Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 1 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
LB-II
Installation Parameters
Document Revision :
Copyright 1996, OTIS GmbH Berlin. No part of this document may be copied or reproduced
in any form or by any means without the prior written consent of OTIS GmbH.
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 2 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
Address Descripiton
F Drive Selection
43 DOH, ARBL,
44 ATT, REV
46 ERO Function
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 3 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
Explanation:
Display at the 7 - segment Display
on the board
C-NT
7-Segment- Time
display Dec. HEX Data (sec) Door times Default
Service Tool
0 0
0 0 1 1 Doortime Car 2
C-NT 2 2
3 3
1 1 4 4 Doortime Hall 4
H-NT 5 5
6 6
7 7 Time for door reversal relay,
2 2 8 8 0...3s in steps of 200ms 0
REV-T 9 9
A 10
B 11
3 3 C 12 Car -call has preference 0
CCP-T D 13 up to 15 sec.
E 14
F 15
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 4 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
7-Segment- En-
display trance
Service Tool Dec. HEX Data Position Indications Default
5 5 1-F 2 - 16 Top Position
TOP
6 6 Position of Lobby
LOBBY
0-F 1 - 16
7 7 Bottom Position
BOT
Installation Parameters
Software - Version 1.x
7-Segment- En-
display Dec. HEX Data trance Position Indications Default
Service Tool
Installation Parameters
Software - Version 1.x
flashing Address Function
7- Segment-
display Dec. HEX Data DCL or FCL Default
Service Tool
0 FCL
F Hydraulic
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 7 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
flashing Address Function
7- Segment-
display Dec. HEX Data Simplex / Duplex, Frequency (Power) Default
Service Tool
0 Simplex, 50 Hz
1 Simplex, 60 Hz
0 XEPO
0 XEFO, XEFS
Installation Parameters
Software - Version 1.x
Function Emergency Stop / DRR / SC / DPPL
1 ESB
5 ESB and SC
ES.. 8 ESS
9 ESB
C ESS and SC
D ESB and SC
Installation Parameters
Software - Version 1.x
Funtion
flashing Address
7-Segment-
display Dec. HEX Data PKS / CTL / DCB / LWO Default
Service Tool
0 X ( PKS, CTL, DCB, LWO )
1 PKS
2 CTL
4 DCB
PKS.. 8 LWO
Installation Parameters
Software - Version 1.x
Function
CHCS on ISS - Input
flashing Address Multilight board / PMO / FLSH
7-Segment- PMO - Lightray device with monitor
display Dec. HEX Data FLSH - Flashing IL / TTL during running Default
Service Tool
0 X ( FLSH, PMO, MLB, CHCS (ISS))
1 MLB
2 FLSH
4 PMO
9 MLB
A FLSH
Installation Parameters
Software - Version 1.x
flashing Address Function
7-Segment-
display Dec. HEX Data Type of door Default
Service Tool
0 ACG / DCP=10sec / X (ADO
1 FLH / DCP=10sec / X (ADO)
2 TLD/CLD / DCP=10sec / ADO
4 ACG ( Automatical car door and 10s pro-
tection time for door closing DCP
5 FLH (Swing doors) and 10s protection time
for DC - relais (cam magnet)
22 16 6 TLD / CLD and DCP without nudging,
limited door reversal and door detector
DOOR 8 ACG / NO DCP / X (ADO)
A TLD/CLD / NO DCP / EDPWITH LDR /
NUDGING / X (ADO)
C ACG ( Automatical car door ) without pro-
tection time for door closing
E TLD / CLD and EDP with LDR and nudging
without DCP
4 GAMMA S, 2ND IP
8 GAMMA S, 1ST IP
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 13 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
Installation Parameters
Software - Version 1.x
2 Position 1 disabled
4 Position 2 disabled
1 Position 4 disabled
2 Position 5 disabled
4 Position 6 disabled
Installation Parameters
Software - Version 1.x
flashing Address Function
7-Segment- Parking enabled or disabled,
display Dec. HEX Data internal position from 8 to 11 Default
0 All position parking enabled ( 8, 9, 10, 11 )
1 Position 8 disabled
2 Position 9 disabled
4 Position 10 disabled
Installation Parameters
Software - Version 1.x
flashing Address Function
7-Segment- Parking enabled or disabled,
display Dec. HEX Data internal position from 12 to 15 Default
Service Tool
0 All position parking enabled ( 12, 13, 14, 15 )
1 Position 12 disabled
2 Position 13 disabled
4 Position 14 disabled
Installation Parameters
Software - Version 1.x
Function
flashing Address
7-Segment-
display Dec. HEX Data For Eng. - Service only Default
Service Tool
0 Normal Operation 0
Function
flashing Address
7-Segment- Timer 1A
display Dec. HEX Data Default
Service Tool
Delay for 1A Relay
30 1E 0 - F ( 0... 3 sec) decelaration in steps of 200ms
1A-T
Function
flashing Address
7-Segment- Timer 2A
display Dec. HEX Data Default
Service Tool
Delay for 2A relay
31 1F 0 - F ( 0... 3 sec) decelaration in steps of 200ms
2A-T
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 19 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
flashing Address Function
7-Segment-
display Dec. HEX Data Landing Masks, Positionincrements Default
Service Tool
32 20 0 Landing enabled 0
POS00
33 21 1 LE Position +1
POS01
34 22 2 LE Position +2
POS02
35 23 3 LE Position +3
POS03
36 24 4 LE Position +4
POS04
37 25 5 LE Position +5
POS05
38 26 6 LE Position +6
POS06
39 27 7 LE Position +7
POS07
40 28 8 Landing disabled
POS08
41 29 9 LE Position -1
POS09
42 2A A LE Position -2
POS10
43 2B B LE Position -3
POS11
44 2C C LE Position -4
POS12
45 2D D LE Position -5
POS13
46 2E E LE Position -6
POS14
47 2F F LE Position -7
POS15
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 20 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
The addresses HEX 20 to 2F are for programming the position indicator when differ from the
internal counting, for example the values 1 to 7 when the display should show a higher num-
ber than the internal counting or 9 to F when the wanted display number is lower than the
internal one.
(see examples for Programming)
Attention! When using a Multi Light Board the calculation has to be done from the
wanted display number to the continuous display is wanted the addresse
HEX 20 to 2F have to be programmed with a 0 value.
see ” MLB, Multi Light Board” and ” Fixing of Indication for lowest Landing when using MLB”.
The value 8 can be choosen only to disable a landing, see description of ” Number of Calls
and Tell Tale Lights”.
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 21 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
Function
flashing Address
7-Segment-
display Dec. HEX Data Error / Warning Numbers
48 30 0-F Eldest error or warning number
: Inspection
In order to enter immediately into address 30 switch S3 twice within 2 seconds from position
2 to 1.
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 22 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
Function
flashing Address
7-Segment-
display Dec. HEX Data Time passed since latest error occured
52 34 0 - F Value X 45 h 30’40,0” ( 163840,0” )
Function
flashing Address
7-Segment-
display Dec. HEX Data Version Identification
Service Tool
57 39 0 - F Number of version
58 3A 0 - F Number of revision
EDDP 2 +20
3 +30
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 23 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Installation Parameters
Software - Version 1.x
Function Changed door functions at parking mode,
internal positions from 0 to 3
flashing Address Type ACG = Parking with closed door
7-Segment- Types CLD/TLD = parking with opened door
display Dec. HEX Data
Service Tool
0 All positions same door functions ( 0, 1, 2, 3)
1 Position 0 changed
2 Position 1 changed
4 Position 2 changed
Installation Parameters
Software - Version 1.x
Function Changed door functions at parking mode,
internal positions from 4 to 7
flashing Address Type ACG = Parking with closed door
7-Segment- Types CLD/TLD = parking with opened door
display Dec. HEX Data
Service Tool
0 All positions same door functions ( 4, 5, 6, 7)
1 Position 4 changed
2 Position 5 changed
4 Position 6 changed
Installation Parameters
Software - Version 1.x
Function Changed door functions at parking mode,
internal positions from 8 to 11
flashing Address Type ACG = Parking with closed door
7-Segment- Types CLD/TLD = parking with opened door
display Dec. HEX Data
Service Tool
0 All positions same door functions ( 8, 9, 10, 11)
1 Position 8 changed
2 Position 9 changed
4 Position 10 changed
Installation Parameters
Software - Version 1.x
Function Changed door functions at parking mode,
internal positions from 12 to 15
flashing Address Type ACG = Parking with closed door
7-Segment- Types CLD/TLD = parking with opened door
display Dec. HEX Data
Service Tool
0 All positions same door functions ( 12, 13, 14, 15)
1 Position 12 changed
2 Position 13 changed
4 Position 14 changed
Installation Parameters
Software - Version 1.x
flashing Address Function
7-Segment-
display Dec. HEX Data
Service
Tool
64 40 ASN / J Phase Relay
J
65 41 0 Brake Current Device
BCD 1
66 42 Motor Protection Device
MPD
Installation Parameters
Software - Version 1.x
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 28 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Programming - Examples
- Number of stops 8
- Number of basements 1
6.Floor 6 7 27 9
5.Floor 5 6 26 9
4.Floor 4 5 25 9
3.Floor 3 4 24 9
2.Floor 2 3 23 9
1.Floor 1 2 22 9
Ground floor 0 1 21 9
Basement -1 0 20 9
Now the position indicator is to be programmed by setting the ”LANDING MASKS” (see be-
low) taking the internal numbering as a basis which always starts with zero (”0”).
Exception:
The following notes are the conditions to program the position indicator :
-- Power on
-- The push button S2 must be pressed repeatly until the hexaDec. address 20
(equivalent Dec. 32)appears on the seven segment display of the logic board.
The segments and flash alternately, see also chapter : programming of parame
ters.
-- Pressing the push button S1 once results in a change of the display from addresses to
data, a non flashing now is shown.
-- Now the switch S2 must be pressed repeatedly again until the required value appears, in
this example a .
-- Pressing the switch S1 once will then terminate the programming sequence of the lowest
position indication.
The hexadecimal. form of the address 20 will appear ( and alternating ).
After this processor internal position is related to the required position indication.
-- Pressing the push button S2 once will display the hexaDec. address 21
( equivalent Dec. 32 ) on the seven segment display of the logic board.
( and flash alternately ) .
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 31 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
-- Pushing the switch S1 will store this number under the address that appears again, now
on the flashing display.
In this example the hexaDec. address 21 is displayed.
A and flashing alternately on the seven segment display.
Remark :
In this example the difference between the processor internal numbering and the requiered
position indication was always ” - 1 ” ( see table below ).
- Number of stops 9
- Number of aements 2
- HexaDec. addresses 20, 21, 22, 23, 24, 25, 26, 27, 28
The above table shows that the difference is not always the same for every landing, which
means that every hexaDec. addresss contains a different data.
As the difference is 0, no data must be programmed and the next hexaDec. address (24) can
be selected right away.
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 34 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
If the default value of 2 seconds door time on car call is to be changed to 4 seconds for
instance, the procedure described below must be carried out:
Conditions are
The seven segment display of the logic board shows the flashing HEX-address .
- Pressing the push buton S1 once results in a change from the flashing display of the
address to the non flashing display of the memory content, a in this example.
Remark:
The door open time can be programmed from 0 to 15 seconds in steps of 1 second.
See table below.
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 35 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
Table
Required 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
time in
seconds
Data
to be
programmed
Address Doortime on car call
0
1 Doortime on hall call
2 Door Reversal Time REV-T not programming in seconds
3 Preference given on car call
OTIS
Part: 4 - AA3
FIELD COMPONENT MANUAL No.: GAA21230FVIIIa
European and Transcontinental
Vintage: 02/1
Operations
Page: 36 / 37
PRODUCT LB-II
Date: 12-NOV-96
ADMINISTRATION List of Installation Parameters
The default value for the doortime on hall call is 4 seconds. If this time is to be altered
according to different requirements in the building ( for instance old peoples home) the
procedure described below must be carried out.
Conditions are
- A functional test of the installation is positive
The seven segment displayof the logic board shows the flashing HEX-address
- Push button S2 once to change from the address to the hexaDec. address
- Push button S2 six times to increment the memory content to the value
which will then be displayed.
Table
Memory
contents
Landings 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
HEX-Address Functions
Example:
For an elevator with eight landings the memory content must be programmed at the
HEX-address 5 with the value (see table)
Note: