The software and hardware described in this document is furnished under a license and
may be used or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Inc.
1021 Main Campus Drive
Raleigh, NC 27606, USA
Toll Free: 1-800-HELP-365, menu option #8
ABB Inc.
3450 Harvester Road
Burlington, ON L7N 3W5, Canada
Toll Free: 1-800-HELP-365, menu option #8
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standards EN 50263 and EN 60255-26 for the EMC directive, and with the product
standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series and
ANSI C37.90.
Table of contents
Table of contents
Section 1 General..................................................................................3
Definitions.................................................................................................4
Section 10 Control.................................................................................29
Section 11 Logic....................................................................................31
Section 12 Monitoring............................................................................33
Section 13 Metering..............................................................................37
Section 16 Hardware.............................................................................43
IED..........................................................................................................43
Connection system.................................................................................43
1
Type test certificate
Table of contents
2
Type test certificate
1MRK505212-TUS D Section 1
General
Section 1 General
This document certifies that the product described below is in accordance with, and
conforms to the data stated in this Type Test Certificate and corresponding data in the
Type Test Report and Product Guide.
The product has been tested according to relevant parts of the standards stated below.
3
Type test certificate
Section 1 1MRK505212-TUS D
General
1.2 Definitions
Reference value
The specified value of an influencing factor to which are referred the characteristics of
the equipment.
Nominal range
The range of values of an influencing quantity (factor) within which, under specified
conditions, the equipment meets the specified requirements.
Operative range
The range of values of a given energizing quantity for which the equipment, under
specified conditions, is able to perform its intended functions according to the specified
requirements.
4
Type test certificate
1MRK505212-TUS D Section 2
Energizing quantities, rated values and limits
Table 1: TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity Rated value Nominal range
Current In = 1 or 5 A (0.2-40) × In
5
Type test certificate
Section 2 1MRK505212-TUS D
Energizing quantities, rated values and limits
6
Type test certificate
1MRK505212-TUS D Section 2
Energizing quantities, rated values and limits
Table 6: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V RL ± 20%
48/60 V RL ± 20%
125 V RL ± 20%
220/250 V RL ± 20%
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
7
Type test certificate
Section 2 1MRK505212-TUS D
Energizing quantities, rated values and limits
Table 8: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed
relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V DC
Test voltage across open contact, 1 min 1000 V rms 800 V DC
Current carrying capacity
Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, continuous 12 A 12 A
Making capacity at inductive load with
L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Making capacity at resistive load
220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
Breaking capacity for DC with L/R < 48 V/1 A 48 V/1 A
40 ms 110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
8
Type test certificate
1MRK505212-TUS D Section 2
Energizing quantities, rated values and limits
Table 9: IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC
61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed
relay)
Binary outputs IOM: 10 IOM: 2
Max system voltage 250 V AC, DC 250 V DC
Test voltage across open 250 V rms 250 V rms
contact, 1 min
Current carrying capacity
Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, 12 A 12 A
continuous
Making capacity at inductive
loadwith L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Making capacity at resistive load
220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos 250 V/8.0 A 250 V/8.0 A
j>0.4
Breaking capacity for DC with L/ 48 V/1 A 48 V/1 A
R < 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
9
Type test certificate
Section 2 1MRK505212-TUS D
Energizing quantities, rated values and limits
Table 10: SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity Static binary output trip
Rated voltage 48 - 60 VDC 110 - 250 VDC
Number of outputs 6 6
Impedance open state ~300 kΩ ~810 kΩ
Test voltage across open contact, 1 No galvanic separation No galvanic separation
min
Current carrying capacity:
Continuous 5A 5A
1.0s 10A 10A
Making capacity at capacitive load
with the maximum capacitance of
0.2 μF :
0.2s 30A 30A
1.0s 10A 10A
Breaking capacity for DC with L/R ≤ 48V / 1A 110V / 0.4A
40ms
60V / 0.75A 125V / 0.35A
220V / 0.2A
250V / 0.15A
Operating time <1ms <1ms
Table 11: SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical
relay outputs
Function of quantity Trip and signal relays
Max system voltage 250V AC/DC
Number of outputs 6
Test voltage across open contact, 1 min 1000V rms
Current carrying capacity:
Continuous 8A
1.0s 10A
Making capacity at capacitive load with the
maximum capacitance of 0.2 μF:
0.2s 30A
1.0s 10A
Breaking capacity for DC with L/R ≤ 40ms 48V / 1A
110V / 0.4A
Table continues on next page
10
Type test certificate
1MRK505212-TUS D Section 2
Energizing quantities, rated values and limits
Table 12: BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Per relay, continuous 8A
Per relay, 1 s 10 A
Per process connector pin, continuous 12 A
Making capacity at inductive load with L/R>10 ms
0.2 s 30 A
1.0 s 10 A
Breaking capacity for AC, cos j>0.4 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
11
Type test certificate
Section 2 1MRK505212-TUS D
Energizing quantities, rated values and limits
90-250 V DC ± 20%
Interruption
interval
0–50 ms No restart
0–∞ s Correct behaviour
at power down
Restart time <300 s
12
Type test certificate
1MRK505212-TUS D Section 3
Type tests according to standards
13
Type test certificate
Section 3 1MRK505212-TUS D
Type tests according to standards
14
Type test certificate
1MRK505212-TUS D Section 4
Differential protection
15
Type test certificate
16
1MRK505212-TUS D Section 5
Current protection
Table 23: Four step single phase overcurrent protection PH4SPTOC (51)
Function Setting range Accuracy
Operate current (1-2500)% of lbase ± 1.0% of In at I £ In
± 1.0% of I at I > In
17
Type test certificate
Section 5 1MRK505212-TUS D
Current protection
Table 24: Thermal overload protection, two time constants TRPTTR (49)
Function Range or value Accuracy
Base current 1 and 2 (30–250)% of IBase ± 1.0% of In
Operate time: Ip = load current before overload IEC 60255–8, ±5% + 200 ms
occurs
æ I 2 - I p2 ö Time constant τ = (1–500)
t = t × ln ç 2 ÷ minutes
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 1)
I = Imeasured
Alarm pickup 1 and 2 (50–99)% of heat content trip ± 2.0% of heat content trip
value
Operate current (50–250)% of IBase ± 1.0% of In
Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip
18
Type test certificate
1MRK505212-TUS D Section 5
Current protection
Table 26: Breaker failure protection, single phase version CCSRBRF (50BF)
Function Range or value Accuracy
Operate phase current (5-200)% of lBase ± 1.0% of In at I £ In
± 1.0% of I at I > In
19
Type test certificate
Section 5 1MRK505212-TUS D
Current protection
20
Type test certificate
1MRK505212-TUS D Section 6
Voltage protection
21
Type test certificate
Section 6 1MRK505212-TUS D
Voltage protection
22
Type test certificate
1MRK505212-TUS D Section 7
Frequency protection
VMin=(50-150)% of Vbase
Exponent=0.0-5.0
t_MaxTripDelay=(0.000-60.000
)s
t_MinTripDelay=(0.000-60.000)
s
Exponent
é V - VMin ù
ëVNom - VMin úû
t=ê
EQUATION1559 V1 EN (Equation 2)
V=Vmeasured
23
Type test certificate
Section 7 1MRK505212-TUS D
Frequency protection
24
Type test certificate
1MRK505212-TUS D Section 8
Multipurpose protection
25
Type test certificate
Section 8 1MRK505212-TUS D
Multipurpose protection
26
Type test certificate
1MRK505212-TUS D Section 9
Secondary system supervision
27
Type test certificate
28
1MRK505212-TUS D Section 10
Control
Section 10 Control
29
Type test certificate
30
1MRK505212-TUS D Section 11
Logic
Section 11 Logic
31
Type test certificate
32
1MRK505212-TUS D Section 12
Monitoring
Section 12 Monitoring
33
Type test certificate
Section 12 1MRK505212-TUS D
Monitoring
34
Type test certificate
1MRK505212-TUS D Section 12
Monitoring
35
Type test certificate
36
1MRK505212-TUS D Section 13
Metering
Section 13 Metering
37
Type test certificate
38
1MRK505212-TUS D Section 14
Station communication
39
Type test certificate
Section 14 1MRK505212-TUS D
Station communication
Table 60: IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
Protocol IEC 61850-8-1
Communication speed 100 Base-FX
40
Type test certificate
1MRK505212-TUS D Section 15
Remote communication
41
Type test certificate
42
1MRK505212-TUS D Section 16
Hardware
Section 16 Hardware
16.1 IED
Table 63: Water and dust protection level according to IEC 60529
43
Type test certificate
Section 16 1MRK505212-TUS D
Hardware
44
Type test certificate
1MRK505212-TUS D Section 17
Basic IED functions
45
Type test certificate
Section 17 1MRK505212-TUS D
Basic IED functions
46
Type test certificate
1MRK505212-TUS D Section 18
Inverse characteristics
æ A ö
t = ç P + B ÷ × td
ç ( I - 1) ÷
è ø
EQUATION1651 V1 EN
Reset characteristic:
tr
t = × td
(I 2
-1 )
EQUATION1652 V1 EN
I = Imeasured/Iset
47
Type test certificate
Section 18 1MRK505212-TUS D
Inverse characteristics
æ A ö
t = ç P ÷ × td
ç ( I - 1) ÷
è ø
EQUATION1653 V1 EN
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10
ms
IEC Normal Inverse A=0.14, P=0.02 IEC 60255-151, 5% + 40
ms
IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Programmable characteristic td = (0.05-999) in steps of 0.01
Operate characteristic: A=(0.005-200.000) in steps of
0.001
æ A ö B=(0.00-20.00) in steps of 0.01
t = ç P + B ÷ × td C=(0.1-10.0) in steps of 0.1
ç (I - C ) ÷ P=(0.005-3.000) in steps of 0.001
è ø
TR=(0.005-100.000) in steps of
EQUATION1654 V1 EN
0.001
Reset characteristic: CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of
TR 0.001
t = × td
(I PR
- CR )
EQUATION1655 V1 EN
I = Imeasured/Iset
48
Type test certificate
1MRK505212-TUS D Section 18
Inverse characteristics
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è td ø
EQUATION1657 V1 EN
I = Imeasured/Iset
49
Type test certificate
Section 18 1MRK505212-TUS D
Inverse characteristics
V = Vmeasured
50
Type test certificate
1MRK505212-TUS D Section 18
Inverse characteristics
V = Vmeasured
V = Vmeasured
51
Type test certificate
Section 18 1MRK505212-TUS D
Inverse characteristics
V = Vmeasured
52
Type test certificate
53