as
is one of the ways to increase district heating systems well.
efficiency. The problems of heat pumps usage in The aggregate of mentioned factors brings to the
district heating systems for achieving delivery water decrease of the fuel consumption which leads to the
high temperature schedules are not covered wide increase of technical and economic characteristics of
enough in corresponding literature. DHS as a whole and improves the ecological
This article outlines the scheme of the central heat situation in the region because of the decrease of CO2
supply station (CHSS) with built-in heat pump emissions and water losses from the cooling towers
system with CO2 (R744) as the working agent. to the atmosphere.
Heat pump cycles for cold (winter) and transitional
(autumn, spring) periods of the heating season are 2.1. Heat pump scheme for district heating
shown and the possibility to obtain heat pump
systems COP in 4.2…6.2 range during HPS Let’s consider the scheme of the central heat supply
transcritical cycle work is demonstrated. station (CHSS) with built-in heat pump.
Results of the pay-back period estimation and net On the fig.1: 1- DHS control valve, 2- load (many-
present value based on methods described in [3, 4, 5] storied buildings), 3 – gas cooler, 4- compressor, 5 –
for HPS usage in CHSS with the thermal power of HPS evaporator, 6 - CHSS circulation pump of, 7-
1.6 MWt are demonstrated as well. throttling valve, 8 – internal heat exchanger of HPS.
Heat pump system is connected to the DHS return
2. HEAT PUMPS IN DISTRICT HEATING water pipe line which comes back to CHP plant.

The use of CO2 as a working agent for the heat


pumps is proved in [6, 7, 8] and a lot of other papers.
As a result of the fact that heating system power for
the winter and the transitional period differs in 2,5-3
times, only one HPS usage looks to be economically
inappropriate to ensure district heating and hot water-
supply. It seems to be more rational to ensure district
heating and hot water-supply using 2-3 HPS with the
decreased power, where each HPS operates at its
temperature of evaporation and its span of the sliding
temperature of the gas cooler.

229
Figure 1: Schematic of CHSS with built-in HPS. Table: 1. Parameters and their values
Other part of return water flow which is being mixed The Coefficient of Performance of HPS is
with direct water from power plant and is heated in [COP=4,26] (Recall that COP is defined as the
the HPS gas condenser (due to heat export out of desired heat transferred divided by the work done on
HPS). the compressor).
The cooled flux of the return water on power plant The transcritical cycle of heat pump in the h-p
can enter in network heaters or in the steam turbine Diagram for Carbon Dioxide (R744) (H [kJ/kg] –P
condenser (in the main or in the built-in heat [MPa]), at the ambient temperature 60? is shown at
exchanging bank). the Figure 3.
2.1.1. Temperature charts
Equations which determine the dependence between
direct and return delivery water temperatures are
described in different manuals, see for example [9,
10], and are not cited here.
For the delivery water coming from the CHP plant
the temperature schedule 80/30 is applied, and for
DHS schedule is – 80/35. The specified temperature
of the ambient air is assumed to be equal to -160?,
and the temperature of the ambient air when heating
season is finishing is assumed to be 60?.
80/35 temperature chart usage is determined by the
fact that currently massive introduction of horizontal
double-pipe heat systems in multistoried buildings is Figure 3: Thermodynamic cycle for the temperature
planned. In this case the temperature of the water of the air 60C.
supplied is the same for all heating appliances. Values of parameters of the working agent in points
1…6 of HPS (see, Fig.1) for this case are shown in
2.1.2. Heat pump cycle Table 2. In this case [COP=6,24].
P-h diagrams are made according to the equations
The transcritical cycle of heat pump in the h-p
elaborated by R. Span and W. Wagner [11].
Diagram for Carbon Dioxide (R744) (H [kJ/kg] –P
[MPa]), at the ambient temperature -90? is shown at
the Figure 2. B of the T(0C) P(MPa) H(kJ/kg)
point
1 25 5,73 -81,87
2 60 9,0 -64,04
3 40 9,0 -162,87
4 37 9,0 -194,01
5 20 5,73 -194,57
6 20 5,73 -98,70
Table: 2. Parameters and their values
After the investigation of thermodynamic cycles
becomes evident that it is necessary to use the
adjustable compressor and heat-exchange equipment
with varying heat-exchange surface which changes
depending on the ambient temperature and the
temperatures of the direct and return delivery water or
Figure 2: Thermodynamic cycle for the temperature the use of some HPS of the smaller output.
of the air -90C. Modeling results show that with the decrease of the
Parameters values of the working agent in points 1…6 ambient temperature the relationship between the
of HPS (see, Fig.1) are shown in Table 1. CHSS thermal power and HPS thermal power
B of the T(0C) P(MPa) H(kJ/kg) increases from 0, 13 at the ambient temperature 60?
point to 0, 39 at the ambient temperature -90?.
1 20 3,5 -45,5
2 90 9 -9,47 2.1.3. Economic efficiency of the use of HPS
3 40 9 -162,87 One of the most important indexes of the investment
4 37,2 9 -192,38 project is pay-back period and Net Present Value. We
5 0 3,47 -192,38 assumed the bank rate to be equal 0.14, inflation
6 0 3,47 -75,82 index equals 0.1.

230
Fig.4 Relationships between the pay-back period of HPS (heat pump station) and the price of K.W.H. of HPS
at the different COP of HPS.

Fig.5 Relationships between the NPV of HPS (heat pump station) and the price of K.W.H. of HPS at the
different COP of HPS.

231
Figure 4 shows the relationships between the pay-back pumps stations. Teplofizika I Aeromehanica,
period of HPS (heat pump station) and the price of 2001, v8, no.1, pp143…149, (in Russian).
K.W.H. of HPS at the different COP of HPS. Figure 5 [4] Tarasov O. Economic efficiency of interaction of
shows relationships between the NPV of HPS (heat independent heat producers and Nerungri CHP
pump station) from COP and the price of K.W.H. of plant. http://www.imce.ru/r3n3.html.
HPS.
[5] Savchuk V.P. Efficacy Evaluation of the
Investment Project.
4. CONCLUSIONS http://www.cfin.ru/finanalysis/savchuk/index.shtml
[6] P. Hrnjak Technological and theoretical
The scheme of CHSS with built-in HPS which works opportunities for further improvement of efficiency
in the integrated heat supply system with the reduced and performance of the refrigerant candidates
temperature chart of heat supply system is examined. achievements and potentials of efficiency increase
Carbon Dioxide is used as a working agent in HPS. http://www.r744.com/knowledge/papers_free_sear
The transcritical cycles of HPS are examined in the ch.php?papers_id=pdf_102&txt_key_free=&sortby
dependence of the ambient air temperature. The =year%20DESC.
directions of the efficient use of heat pump systems [7] Man-Hoe Kim, Jostein Pettersen, Clark W.
on CHSS are proposed. The indices of technical and Bullard Fundamental process and system design
economic efficiency of the use of HPS in CHSS are
issues in CO2 vapor compression systems.
determined.
Progress in Energy and Combustion Science 30
Acknowledgments (if any) should appear as a
(2004) 119–174.
separate non-numbered section before the list of
references. [8] Bullard C. Transcritical CO2 systems- recent
progress and new challenges.
References http://www.iifir.org/en/doc/1057.pdf
[9] Sokolov E.Ia. Tepofikatsia i teplovie seti. M.
[1] A.I. Andriuschenko Combined heat supply Energia, 1974 (in Russian).
systems. Teploenergetika, no.5, 1997, pp.23- [10] Iantovskii E.I., Pustovalov Iu.V.
27,(in Russian). Parokompessionnie teplonasosnie ustanovki.
[2] A.I.Andriuschenko Principles of creation of Energoizdat, 1982.
highly economical centralized heat supply systems [11] R. Span and W. Wagner Equations of State for
for cities. Promishlennaia Energetica, 2003, no.3, Technical Applications. III. Results for Polar
pp.8-11, (in Russian). Fluids,International Journal of Thermophysics,
[3] Tomilov V.G., Schinnikov V.F., P.A. Nozdrenko, 2003, Vol. 24, No. 1, pp.111-162.
Iu.L. Pugach Fuel economy in the system due to
the use of CHP plant in the combined
thermalclamping regime with district heating heat