This specification has been revised as indicated below and described in the revision record on the following
page. Please destroy all previous revisions.
Lead Engineer
Project Manager:
Client Approval:
Record of Revisions
Revision Date Description
No.
TABLE OF CONTENTS
1.0 GENERAL......................................................................................................................................................... 5
1.1 Summary............................................................................................................................................. 5
A. Scope of Specification........................................................................................................... 5
B. Related Specifications and Documents ................................................................................ 5
1.2 References ........................................................................................................................................... 5
1.3 Design Requirements......................................................................................................................... 6
A. General .................................................................................................................................. 6
B. Performance........................................................................................................................... 7
2.0 PRODUCTS ...................................................................................................................................................... 7
2.1 General ................................................................................................................................................ 7
2.2 Material............................................................................................................................................... 7
2.3 Equipment........................................................................................................................................... 8
A. Gas System ............................................................................................................................ 8
B. CB (Circuit Breaker) ............................................................................................................. 8
C. Disconnect and Ground Switches ......................................................................................... 9
D. Bus System ..........................................................................................................................10
E. Instrument Transformers.....................................................................................................10
F. Terminal Equipment............................................................................................................11
G. Local Control Panel.............................................................................................................11
H. Remote Control Panel .........................................................................................................12
2.4 Design Criteria .................................................................................................................................13
2.5 Accessories And Wiring ..................................................................................................................13
A. Accessories..........................................................................................................................13
B. Control, Control Wiring, and Terminal Blocks..................................................................14
2.6 Fabrication and Manufacture ........................................................................................................14
2.7 Finish .................................................................................................................................................14
2.8 Inspection And Tests .......................................................................................................................15
A. Inspection ............................................................................................................................15
B. Testing .................................................................................................................................15
2.9 Identification And Tagging.............................................................................................................15
2.10 Preparation For Shipment..............................................................................................................15
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-E-6027
Project Name: Date: 01 Apr 2011
Contract Number: Page 4 of 16
Revision 1
4.0 ATTACHMENTS...........................................................................................................................................16
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-E-6027
Project Name: Date: 01 Apr 2011
Contract Number: Page 5 of 16
Revision 1
1.0 GENERAL
1.1 Summary
A. Scope of Specification
2. See Datasheet MQ-DS-E-6027: Datasheet for High Voltage SF6 Switchgear for
additional requirements.
3. See the Request for Quotation (RFQ) or Purchase Order (PO) for other
documents for additional requirements.
1.2 References
The latest issues, amendments, and supplements to these documents shall apply unless
otherwise indicated.
A. General
1. The assembly shall be of dead tank type where all components of the switchgear
{CB (Circuit Breaker), bus bars, disconnect switches, grounding switches, and
instrument transformers} shall be in grounded metal enclosures completely
surrounding all the live parts.
5. The equipment shall be designed to allow for thermal expansion due to operating
and short-circuit temperature rise of the bus bars within enclosures (and of the
enclosures themselves) as required.
6. The required base frame and supporting structures shall form part of the
equipment. Any support rails or channels that are to be connected to or
imbedded in concrete floor shall be furnished by Supplier.
7. Adequate space, ladders, and platforms shall be provided for easy access during
inspection, operation, and maintenance.
10. The switchgear shall be designed to carry the normal rated current and withstand
the short-circuit currents as specified in the datasheets.
12. Design, construction, and material of the enclosure shall ensure that it shall
withstand an internal arc without burn-through for 0.5 seconds.
13. The transportable units shall be completely factory wired. All the
interconnection leads shall be brought to a multi-pin connector to facilitate
testing and quick connection of the unit at the jobsite.
14. Manufacturer shall include in the supply the necessary preassembled cords with
multi-pin connectors to interconnect the different units and the local control
panel.
15. The switchgear shall be designed and fabricated for 20 years of system life.
B. Performance
2.0 PRODUCTS
2.1 General
This specification covers only the general requirements of the assemblies. The specific
requirements of each assembly (plan, arrangement, indoor or outdoor, component ratings,
relaying, metering, one-line diagrams, and control schemes), shall be shown on detailed
datasheets and documents that shall be part of the RFQ or PO.
2.2 Material
2.3 Equipment
A. Gas System
1. The assembly shall be divided into bays and each bay into gastight and arc-
resistant compartments so that the effect of any fault is confined to the respective
compartment.
2. The gas barriers and joints in the assembly shall have a high degree of tightness
to keep the loss of gas pressure to less then 0.1 percent per year.
3. Each major device or section shall be accessible for monitoring and maintenance
without evacuating a large volume of gas.
4. Each gas filled compartment shall have its own SF6 gas monitoring device and
rupture diaphragm that ruptures to discharge gas under excessive pressure.
Vented gas shall be diverted away from the operating aisle.
6. Gas monitoring shall be provided with one high pressure contact and 2 low
pressure contacts for alarm.
7. Each gas section also shall be provided with a gas connection valve for
evacuating and refilling the section. In addition, a means shall be provided for
connection of a manometer for checking the gas pressure.
B. CB (Circuit Breaker)
5. A loss of electric power to the stored-energy unit shall initiate a local alarm and
shall have a contact to initiate a remote alarm.
8. Each CB shall have a mechanical position indicator linked to the main contact.
10. The control panel shall contain equipment for monitoring, control, and
maintenance of the CB and its associated equipment.
11. The CB shall be capable of carrying the rated current and interrupting and
withstanding the short-circuit currents specified in the datasheets.
12. The CB also shall be capable of interrupting the rated current in the event of total
loss of SF6 gas pressure.
1. All switches shall be motor operated. A single operator shall operate the 3 poles
of the switch simultaneously.
3. Each switch shall have a mechanical position indicator linked with the main
contacts as well as viewing windows in the enclosure to see the actual position.
4. Provision shall be made for padlocking the switches in both open and closed
position.
6. All auxiliary contacts of the switches shall be wired out to accessible terminal
blocks in the local control panel.
7. Disconnect switches shall normally operate at zero current, but they shall be
capable of switching low charging currents.
8. The grounding switches on the bus bars, and the incoming and outgoing
disconnect switches shall be of the high speed type. High speed switches shall
be operated by motor charged springs.
9. When high speed switches operate, the contact rod shall be actuated directly to
release the springs.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-E-6027
Project Name: Date: 01 Apr 2011
Contract Number: Page 10 of 16
Revision 1
10. The disconnect switches shall be interlocked with associated CBs and grounding
switches to prevent any incorrect sequence of operation.
D. Bus System
2. The bus subassemblies shall be segregated from each other by gas barriers to
form separate gastight compartments.
4. Bus bars shall be able to carry the continuous current and shall be mechanically
braced to withstand the asymmetrical current as shown on the datasheets.
E. Instrument Transformers
1. Each CT shall have a secondary current rating as specified in data sheet MQ-DS-
E-6027.
2. CT’s shall be rated to withstand the steady state current and maximum short
circuit momentary rating of the switchgear.
3. The secondary winding ends and tappings of each bay shall be brought out
through gas-tight bushings to terminals in the respective local control cabinet.
These terminals shall be of the disconnectable shorting link type.
4. The number of CT’s and their ratios shall be shown on the one-line diagrams.
5. CT’s shall be selected to not saturate for a fault current equal to the switchgear
maximum short circuit rating.
8. PT’s shall have a BIL equal to or greater than the BIL rating of the switchgear,
and shall have primary voltage rating equal to the system’s line-to-line voltage.
10. Accuracy classes and burdens shall be in accordance with IEC 60186 or IEEE
1300 for voltage transformers.
11. All secondary-winding ends shall be brought out through gas-tight bushings to
terminals in a terminal box mounted on the outside of the voltage transformer
module.
F. Terminal Equipment
1. Overhead Lines
2. Power Cables
(1) Gland forming the seal with the sheath of the cable.
(2) Pressure tight insulator separating the SF6 gas from the cable and its
constituents.
3. Transformer Bushings
A modular connector shall connect the SF6 switchgear to the bushings of the
transformer connected to the SF6 switchgear.
1. Each bay of the assembly shall be provided with a local control panel.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-E-6027
Project Name: Date: 01 Apr 2011
Contract Number: Page 12 of 16
Revision 1
4. A copper ground bus, 6 by 50 mm, shall be provided throughout the length of the
panel assembly. The ground bus shall have on each of its ends, 1 solderless
compression terminator suitable for a stranded copper 70 mm2 grounding
conductor.
5. The local control panel shall contain equipment for control, monitoring, and
maintaining the following:
6. The face of the panel shall contain all gages, counters, mimic bus of the
assembly, status indication, and control switches for CB, disconnect, and
grounding switches.
7. A diagram shall be located on the inside of the panel door to show the
relationship of valves, gages, and other components in the SF6 gas systems.
8. Wiring between the switchgear and the remote control panel shall be wired
through the local control panel.
9. The interconnection of wires between the switchgear assembly and the local
control panel shall be by means of preassembled cords with multi-pin
connectors.
11. Provision shall be made for cable or conduit entry into the panel for external
connections.
4. A copper ground bus, 6 by 50 mm, shall be provided throughout the length of the
panel assembly.
5. The ground bus shall have on each of its ends, 1 solderless compression
terminator suitable for a stranded copper 70 mm2 grounding conductor
6. The remote control panel shall contain all protective relaying, meters, and
controls shown on the datasheets or documents. A mimic bus shall be provided
on the face of the panel with associated switches, relays, and meters to indicate
the functional condition of the switchgear.
A. Accessories
1. Suppliers shall supply all the auxiliary equipment required to support, monitor,
and maintain the switchgear.
2. The auxiliary equipment shall include but not necessarily be limited to the
following:
b. Equipment for handling and storing SF6 gas evacuated during maintenance
of switchgear
e. Resistance tester
f. Grounding devices
1. Control power for closing, tripping and auxiliary motor drivers shall be 125
VDC.
3. Terminal blocks shall have marking strips, terminal screws, and divider strips
between them.
4. Screw type wire terminations shall make use of compression type insulated
connectors that firmly grip the conductor and employ compression sleeves to
grip the wire insulation.
5. Terminal blocks shall be suitable for 2.5 through 10 mm2 stranded copper
conductors.
6. Control wiring shall be flexible stranded copper wire of a size not less than 2.5
mm2, with moisture resistant and flame retardant insulation.
7. The size of wire for CT circuits shall not be less than 6 mm2.
9. All spare auxiliary and relay contacts shall be wired to the terminal blocks for
Buyer's use.
10. Each end of every wire shall be identified with a permanent typewritten sleeve
type label.
The equipment shall be completely assembled at the factory. Sections may be shipped loose
for large equipment.
2.7 Finish
2. Manufacturer’s premium paint system for high humidity salt laden atmospheres
shall be used for all outdoor installations.
4. The front panel shall display a mimic and operational diagram providing clear
indication as to the status of all switches and breakers.
A. Inspection
B. Testing
2. Manufacturer shall fully describe in the proposal the details and procedures of
the tests that shall be carried out at the factory and the tests required at the jobsite
after erection.
3.0 EXECUTION
Not applicable.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-E-6027
Project Name: Date: 01 Apr 2011
Contract Number: Page 16 of 16
Revision 1
4.0 ATTACHMENTS
Not Applicable
End of Specification