Check +220V DC to I -13, -220V to I -15, then close ZK & turn the switch DTK to Auto
verify whether the synchronizer is electrified or not. Turn the switch DTK to Manual
3 Check D.C circuit verify whether the synchroscope is electrified or nor not.
Turn the switch DTK to Auto then open ZK , check +110 V / 50 HZ to I-1 -110V / 50 HZ
to I-3 then close ZK , check that the synchroscope stops at 12 0'clock after synchronizer
4 Check 3 φ sequence ( Auto ) Position electrified
Turn the switch DTK to Manual check that the Synchroscope TBB stops at 12 o' Clock
5 Check 3 φ sequence ( Manual ) Position after the synchroscope electrified
Allowable freq diff -= +- 0.15 HZ, Allowable Volt Diff. = +- 5%, allowable angle diff. = 20
6 SID -2AS device ( phase angle ) 30 degree degree
Resistance between
Check record of #1 IPRC controllable Silicon 1 K & G electrode
Check record of #2 IPRC controllable Silicon 1
Check record of #3 IPRC controllable Silicon 1
Fan Check I/P VOLTS Fan running
Winds blows right position check Two way power supply check Switchover to normal
( Check record of #1 IPRC Fan 1, ) Fan Power
supply I - 11FDK
Fan Power supply I - 12FDK
( Check record of #1 IPRC Fan 2) Fan Power supply
I - 21FDK
Fan Power supply I - 22FDK
Check record of #1 IPRC Fan 3 Fan Power supply I
- 31FDK
Fan Power supply I - 32FDK
Energization check
Each channel energization initialization check of
regulator cubicle
Digital Signal Check of Regulator
Item Condition Relay Position ECU I/P bit
AVR A AVR B
Technique request :- accord with product technical requirement relay action , auxiliary contact position , ECU display are correct , this cabinet "
Cimmissioning position " should put PN location when check binary output loop of regulator cabinet, click DO test " on the AVR state " interface of
ECU , in tern check binary O/P loop.
Relay & indicator light
Item Condition position ECU O/P bit indication
AVR A AVR B
KO1 action 1 HD
1 Function Normal AVR hardware normal LIGHTING
2 Off - Normal alarm ECU alarm 2 HD lighting
KO2 action 3 LD
3 Set A in effect A set is master LIGHTING
Check Generator
transformer Unit 2 2
differential current Multimeter, Megger, ma Screw driver Set, Box spanner set, D &
6 Generator Transformer correct. meter ring Spanner set
388.2 MVA, 330MW, 0.85 lagging , 24 kV, 9339A, 98.8% η, Generator Synchronising before activities
Disconnect 6.9kV
busbar room temporary 2 2
excitation power switch,
make short -circuit point
K2 grounding , for safety
measures demolished
K2 short - Circuit point Multimeter, Megger, ma Screw driver Set, Box spanner set, D &
8 Excitation system back to normal wiring. meter ring Spanner set
Recover the short CT of 2 2
9 Switchyard switchyard
Generator 3 Phase short Circuit test (K3, K4 point )
3
388.2 MVA, 330MW, 0.85 lagging , 24 kV, 9339A, 98.8% η, Generator Synchronising before activities
4
Generator No-load test
Put into
synchronization, check 2 2
that the correct
synchronization device,
synchronous table
pointer instructions Phase sequence tester,
7 Synchronising Panel "12 " position. multimeter
Check MT secondary 2 2
side TV4 and MT
primary side TV phase
3 Generator CT sequence correct.
Close the FCB switch,
rise generation voltage 2 2
4 Field circuit breaker to rated Multimeter Screw driver set, Plier, Wire Stripper
Check generator
protection has been put 2 2
into correctly in
accordance with setting Manuals, relay settings, Drawings,
1 GRP value table Screw driver sets,
DCS 2 2
Through the automatic
quasi-synchronization
4 device to synchronize.
Generator load test
13 Check Parameter
Active Power (MW) 330 Field Voltage (V) 542
P.F 0.85 Field Current (A) 2495
Stator Vtg (kV) 24 Grid Vtg (KV) 400
Stator Current (A) 9339
14 Set A DI
Inc. Excitation FCR ON
DCR Excitation M/S Switch
FMK Open Protect ON
Sync. BK. Open Debug
Start up Current Dist ON
De- Excitation Const. MVar ON
Signal Reset Const. PF ON
PSS ON Define Set -A
15 Set B DI
Inc. Excitation FCR ON
DCR Excitation M/S Switch
FMK Open Protect ON
Sync. BK. Open Debug
Start up Current Dist ON
De- Excitation Const. MVar ON
Signal Reset Const. PF ON
PSS ON Define Set -B
16 Set A DO Set B DO
Run Run
Flashing ON Flashing ON
18 3rd IPRC
Indication Working
Pulse POW
Fault
ICD Good
Switch Fan Operation
Pulse Pow
Self Run
19 Field Discharge Cubicle Field Discharge Resistor Cubicle
Oper POW Flashing POW
Close POW Over Volt
Closing OV Rest
Trip
Manual trip
FMK
21 GRP A GRP B
Trip Check
Checked By :
inspection Date :