Magnetic-pickups Transducers
Speed sensors Magnetic probes
Motion sensors, Timing probes
Pulse generators Monopoles
Frequency generators Pick-offs
Variable reluctance sensors
Figure 2: High Reluctance Position of Magnetic Circuit Figure 5: Steel Coarse Tooth Gear
A = Dimension of top tooth E = Clearance The example calculation first looks at the 3010 General
B = Height of tooth F = Gear thickness Purpose device.
C = Space between teeth G = VRS sensor
D = Diameter of pole piece
8.2. Calculate the minimum surface speed: 8.4. Consider the gear pitch/pole piece factor.
MIN SURFACE SPEED = 100 x 3.1 x 3.14 Table 3 shows that the output from a sensor having a 0.106”
60 dia. pole piece (3030 High Output) when sensing a 20 pitch
= 16.2 in/s
gear is 100%. Therefore, no correction factor is applied. The
output voltage remains at 3.078 Vp-p.
= 2.748 Vp-p
Figure 8. Equivalent Circuit All the variables that have an effect on the actual output
voltage at the lowest speed of interest have been considered,
and the 3030 High Output device has been found to be
appropriate.
8.6. Consider the Allowable Air Gap MAX FREQUENCY = MAX RPM x # OF GEAR TEETH
Air gap is also known as the pole piece clearance. In this 60
example, the air gap is 0.010 in. Figures 9 and 10 show that = 1000 x 60
60
the output of the 3030 High Output at 0.010 in is 60% of the = 1000 kHz
present value.
= 1 kHz
Figure 9. 3030 Output for Pole Pieces Less Than The 3030 High Output product specifications show a typical
0.187 in Dia. frequency response of 15 kHz. 1 kHz is obviously well within
this limit.
10.0 VRS Sensor General Notes Table 4. Recommended Max. Mounting Torques
All housings, unless otherwise noted, are 303 stainless steel. for Stainless Steel VRS Sensors:
Recommended cabling is twisted pair, shielded type. Thread Size ft-lb (max.) N m (max.)
All pole pieces are conical, except 0.187 in units, which are ¾ 27 36
straight, and chisel units, which are indicated where used. 5/8, M16 15 20
All sensors are designed to operate in moderate oil/fluid 3/8, M10 3 4
splash applications up to the rated temperature. For heavy ¼, M8 1 1.4
oil/fluid splash, immersion. or if any differential pressure 10/32 0.3 0.4
exists, sealed front end sensors are recommended.
If a VRS sensor is mounted completely surrounded by
ferrous metal, a 10% to 20% output voltage reduction may
occur.
Recommended max. mounting torques are given in Table 4.
WARNING WARNING
PERSONAL INJURY MISUSE OF DOCUMENTATION
DO NOT USE these products as safety or emergency stop The information presented in this application sheet is for
devices or in any other application where failure of the reference only. Do not use this document as a product
product could result in personal injury. installation guide.
Failure to comply with these instructions could result Complete installation, operation, and maintenance
in death or serious injury. information is provided in the instructions supplied with
each product.
Failure to comply with these instructions could result in
WARRANTY/REMEDY
death or serious injury.
Honeywell warrants goods of its manufacture as being free of
defective materials and faulty workmanship. Honeywell’s
standard product warranty applies unless agreed to otherwise SALES AND SERVICE
by Honeywell in writing; please refer to your order Honeywell serves its customers through a worldwide network
acknowledgement or consult your local sales office for specific of sales offices, representatives and distributors. For
warranty details. If warranted goods are returned to Honeywell application assistance, current specifications, pricing or name
during the period of coverage, Honeywell will repair or replace, of the nearest Authorized Distributor, contact your local sales
at its option, without charge those items it finds defective. The office or:
foregoing is buyer’s sole remedy and is in lieu of all other
warranties, expressed or implied, including those of E-mail: info.sc@honeywell.com
merchantability and fitness for a particular purpose. In no
event shall Honeywell be liable for consequential, special, Internet: www.honeywell.com/sensing
or indirect damages.
Phone and Fax:
While we provide application assistance personally, through Asia Pacific +65 6355-2828; +65 6445-3033 Fax
our literature and the Honeywell web site, it is up to the Europe +44 (0) 1698 481481; +44 (0)
customer to determine the suitability of the product in the 1698 481676 Fax
application. Latin America +1-305-805-8188; +1-305-883-8257 Fax
USA/Canada +1-800-537-6945; +1-815-235-6847
Specifications may change without notice. The information we +1-815-235-6545 Fax
supply is believed to be accurate and reliable as of this
printing. However, we assume no responsibility for its use