DEP Doha Electromechanical Projects

Contracting and Trading Co. W.L.L


P.O.Box: 22914, Mobile: 55460127, Tel /Fax: 4313589, Email; dohaelmp@ gmail.com

Firetrace Direct low Pressure System


Installation and Commissioning Sheet
Test/Check on Fire Fighting System

Designation :
FTP No. :
FTP Zone No. :
MCC Column/No. :
Device No. :
Cylinder Location :
Manufacturer of FFS :
Model / Type No. :
Cylinder Serial No. :

A. Check the installation of the following: Checked


FM 200 Cylinder (HFC-227ea)
Direct Low Pressure valve
Pressure Switch
Firetrace Tube layout
T- Connector and Plug end of line

B. Leak Test for Fire Trace Tubing: Gauge Reading Date Time Checked
Apply nitrogen at 10 Bar on the Firetrace Tubing.
Check for system leak for 30 minutes after pressurizing.

C. Fire Alarm Condition:


1. Change or jumper the Pressure switch NO Line to NC line at the terminal block located N/A
inside the VFD panel where the cylinder is installed to activate Fire Alarm in designated
Zone No. __.
2. Verify Common Fire Alarm Contact to be used for interfacing If activated. N/A

D. Fault Alarm Condition:


1. Disconnect pressure switch line at the terminal block located inside VFD panel where N/A
the cylinder is installed to activate Fault Alarm in designated Zone No. __.
2. Verify Common Fault Alarm Contact to be used for interfacing If activated. N/A

Notes/Comments:
Item C & Item D to be check and verified by Fire Alarm Contractor.

Carried out by Approved by Witnessed by

Fire Alarm System Sub- ABB Customer


VEOLIA
Contractor - DEP
Name: Name: Name:
Signature: Signature: Signature:
Date: Date: Date:

Page 1 of 1