Documente Academic
Documente Profesional
Documente Cultură
SYSTEM EVACUATION
If, as an example, we were to ascend to an reduce bearing clearances and can cause
altitude of 3048 metres above mean sea close tolerance sliding components to
level, the atmospheric pressure exerted on stick, or seize. Acids present may also
us would now be less, at 67 000 Pascals, or attack the insulation of motor windings,
670 mBar. etc., leading to the electrical burnout of
hermetic compressor motors.
liquid line filter / drier cores, and may There is a common mistake that can be
also be circulated around the lubrication made during system service, whereby
circuit, having displaced the oil. This is chilled water is allowed to continue to
possibly the worst system scenario, and flow through the evaporator of a system
the main subject of this Service Technique with a refrigerant circuit open to
Bulletin. atmospheric pressure. As the chilled
water temperature is likely to be below
the dew point temperature of the plant
3. THE ELIMINATION OF MOISTURE FROM room, large amounts of water can
A SYSTEM condense on the inside of the refrigerant
circuit, compounding an already difficult
This section is deliberately not called task. Remember to valve-off the water
"EVACUATION", as the first action taken by flow to the chiller worked on!
some service engineers, to remove system
moisture, is to connect a vacuum pump. The identification of the leakage is
Let us first reflect on our diagnosis of the extremely important, as to evacuate a
presence of moisture. system with a leakage still evident will
allow the further ingress of air, moisture,
• On internal inspection, is there a and possibly quantities of water, if the
physical presence of water within the leakage was at a water chiller evaporator,
system in the form of droplets, or or water-cooled condenser. Evacuation of
puddles?!! moisture from a system will only be
effective where only small amounts of free
• Has the presence of moisture affected moisture exist - that is, moisture present
the flow of refrigerant, during in the vapour-state. If large quantities of
operation? liquid water are present within the system,
preliminary works to remove this water
• Or is there evidence of the presence of will need be in place before a vacuum
moisture through the colour change of pump is put anywhere near the serviced
a moisture indicator, oil analysis, plant.
copper plating, sludge, etc.?
If we take for our example a leakage to
Small amounts of free moisture may simply the evaporator of a water-cooled,
be removed from a system by the repeated packaged water chiller, it may be common
replacement of liquid line drier cores and for the water-side pressure of the vessel to
compressor oil charge. Simple, if the cause exceed the refrigerant-side pressure. Once
was previously sloppy service work. the refrigerant pressure, through leakage,
Sometimes, however, experience provides falls to and below the water-side pressure,
some cynicism, and the moisture may be the system will fill with water - a truly
present from a more sinister source. catastrophic event, especially where the
Where a heat-exchanger has been compressor continues to operate as the
suspected as leaking due to the moisture low-pressure safety control, if set too low,
content of the system, or where larger may not trip due to the water pressure.
quantities of water are found to be
present, the refrigerant and oil charges This type of failure would require each
must first be removed, by qualified individual major component of the system
personnel and to mandatory procedures, to be disconnected and treated separately.
for disposal. The water-side of each heat The compressor would obviously undergo a
exchanger must first be drained, the complete strip-down, cleaning and drying
system then leakage pressure tested to process, paying particular attention to
trace the point(s) of leakage. Remember; blowing-through and clearing all oil
there may be more than one. passageways and unit capillary lines with
Oxygen-free, dry Nitrogen. The motor
would require more specialist attention.
Figure 4 – Condenser moisture removal using hot-air drier and nitrogen purging
or too quick a reduction of system system allows for greater efficiency of the
pressure, may freeze trapped water within pump. Use short, large I.D. pipe-work to
a smaller system. This makes the removal connect to a system. Resist the temptation
of moisture much more difficult. of using flexible charging hoses, which
Somewhere in the region of 2.5 CFM (1180 have small internal diameter, contract on
cm3/s) is adequate for most packaged reduction of pressure, and restrict flow.
applications, and up to 8.0 - 10.0 CFM
(3776 - 4720 cm3 /s) for large systems.
6. THE TWO STAGE VACUUM PUMP
The key to a good evacuation is to satisfy
all of the following: By dividing the total pressure difference
over which the pump operates, we can
• The satisfactory removal of water from improve the pumps overall volumetric
the system - obvious really! efficiency, allowing a deeper vacuum to be
achieved. The two-stage vacuum pump
• Having previously achieved a incorporates two separate rotors and
satisfactory leakage pressure test to BS chambers, in series, driven by a common
4434 (EN378). drive shaft and within a single housing.
The low-pressure inlet of the first stage is
• Having a well maintained vacuum pump connected to the system to be evacuated;
its discharge flowing to the intermediate
• Sufficient fresh vacuum pump oil and pressure inlet of the second stage. The
OFN for the process. outlet of the second stage is open to
atmospheric pressure.
• The vacuum pump incorporating a gas
ballast.
The vacuum pump oil is in contact with
• Short and non-restrictive connection of both stages to provide lubrication, sealing
the vacuum pump to the system. and cooling functions. As stated earlier,
the vacuum pump oil is very hydroscopic,
Having already dealt with the first two meaning that its moisture content is
items, a regularly maintained, clean and extremely low, and its ability for
well-treated, vacuum pump will last many absorption of moisture very high. Moisture
years of service. The condition of the vane removed by the vacuum pump comes in
tips is vital in the pump continually contact with, and is absorbed by the oil.
achieving such low pressures. As The oil changes colour through the
important, is the vacuum pump oil. This is absorption of moisture, from a cloudy
a specialist, highly hydroscopic oil, appearance to a "milky" white as the oil
specifically for vacuum pumps. becomes fully emulsified. At the first sign
of this condition the oil must be changed,
Replace regularly and do not use any and is a good and early indication of a still
other type of oil, nor oil from an "wet" system. Moisture is removed by the
unknown or unsealed container. vacuum pump not through the vacuum
produced alone, but by the difference in
The gas ballast is not an essential feature water saturation pressure / temperature
of the vacuum pump, but will greatly relationship between the system and the
reduce the frequency of need to replace vacuum pump oil. Dalton's law of partial
the vacuum pump oil during initial pressures states that:
evacuation. OFN is required, and
introduced to the system, to "break" a " The pressure of a mixture of gases at a
vacuum between multiple system specified volume and temperature is equal
evacuations. As the OFN is dry, it is able to to the partial pressures of its constituent
act like a sponge to absorb free moisture species".
present within a system. A low pressure-
drop between the vacuum pump and the
4) Operate the pump with the valve and stops on the scale, moisture is
closed for a period until the pump is present - check the vacuum pump oil
hot. Isolate the pump, drain and flush coloration.
with fresh oil before again filling.
12) If the needle rises above the scale,
5) Fit a calibrated, barometrically either a leak is evident and/or there is
isolated, absolute pressure gauge to a large quantity of moisture still within
the inlet of the pump and operate the the system - check the coloration of
pump, hot, to achieve the lowest the vacuum pump oil. Take necessary
pressure indicated. Ideally, a zero action depending upon result.
mBar reading is required. Isolate the
pump and watch for any rise in 13) If 11, valve-off and remove the
pressure. A rise would indicate a pump absolute pressure gauge before
seal and/or connection leak to be introducing OFN to raise the system
repaired. Proceed to 6. if OK. pressure to atmospheric. Allow the
system to stand, as the nitrogen will
6) Connect the inlet of the pump to the absorb free moisture within the
system to be evacuated, which must be system. Change the vacuum pump oil,
at atmospheric pressure. The pipe or re-evacuate the system and re-connect
hose must be as short as possible and the absolute pressure gauge. The
have the largest practical internal lowest pressure attainable should now
diameter. be lower than for the first evacuation,
and take less time. Try to reach 4
7) Ensure that all of the system valves
mBar, or below. Repeat the process
have been opened. Jack open where
above until a satisfactory evacuation
necessary.
has been reached.
8) Ensure where possible that the ambient
temperature, or air surrounding the 14) Isolate the final evacuation for a
machine, is above 12 °C during minimum of four hours, preferably over
evacuation. Add heat if necessary. 24 hours, on a pressure-rise test. The
attained pressure and ambient
9) Fit the calibrated absolute pressure temperature must be logged at the
gauge to a point on the system furthest time of day the test was initiated. If
from the vacuum pump connection. there is no indicated rise in pressure,
The lowest pressure will be at the the system is tight, and refrigerant
vacuum pump inlet, so if a point on the vapour charging may continue.
system furthest from the pump The use of OFN should minimise any
indicates a low reading, the entire change in recorded pressure due to
system pressure must be at this deviation of ambient temperature,
pressure. however, where the final ambient
temperature has changed, transpose the
10) Operate the pump, connected to the formula: P1 = P2
system, with the gas ballast open until T1 T2
a reading has just been indicated on
the absolute pressure gauge, and then to calculate the revised pressure, where
close the ballast. Operate the pump to the system is already leak-tight.
a pressure of less than 4 mBar, or less,
as read from the absolute pressure For example:
gauge fitted to the system.
P1 = the system pressure after
11) Once the lowest pressure has been evacuation, in mBarA.
reached, record it and valve-off the
pump from the system for a minimum T1 = the ambient temperature after
of four hours. If the gauge needle rises evacuation, in Kelvin.
Water vapour present from the system will BS4434 (soon to be superseded by EN378)
condense and freeze on the internal cold available from British Standards Institute
surface of the trap. Frost will accumulate Customer Services on 0181 996 9001.
and the cold trap will eventually need to
be isolated, defrosted and dried-off Institute of Refrigeration Safety Code for
thoroughly, before the trap is re-used. A1/A2 refrigerants (for guidelines for
essential maintenance routines etc)
10. ACKNOWLEDGEMENTS
The information contained in the Bulletin should be seen as a guide to interpretation of relevant industry
standards, legislation and statutory information which should be consulted by the relevant competent person
responsible for servicing refrigeration equipment. The Service Engineers’ Section and the Institute of
Refrigeration accept no liability for any errors or omissions.
Service Engineers’ Section of the Institute of Refrigeration, Kelvin House, 76 Mill Lane, Carshalton SM5 2JR