Documente Academic
Documente Profesional
Documente Cultură
System
Hardware Description 7 Power Boards
7 Power Boards
This chapter describes the power boards that the OptiX OSN 500 supports.
7.1 UPM
The uninterruptible power module (UPM) consists of a power box and storage batteries. It
provides access to 110 V/220 V AC mains power supplies.
7.2 PIU
The PIU is a power interface board, which receives two -48 V/-60 V DC power supplies.
7.1 UPM
The uninterruptible power module (UPM) consists of a power box and storage batteries. It
provides access to 110 V/220 V AC mains power supplies.
NOTE
The management module of the UPM is the CAU. On the U2000, you only need to configure the CAU.
The UPM power system consists of the GIE4805S power system (converting the 110 V/220 V
power into the -48 V power) and storage batteries. The output power of a single GIE4805S
power system is 340 W. The GIE4805S power system is 1U high. Figure 7-1 shows the
appearance of the GIE4805S power system.
5S
80
E4
GI
Function Board
and
Feature
Dual hot The power conversion part of the UPM adopts the hot backup design by
backup using two AC/DC rectifier modules. The two rectifier modules can work
function simultaneously and share the load. If one rectifier module fails, the other
rectifier module immediately bears all the load. In this case, the services
running on the equipment are not affected, which improves the stability of
the system.
Hot- The AC/DC rectifier module of the UPM is hot-swappable. When you
swappable replace a faulty rectifier module, the other rectifier module can still work
function normally. Therefore, the maintainability of the system is improved.
Storage The UPM provides the storage battery protection function. When the mains
battery supply is interrupted, the power system of the equipment automatically
protection switches to the storage battery, which ensures that the equipment operates
function normally. If the storage battery uses the 12AH module, it can supply power
for three to four hours.
Monitoring The UPM provides the monitoring module and the NM monitoring
function function. The monitoring module monitors and controls the rectifier
module, AC power distribution, DC power distribution, and parameters and
status of the battery group in real time. The monitoring module also reports
the collected information to the transmission NMS in real time. The storage
battery realizes float charging and current limiting.
The UPM consists of the rectifier module and the monitoring module. Figure 7-2 shows the
block diagram of the UPM.
100V/220V AC -48V DC
Rectifier module
PIU
Monitoring module
System control
unit
Rectifier Module
The rectifier module converts the 110 V/220 V AC mains power supply into -48 V DC
voltage required by the transmission equipment.
Monitoring Module
When the UPM works normally, the monitoring module controls the rectifier module, storage
battery loop, and load loop, which work according to the preset parameters or user settings.
The monitoring module also monitors the status and data of the rectifier module, storage
battery loop, and load loop.
In the case of a mains supply failure, the equipment is fed by the storage battery group that is
connected to the UPM. The battery group must be connected to the UPM before the mains
supply fails. When the batteries start to discharge due to a mains supply failure, the
monitoring module reports the no-mains-supply alarm. With the discharge of the batteries, the
battery voltage starts to drop. When the battery voltage is lower than 45 V, the monitoring
module reports the DC undervoltage alarm. When the battery voltage reaches 43 V, the
battery group enables the power-off protection function to interrupt the connection between
the battery group and the equipment. As a result, the batteries are automatically protected.
When the mains supply is restored, the UPM resumes normal operations.
48V+
48V-
LOAD1 LOAD2
5 6
1 2 3
Indicators
The front panel of the rectifier module on the left of the UPM has the following indicators:
The front panel of the monitoring module on the top panel of the UPM has the following
indicators:
For the meanings of the status of the indicators, see 13 Indicator Status Explanation.
Ports
The front panel of the GIE4805S has four interfaces. Table 7-2 describes the types and usage
of the interfaces of the GIE4805S.
AC100-240 Power It is the AC mains input socket for accessing 110 V/220
interface V AC power.
Red on/off Button It is on the right side of the front panel of the rectifier
button module. You can enable or disable the rectifier module
by pressing the button.
RS-232 RS-232 The UPM communicates with the SCC through this
communicatio interface so that the UPM can report alarms to the SCC
n interface and the SCC can control the UPM remotely.
The RS-232 serial port of power system is connected to
the NMS/COM port of the OptiX OSN equipment to
enable the NMS to monitor the battery group and the
connected power system.
Power output Power Three power output interfaces are on the rightmost side
interface interface of the power system. The interface at the top is the
battery interface, through which the power system is
connected to the battery input socket at the back of the
storage battery box through a battery cable. The other
two interfaces are the load interfaces and can supply
power to the OptiX OSN equipment by using power
cables.
Table 7-3 provides the pin assignments of the RS-232 serial port.
Table 7-4 and Table 7-5lists the technical specifications of the UPM.
Item Performance
Weight < 10 kg
Parameter Value
Rated output current 8 A (two load outputs with each current not more than
5 A)
Parameter Value
7.2 PIU
The PIU is a power interface board, which receives two -48 V/-60 V DC power supplies.
Table 7-6 lists the functions and features that the PIU supports.
Basic functions Power access One PIU is provided and the PIU receives two -48 V
DC or -60 V DC power inputs.
Maximum 5A
current
Power output The PIU provides other boards with -48 V power.
Surge Supported
protection
-48V/-60V Protection
-48 V 1 Board operating in distributed
and detection EMI filtering unit
unit power supply mode
-48V/-60V Protection
-48 V 2 Board operating in distributed
and detection EMI filtering unit
unit power supply mode
Detection
Detection signal System control and
signal communication unit
Communication
control unit
+3.3V
Indicators
The front panel of the PIU has the following indicators: PWRA and PWRB. For status
explanation for the indicators, see 13 Indicator Status Explanation.
Ports
The PIU receives two power supplies. Table 7-7 lists the types of the ports on the PIU and
their respective usage.
Labels
Power caution label: instructs you to read related instructions before performing any power-
related tasks.
Do not remove or install a PIU while the equipment is being powered on. That is, turn off all
the power supplies to the PIU before removing or installing it.
Weight 0.18 kg