Sunteți pe pagina 1din 24

#1 Generator Protection System I Commissioning Report (10CHA01)

2X300MW TTHERMAL POWER PLANT


YAMUNA NAGAR HARYANA-INDIA

#1 Genrator Protection System I (10CHA01)

Commissioning Report

Commissioning:

Check:

Date:

-1-
#1 Generator Protection System I Commissioning Report (10CHA01)

Section I: Authorized Illumination

I. Objective
This report is specially set for the designed of 2X300MW TTHERMAL POWER PLANT YAMUNA
NAGAR HARYANA-INDIA #1 Generator Protection System I(10CHA01) as a verification plan for
inspection of system and performance of device.

II. Foundation & Sampling


1. 《Technical Specifications for Relaying Protection and Safe Automatic Devices》Issued by Ministry
2. 《Generad specification for control and protection panel(cabinet、desk)of secondary circuit of power
system》
JB/T 5777.3 – 2002

III. Testing condition


3.1 Testing environment:
On the condition of normal atmosphere as followings:
Environment temperature: 10℃~35℃
Relative humidity: 45%~75%
Atmospheric pressure: 86kPa~106kPa

3.2 Testing power supply:


3.2.1 AD power supply: DC220V, ripple factor is not more than 5%
3.2.2 AC power supply: AC240V, 50HzASine wave, Aberrance factor is not more than 5%

3.3 Testing instrument:


Relay protection star 802 micro-relay protection instrument
ZC25-3 500V Meganeter
FLUKE numeric multimeter
Portable equipment with DIGSI4.71software
Several test leading wires

IV. Notice proceedings


4.1 Turn off the switch of power supply before plug or pull the module to make the DC power supply off.
Never plug or pull the module with electricity to prevent the component from damage.
4.2 Special measures must be adopted during the module plug or pull to avoid component damages by static
electricity of human body.
4.3 Fix earthing screw firmly to the earth lead before other connections achieved
4.4 High voltage may occur between the circuit and component used for connecting the DC power supply or
testing or experiment.
4.5 Risky high voltage may occur on the device even if the DC circuit switch off. (The energy storage
capacitor discharge)

-2-
#1 Generator Protection System I Commissioning Report (10CHA01)

4.6 The testing capacity cannot exceed the limit number specified in the technical datasheet for every device.

V. Testing Contents
5.1 Machinery appearance and configuration inspection
5.2 Equipment and connections
5.3 Insulation property
5.4 Electric property

Section II: Test data and results

I. Machinery appearance and configuration (Qualified√)


NO. Content Conclusion
1 Fix of protection equipment meet the requirement of drawing √
2 Appearance of insert piece and quality of welding meet the requirement of techniques √
3 Fixed well, no loose, no obvious damage and distortion on the protection equipment √
4 Marking is clear and right, the terminal of protection equipment connected reliable √
5 Switch, keyboard should be operated flexible with right handle √
6 No dust and sundries in the screen √
7 Easy to move the door of screen and open the lock √
8 No lacquer drop and knock and fish tail inside and outside of the screen √
9 All kinds of markings and signs are right and clear √

II. Device and connection inner screen (Qualified √)


No. Test content Conclusion
1 Check if the nameplate, model of relay meets the design requirement. Pay special √
attention on rating current of the assistant power supply and mutual-inductor
2 Check if the actual connection meets the requirement of design drawing and the √
connection is fixed firmly
3 Check if the protection screen and all shielding cable earthed well √
III. Insulation test (insulation resistance)
1. Remove all the connection points on the screen, with the DC circuit short circuit on the both input points
and input points of AC circuit.
2. Measure the insulation resistance about all independence circuits to earth and among all independence
circuits with ZC25-3 500V Megameter

No. Items Insulation resistance

-3-
#1 Generator Protection System I Commissioning Report (10CHA01)

(MΩ)
1 DC circuit to earth >100MΩ
2 AC circuit to earth >100MΩ
3 Open circuit to earth >100MΩ
4 Out circuit to earth >100MΩ
5 DC circuit to AC circuit >100MΩ
6 DC circuit to open circuit >100MΩ
7 DC circuit to out circuit >100MΩ
8 AC circuit to out circuit >100MΩ
9 AC circuit to out circuit >100MΩ
10 Open circuit to out circuit >100MΩ

Note: not less than 5 MΩ with secondary circuit, not less than 10 MΩ without secondary circuit.

IV. Power performance


4.1 List of 10CHA01 1st set electric generator protection function

Code /Model ANSI Code setting value function Setting value Remarks
Address

-4-
#1 Generator Protection System I Commissioning Report (10CHA01)

F11 87G Generator differential 2001~2063


7UM6225-5EB92-0CA0-LOD protection

64G Stator earth protection 6001

21 Impedance protection 3301~3317

59 Over voltage protection 4101~4107

95 Generator interturn fault Pro. 5501

27 undervoltage protection 4001~4006

50V Overcurrent protection(with 1301~1305


undervoltage)

81 Frequency protection 4201~4215


46 Neg. overcurrent protection 1701~1707
49 Overload protection 1601~1616
40 Loss of execited 3001~3014
32F Low power protection 3201~3206
32R Reverse Power protection 3101~3105
24 Overexcitation protection 4301~4305
78 Generator Pole Slipping 3501~3512
Protection
50/27 Inadvertent energizing Pro. 7101~7105

F12 32R Reverse Power protection 3101~3105


7UM6115-5EB90-0AA0-LOD

4.1.1 Information about protection equipment of electric generator (7UM6225-5EB92-0CA0-LOD)

Manufacturer SIEMENS Model 7UM6225-5EB92-0CA0-LOD


Serial No. BF061005154 Software version V 4.6
2
Mounting position 10CHA01-F11 Purpose Generator protection
4.1.2 Information about protection equipment of electric generator (7UM6115-5EB90-0AA0-LOD)

Manufacturer SIEMENS Model 7UM6115-5EB90-0AA0-LOD


Serial No. BF061005152 Software version V 4.1
7
Mounting position 10CHA01-F12 Purpose Generator protection

4.2 DC power supply

-5-
#1 Generator Protection System I Commissioning Report (10CHA01)

Check if the magnitude and polarity of voltage meet the requirement by multimeter before the equipment
electrified with DC. Check the DC control voltage of input circuit on relay according to the design requirement
1. DC input:

Theoretical value (Allowable deviation ±20%) Real value DC I Real value DC II


219.7V 220.4V
220V DC
Test result:OK

2. Press the LED reset button to check if the light on the panel bright and the testing finished: Press the B10
black button the check if the yellow and red light are bright and the testing finished.
Test result: OK

4.3 Input of setting value


1. Input the setting of all function, parameters, fixed value according to the setting book
2. Category the required LED light, way out circuit, switching value input circuit according to the design or
setting book or the requirement of user on-site.
3. Logic programmed according to the situation of field apparatus or the operation requirement
Note: set and test according to leaving factory default value if there is no setting book for inference
4.4 Test of AC phase sequence and current, voltage input circuit linearity (Current, voltage error is less than
5%)
Note: reading is first value Unit: kA; kV. Transformation ratio CT side1 is set as 30000/5A; side2 as
30000/5A; Transformation ration PT is set as 20kV/110V.

F11 (7UM6225-5EB92-0CA0):
Sampling value of currentM1(side1) IA IB IC
IE
0.6 0.6 0.6
0.1A
3 3.01 3
0.5A
6.02 6 6.02
1A
12.02 12.01 12.01
2A
Sampling value of Current M2 IA IB IC
(side2) IE
0.6 0.6 0.6
0.1A
3.01 3 3.01
0.5A
6.01 6.01 6
1A
12.01 12 12.01
2A
Sampling value of voltage UAB UBC UCA Uen
0.91 0.909 0.91 0.91
5V
1.82 1.818 1.82 1.82
10V
3.636 3.64 3.636 3.64
20V

-6-
#1 Generator Protection System I Commissioning Report (10CHA01)

Note: reading is first value Unit: kA; kV. Transformation ratio CT is set as 30000/5A; Transformation ration
PT is set as 20kV/110V.
F12 (7UM6115-5EB90-0AA0):
Sampling value of current IA IB IC
0.6 0.6 0.6
0.1A
3 3.01 3.01
0.5A
6.01 6.02 6.02
1A
12.01 12.02 12
2A
Sampling value of voltage UAB UBC UCA Uen
0.909 0.91 0.909 0.909
5V
1.818 1.8 1.82 1.818
10V
3.636 3.64 3.64 3.636
20V
Test result:OK

4.5 Protection function test


Requirements: the error of operated value can not over the 5 % of setting value; if the start value of operated
for differential protection is 0s, the value of 1.5 times is about 35ms and the allowable error of additional relay
time is 1% of setting value for time.

4.5.1 F11 (7UM6225-5EB92-0CA0):


1. Test data of differential protection (87G):
Title Name:GenratorProtectionAddress:11Model: 7UM6225-5EB92-0CA0
Items Serial No.: Version of software: Voltage ratio:
BF0610051542 V4.6 20KV/110V
Power parameter Side1CT no-load Side 2 CT no-load Capacity: 353MVA
voltage ratio: voltage ratio:
12000A/5A
12000A/5A

-7-
#1 Generator Protection System I Commissioning Report (10CHA01)

Differe Setting value Test result


I=0.3I/In0
nt pickup SIDE1 A SIDE1 B SIDE1 C SIDE2 A SIDE2 B SIDE2 C
T=0 1.266A 1.264A 1.265A 1.266A 1.265A 1.263A
ia
l Diff. I=5 I/In0 SDIE1 A SIDE1 B SIDE1 C SIDE2 A SIDE2 B SIDE2 C
T=0 2.115A 2.114A 2.116A 2.117A 2.115A 2.113A
pr
ot Slope 1 S1=0.25 SIDE1 A & SIDE2 A SIDE1 B & SIDE2 B SIDE1 C & SIDE2 C
e Basic point 0 5.33A/3.198A 5.33A/3.196A 5.33A/3.194A

ct
Slope 2 S2=0.5 SIDE1 A & S2 A SIDE1 B & SIDE2 B SIDE1 C & SIDE2 C
io 16.453A/9.01A 16.453A/9A 16.453A/8.98A
Basic point
n 2.5 I/In0
8
7
G

2. Test data of stator earth protecion (59N/67GN) :

Protection Setting value Operated value Setting time (s) Operated time (s)
10V 10.01V 0.3 0.301
59N>

3. Test data of stator earth protection with 3rd Harmonics(27/59TN) :

Protection Setting value Operated value Setting time (s) Operated time (s)
2V 2.01V 0.5 0.501
59TN>

4. Test data of low resistance protection (21):

Protection Setting value Operated value Setting time (s) Operated time (s)
0.11 Ohm 0.11 Ohm 0.3 0.3
Z1
0.19 Ohm 0.19 Ohm 0.3 0.3
Z1B
0.19 Ohm 0.19 Ohm 3.5 3.501
Z2

5. Test data of over-voltage protection (59):

Protection Setting value Operated value Setting time (s) Operated time (s)
120V 119.85V 3 3.02
U>
130V 129.73V 0.5 0.501
U>>

6. Test data of interturn protection on generator:

-8-
#1 Generator Protection System I Commissioning Report (10CHA01)

Protection Setting value Operated value Setting time (s) Operated time (s)
2.2V 2.2V 0.5 0.501
95

7. Test date of under-voltage protection (27):

Protection Setting value Operated value Setting time (s) Operated time (s)
75V 74.99V 3 3.01
U<
65V 64.95V 0.5 0.502
U<<

8. Test data of back up over current protection (51) (undervoltage holding):

Protection Setting value Operated value Setting time (s) Operated time (s)
7A 7.01A 3.5 3.499
I>
80V 79.9V 8 8.01
U<

9. Test data of generator pole slipping protection (78):

Borderline of Operated state First list Second list Third list


impedance

U=5V,I=6.5V,Φ= U=0V,I=6.5V,Φ= U=5V,I=6.5V,


Za operated
0° 180° Φ= 180°
U=5V,I=6.5V,Φ= U=0V,I=6.5V,Φ= U=0.5V,I=6.5V,
No-operated
0° 180° Φ= 180°
U=2V,I=6.5V,Φ= U=1.45V,I=6.5V, U=2V,I=6.5V,
Zb operated
0° Φ=-90° Φ= 180°
U=2V,I=6.5V,Φ= U=1.5V,I=6.5V, U=2V,I=6.5V,
No-operated
0° Φ= -90° Φ= 180°
U=2V,I=6.5V,Φ= U=0.84V,I=6.5V, U=2V,I=6.5V,
Zc operated
0° Φ= 90° Φ= 180°
U=2V,I=6.5V,Φ= U=0.9V,I=6.5V, U=2V,I=6.5V,
No-operated
0° Φ= 90° Φ= 180°
U=2V,I=6.5V,Φ= U=1.9V,I=6.5V, U=2V,I=6.5V,Φ=
Zd operated
0° Φ= 90° 180°
U=2V,I=6.5V,Φ= U=2.1V,I=6.5V, U=2V,I=6.5V,Φ=
No-operated
0° Φ= 90° 180°

10. Test data of loss of excitation protection (40):

Angle of U/I Static state value Dynamic value


(0MW,-187.38MVAR) (0MW,-458.78MVAR)
90°
(50.26MW,-187.46MVAR) (129.35MW,-505.93MVAR)
75°

-9-
#1 Generator Protection System I Commissioning Report (10CHA01)

(109.55MW,-189.63MVAR)
60°
(177.75MW,-177.81MVAR)
45°
Oerated time(s) Operated time t1=10.02 Operated time t2 Operated time t3 t3=2.03
t2=0.505
Φ1 80° Φ2 90° Φ3 110°
Setting value
Φ1=arctg[(177.75-109.55)/(-177.81+189.63)]= 80.167°
Calculate
Φ2=arctg[(50.26-0)/(-187.46+187.38)]= 89.94°
Φ3=arctg[(129.35-0)/(-505.93+458.78)]=110°

Voltage(v) operated value dropped value dropped rating


8.05 7.64 0.95

11. Test data of overexcitation protection (24):

Protection Setting value Operated value Setting time (s) Operated time (s)
1.07 1.07 10 10.242
24-1
1.2 1.2 60 60.21
24-2
12. Test data of frequency protection (81):

Protection Setting value (HZ) Operated value (HZ) Setting time (s) Operated time (s)
48.0 47.9 1 1.01
81-1
47.0 46.8 6 5.99
81-2
49.5 49.46 20 20.03
81-3
52 52.1 10 10.08
81-4

13. Test data of forward power protection (32F):

Protection Setting value Operated value Setting time (s) Operated time (s)
96.6% 482.69W 10 9.98
P>
7.7% 73.83W 2 1.99
P<

14. Test date of overload protection (49):

Protection Setting Setting Setting Operated Operated Operated


time1 (s) time2 (s) time 3 (s) time 1 (s) time 2 (s) time 3 (s)
20 32 38.7 19.08 31.096 38.069
49

15. Test data of negative sequence protection of generator (46):

Protection Setting value Operated value Setting time (s) Operated time (s)
10% 0.504A 20 19.89
46-1

- 10 -
#1 Generator Protection System I Commissioning Report (10CHA01)

60% 3A 3.5 3.501


46-2

16. Test data of Inadvertent Energizing Protection (50/27):

Protection Setting value Operated value


1.5A 1.48A
I
55V 54.97V
V1
0.5S 0.498S
T

4.5.2 F12 (7UM6115-5EB90-0AA0):


1. Test data of reverse power protection (32R):

Protection Setting value Operated value Setting time (s) Operated time (s)
-3.62% -11.49W 5 5.08
P>
Test result: OK

4.6 Function test (Qualified “√”)


4.6.1 F11 (7UM6225-5EB92-0CA0)
Name Test method Device F11 Result
Loss-water of generator Short circuit between X130-1and X130-9 BI1 √
Tripping operation on Short circuit between X130-1 and X130-10 BI2 √
thermodynamic protection
Main stop valve shut off Short circuit between X130-1 and X130-11 BI3 √
Field breaker close Short circuit between X130-1 and X130-12 BI4 √
Main convertor 220kV side Short circuit between X130-1 and X130-13 BI5 √
circuit breaker close
High temperature on the Short circuit between X130-1 and X130-14 BI6 √
Stator winding
High-high temperature on Short circuit between X130-1 and X130-15 BI7 √
the stator winding
Differential generator- Short circuit between X130-21 and X130-29 BI9 √
transformer set
Unit transformer#1 Short circuit between X130-21 and X130-30 BI10 √
differential protection
Unit transformer#2 Short circuit between X130-21 and X130-31 BI11 √
differential protection

- 11 -
#1 Generator Protection System I Commissioning Report (10CHA01)

Unit transformer#1 zero- Short circuit between X130-21 and X130-32 BI12 √
sequence differential
protection on low voltage
Unit transformer#1 Short circuit between X130-21 and X130-33 BI13 √
instantaneous current
protection on the high
voltage side
unit transformer#2 Short circuit between X130-21 and X130-34 BI14 √
instantaneous current
protection on the high
voltage side
Main transformer on the Short circuit between X130-21 and X130-35 BI15 √
side of high voltage backup
earth fault protection

4.6.2 F12 (7UM6115-5EB90-0AA0)


Name Test method Device F11 Result
Main heavy gas relay Short circuit between X130-1and X130-9 BI1 √
Main transformer Short circuit between X130-1 and X130-10 BI2 √
onloadtapchanging oil
pressure release
Heavy gas relay of plant unit Short circuit between X130-1 and X130-11 BI3 √
transformer #1
High-high oil temperature of Short circuit between X130-1 and X130-12 BI4 √
unit transformer #1
Heavy gas relay of unit Short circuit between X130-1 and X130-13 BI5 √
transformer#2
High-high oil temperature of Short circuit between X130-1 and X130-14 BI6 √
unittransformer #2
High-high temperature of Short circuit between X130-1 and X130-15 BI7 √
main transformer winding

4.7 Output test of protection (Right “√” )


PROTECTION links Corresponding teminal State Result

- 12 -
#1 Generator Protection System I Commissioning Report (10CHA01)

F11 X160:21-22 OPEN √


GEN.DIFF.PROTOPTD X160:24-25 OPEN √
(87G)
X160:27-28 OPEN √
X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN.STATOR EARTH FAULT X160:24-25 OPEN √
PROT.95% (64G1)
X160:27-28 OPEN √
X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √

- 13 -
#1 Generator Protection System I Commissioning Report (10CHA01)

Close L108 X160:63-65 CLOSE √


Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN.REVERSE POWER PROT X160:24-25 OPEN √
3R-2
X160:27-28 OPEN √
X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN.LOW FORWARD POWER X160:24-25 OPEN √
PROT .32F
X160:27-28 OPEN √

- 14 -
#1 Generator Protection System I Commissioning Report (10CHA01)

X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN.LOW IMPEDANCE PROT X160:24-25 OPEN √
21G
X160:27-28 OPEN √
X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √

- 15 -
#1 Generator Protection System I Commissioning Report (10CHA01)

Close L113 X160:75-77 CLOSE √


X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN. OVEROVOLTAGE PROT X160:24-25 OPEN √
59G2
X160:27-28 OPEN √
X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN. INTERTURN PROT X160:24-25 OPEN √
95
X160:27-28 OPEN √
X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √

- 16 -
#1 Generator Protection System I Commissioning Report (10CHA01)

Close L102 X160:39-41 CLOSE √


Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN. BAK-UP OVERCURRENT X160:24-25 OPEN √
PROT. I>SPACE WITH U< SEAL-IN
50V
X160:27-28 OPEN √
X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √

- 17 -
#1 Generator Protection System I Commissioning Report (10CHA01)

X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN. UNBLANCED LOAD PROT X160:24-25 OPEN √
I2>>TRIP
46-2
X160:27-28 OPEN √
X160:30-31 OPEN √
X160:33-34 OPEN √
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 Close L111 X160:67-69 CLOSE √
GEN. UNDER FREQUENCY PROT. X170:17-18 CLOSE √
F<47HZ
81U-3
X171:9-10 CLOSE √
X172:9-10 CLOSE √
X173:5-6 CLOSE √
X100:3-9 CLOSE √
F11 Close L111 X160:67-69 CLOSE √
GEN. OVEREXCETION PROT. X170:17-18 CLOSE √
STAGE-II
X171:9-10 CLOSE √

- 18 -
#1 Generator Protection System I Commissioning Report (10CHA01)

OPTD (U/F>>) X172:9-10 CLOSE √


24-2
X173:5-6 CLOSE √
X100:3-9 CLOSE √
F11 Close L111 X160:67-69 CLOSE √
GEN. OVERLOAD PROT. Θ》TRIP X170:17-18 CLOSE √
49-2
X171:9-10 CLOSE √
X172:9-10 CLOSE √
X173:5-6 CLOSE √
X100:3-9 CLOSE √
F11 Close L111 X160:67-69 CLOSE √
GEN.LOSS OF EXCITATION X170:17-18 CLOSE √
PROT.CHAR2 OPTD (STAT. STAB 2)
40-2
X171:9-10 CLOSE √
X172:9-10 CLOSE √
X173:5-6 CLOSE √
X100:3-9 CLOSE √
F11 Close L111 X160:67-69 CLOSE √
GEN.UNBLANCED LOAD PROT X170:17-18 CLOSE √
I2P> SPACE 46
PROTECTION
X171:9-10 CLOSE √

X172:9-10 CLOSE √
X173:5-6 CLOSE √
X100:3-9 CLOSE √
F11 EXTERNAL BINARY INPUT X160:21-22 OPEN √
BI: GT OVERALL DIFFERENTIAL X160:24-25 OPEN √
PROT
BI: UAT #1 DIFFERENTIAL PROT
X160:27-28 OPEN √
BI: UAT #1 DIFFERENTIAL PROT X160:27-28 OPEN √
BI: UAT #1 LV RESTRICTED E/F X160:30-31 OPEN √
PROT
X160:33-34 OPEN √
BI: UAT #1 HV HIGH SET INST.O/C
PROT Close L101 X160:35-37 CLOSE √
+ LOW SET INVERSE O/C PROT Close L102 X160:39-41 CLOSE √
BI: UAT #1 HV HIGH SET INST.O/C
Close L103 X160:43-45 CLOSE √
PROT
+ LOW SET INVERSE O/C PROT Close L104 X160:47-49 CLOSE √
BI: GT HV IDMT STANDBY E/F Close L105 X160:51-53 CLOSE √
PROT
Close L106 X160:55-57 CLOSE √

- 19 -
#1 Generator Protection System I Commissioning Report (10CHA01)

Close L107 X160:59-61 CLOSE √


Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F12 EXTERNAL BINARY INPUT X160:21-22 OPEN √
TRIP X160:24-25 OPEN √
BI: GT TRANS. BUCHHOLZ
X160:27-28 OPEN √
RELAY
BI: GT OLTC OIL SURGE PROT X160:30-31 OPEN √
BI: UAT #1 BUCHHOLZ RELAY X160:33-34 OPEN √
BI: UAT #1 OIL TEMP. HIGH-HIGH Close L101 X160:35-37 CLOSE √
BI: UAT #1 BUCHHOLZ RELAY
BI: UAT #1 OIL TEMP. HIGH-HIGH
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
Close L105 X160:51-53 CLOSE √
Close L106 X160:55-57 CLOSE √
Close L107 X160:59-61 CLOSE √
Close L108 X160:63-65 CLOSE √
Close L111 X160:67-69 CLOSE √
Close L112 X160:71-73 CLOSE √
Close L113 X160:75-77 CLOSE √
X170:15-16 CLOSE √
X171:7-8 CLOSE √
X172:7-8 CLOSE √
X173:3-4 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN. UNDER FREQUENCY PROT. X160:24-25 OPEN √

- 20 -
#1 Generator Protection System I Commissioning Report (10CHA01)

81U-2 Close L101 X160:35-37 CLOSE √


F<48HZ
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
X170:19-20 CLOSE √
X171:11-12 CLOSE √
X172:11-12 CLOSE √
X173:7-8 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
EN. LOSS OF EXCITATION PROT. X160:24-25 OPEN √
40-3
CHAR.3 OPTD (DYA. STAB)
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
X170:19-20 CLOSE √
X171:11-12 CLOSE √
X172:11-12 CLOSE √
X173:7-8 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN. POLE SLIPPING PROT. X160:24-25 OPEN √
78
CHAR.1 OPTD
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
X170:19-20 CLOSE √
X171:11-12 CLOSE √
X172:11-12 CLOSE √
X173:7-8 CLOSE √
X100:3-9 CLOSE √
F11 X160:21-22 OPEN √
GEN. DEAD MACHINE PROT. X160:24-25 OPEN √

- 21 -
#1 Generator Protection System I Commissioning Report (10CHA01)

50/27 Close L101 X160:35-37 CLOSE √


Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
X170:19-20 CLOSE √
X171:11-12 CLOSE √
X172:11-12 CLOSE √
X173:7-8 CLOSE √
X100:3-9 CLOSE √
F12 EXTERNAL BINARY INPUT X160:21-22 OPEN √
BI: GT WINDING TEMP. HIGH- X160:24-25 OPEN √
HIGH
Close L101 X160:35-37 CLOSE √
Close L102 X160:39-41 CLOSE √
Close L103 X160:43-45 CLOSE √
Close L104 X160:47-49 CLOSE √
X170:19-20 CLOSE √
X171:11-12 CLOSE √
X172:11-12 CLOSE √
X173:7-8 CLOSE √
X100:3-9 CLOSE √
CIRCUIT BREAKER START FAULT Close L109 X160:79-81 CLOSE √
PROT. Close L110 X160:83-85 CLOSE √
F11 LOAD REDUCTION PROT. Close L114 X160:87-89 CLOSE √
F11 MAGNETIC REDUCING Close L115 X160:91-93 CLOSE √
F11 FREQUENCY PROT. ALARM X171:13-14 CLOSE √
X172:13-14 CLOSE √
F11 UNBLANCED OVERCURRENT X171:15-16 CLOSE √
PROT. STAGE T1 ALARM X172:15-16 CLOSE √
F11 OVERLOAD ALARM X171:17-18 CLOSE √
X172:17-18 CLOSE √
F11 LOSS OF EXCITATION PROT. X171:19-20 CLOSE √
STATIC STEADY STAGE ALARM X172:19-20 CLOSE √
F11 FORWARD LOW POWER X171:21-22 CLOSE √

- 22 -
#1 Generator Protection System I Commissioning Report (10CHA01)

PROT. ALARM
F11 OVER EXCITATION PROT. 1 X171:23-24 CLOSE √
ALARM X172:23-24 CLOSE √
F11 LOSS OF SYNCHRONISM X171:25-26 CLOSE √
PROTECTION CHARACTERISTIC X172:25-26 CLOSE √
2 ALARM
F11 WATER CUT-OFF PROT. T1 X171:27-28 CLOSE √
ALARM X172:27-28 CLOSE √
F11 VT1 LINE BREAKAGE X171:29-30 CLOSE √
X172:29-30 CLOSE √
Close L116 X160:95-97 CLOSE √
F11 WINDING TEMP. HIGH X171:33-34 CLOSE √
X172:33-34 CLOSE √
F11 WINDING TEMP. HIGH-HIGH X171:35-36 CLOSE √
X172:35-36 CLOSE √
F12 REVERSE POWER PROT. X171:31-32 CLOSE √
ALARM X172:31-32 CLOSE √
F11 PROT. 1 7UM622 TRIP X170:11-12 CLOSE √
F12 PROT. 1 7UM611 TRIP X170:13-14 CLOSE √
PROT. SYSTEM FAULT X171:1-2 CLOSE √
X172:1-2 CLOSE √
PROT. SYSTEM 1 TRIP X171:5-6 CLOSE √
X172:5-6 CLOSE √
PROT. CABINET POWER BUS X171:3-4 CLOSE √
DISAPPEAR X172:3-4 CLOSE √

4.8 Reset button test


4.8.1 The red light H12 illumine if any fault on the protection system, off after the B10 reset button pressed.

Test result:OK

Section III: Conclusion

- 23 -
#1 Generator Protection System I Commissioning Report (10CHA01)

The conclusion of #1 Generator Protection System I (10CHA01) is as followings:OK

Commissioning: Commissioning Date:

- 24 -