Sunteți pe pagina 1din 4

Part No.

: 4417660 Honeywell Internal Use only


ISA100 SmartRadar FlexLine Specification

Technical Specifications
Description Specifications

Maximum number of SmartRadar FlexLine field devices


100
per Wireless Device Manager (WDM)

Maximum number of ENRAF interface serial clients (CIU


1
Prime field port or Engauge tool) per WDM

Maximum number of ENRAF interface UDP clients (CIU


12
Prime field port or Engauge tool) per WDM

Maximum number of field ports per CIU Prime 4

Maximum number of SmartRadar FlexLine field devices


13
per CIU Prime field ports

Maximum number of SmartRadar FlexLine field devices


50
per CIU Prime

3 requests per second (per client) - That is, 50 gauges


can be scanned (level record) in 7 seconds per CIU
Prime.
This value varies depending on the network topology as
follows:

1. Impact of enabling the routing:

a. Performance reduces if the routing in


SmartRadar FlexLine is enabled.
Protocol tunnel request rate for the ENRAF interface per
client (CIU Prime field port or Engauge tool) 2. Impact of the access points:

a. Performance increases when all the


SmartRadar FlexLine field devices in
a single access point are mapped in a
single field port of the CIU Prime.

b. Performance decreases when the


SmartRadar FlexLine field devices in
a single access point are mapped in
multiple field ports of the CIU Prime.

c. Performance decreases when the


access point has any other additional
device other than the 13 SmartRadar
FlexLine field devices.

d. Performance decreases when the


SmartRadar FlexLine field devices are
configured at reporting period which is
less than 10 seconds.

3. Impact of the number of clients (CIU Prime field


port or Engauge tool)

a. Performance increases by 50% for

Part No.: 4417660 Honeywell Internal Use only


ISA100 SmartRadar FlexLine Specification

Description Specifications
each additional client.

4. Impact of the device’s Hop level:

a. Performance decreases by 15% at


every hop level.

Note: For optimal performance, Honeywell does not


recommend to configure a SmartRadar FlexLine field
device through the Enguage tool when the CIU Prime
field ports are requesting tunnel data through wireless
network.

Maximum number of SmartRadar FlexLine field devices


(with any reporting period) that can be connected to a 13
access point (input channels only)

Maximum number of SmartRadar FlexLine field devices


in redundant configuration (with any reporting period)
13
that can be connected to two access points (input
channels only)

The publication rates supported by SmartRadar FlexLine 1, 5, 10, 30, or 60 seconds


field devices for access points The default publication rate is 10 seconds

4
Note: The number of ISA100 network hops does not
Maximum number of ISA100 network hops supported
include the IEEE 802.11 mesh network hops between
Multinodes or Cisco 1552S access points.

Maximum time taken for SmartRadar FlexLine radio


15 minutes
firmware upgrade through OneWireless user interface

Maximum time taken for SmartRadar FlexLine


application HCI-1WL (CAN-1WL) firmware through 30 minutes
OneWireless user interface

Maximum time taken to upgrade firmware on FlexLine


35 minutes
cards (other than CAN-1WL) through Engauge tool

3 SmartRadar FlexLine field devices are recommended


for radio firmware.
Maximum time taken for the parallel Radio/Application
Only one SmartRadar FlexLine field device sensor card
firmware upgrades supported through OneWireless user
interface (TII-XR, FCI-HT, FII-VT, FII-SMV, FII-RTD, HCI-GPU,
HCI-BPM, and FII-DO) firmware is recommended to be
upgraded at a time.

Maximum number of SmartRadar FlexLine field devices


(with any reporting period) connected to the FDAP
Router 10

Maximum number of SmartRadar FlexLine field devices 2 devices with 1 second publication rate
connected to the field router (line-powered) 3 devices with 5 seconds or greater publication rate
Note: Honeywell does not recommend to connect the Note: The number of SmartRadar FlexLine devices that
SmartRadar FlexLine field devices to a battery powered can be connected to a field router depends on the

Part No.: 4417660 Honeywell Internal Use only


ISA100 SmartRadar FlexLine Specification

Description Specifications
router number of devices that the field router can support.

2 devices with 1 second publication rate


3 devices with 5 seconds or greater publication rate
Maximum number of field devices connected to the (using a double slot communication module)
SmartRadar FlexLine field device acting as a router
5 Devices with 5 seconds or greater publication rate
(using a single slot communication module)

Total number of configurable transducer blocks 17

Maximum number of configured transducer blocks that


8 (1 fixed and 7 configured)
can be in use at any given time

Maximum time required to establish communication with 2 minutes for the first hop
the SmartRadar FlexLine field device after the Note: 30 seconds additional time is required for each
SmartRadar FlexLine field device restarts hop

Baudrate: 19200 bits per second


The recommended settings to be configured in CIU
Timeout: 500 milliseconds
Prime for optimal tunnel performance
Retries: 3

Baudrate: 19200 bits per second


The recommended settings to be configured in Engauge
Timeout: 9999 milliseconds
tool for optimal tunnel performance
Retries: 3

Minimum recommended connection status metrics RSSI: Greater than -75


required to get the optimal tunnel performance or RSQI: Greater than 180
wireless network performance Transmit failure ratio: Less than 20%

This technical specification is qualified for the following versions:

1. OneWireless – R220

2. Engauge tool – V 2.6

Note: Prior versions of Engauge tool are not supported.

3. CIU Prime – B03.002-D02.002-E02.001

Part No.: 4417660 Honeywell Internal Use only