AP-FCU-14

Chilled Water
PRODUCT SYSTEM
Wall Mounted

Cassette

Ducted

Fan Coil Unit


Product Catalogue

Products manufactured in an ISO certified facility.


This document contains the most current product information as of this printing.
@2014-1
Contents

40
35

20 / 25 / 30 / 40
30
Wall Mounted Type

25
02

kW
20
Ceiling Cassette Type
* With Brushless DC Motor

15
04 06 08

3 / 4 / 6 / 7 / 9 / 11 / 12 / 14 / 16
5 / 6 / 8 / 9 / 11 / 13
10

2 / 3 / 4 / 6 / 8 / 10 / 12
Ceiling Concealed Type

Products Overview
5

02 / 03 / 04 / 05 / 06

2/4/5
10 15

0
Ducted Blower Type

18

Cooling Capacity
FWMJC-B
FWMT-CV1 FWMJCC-A FWMH-A FWPMM-A UAHMM-A
FWKE-E
Remark: All unit photos in this catalog are solely for illustration purpose, actual outlook may differ slightly.
All specifications are subjected to change by the manufacturer without prior notice.
Ceiling Cassette Compact Type (600x600) Specification for Ceiling Cassette Compact Type
*
MODEL FWMJCC2BV1 FWMJCC4BV1 FWMJCC5BV1
AL BL
Btu/h 8500 14000 15500
NOMINAL COOLING CAPACITY
* Optional Item W 2490 4100 4540
Btu/h 6500 10000 11500
NOMINAL SENSIBLE COOLING CAPACITY
W 1910 2930 3370

NOMINAL HEATING CAPACITY Btu/h 12000 16000 18000


(ENTERING WATER TEMP. = 50°C) W 3520 4690 5280
NOMINAL TOTAL INPUT POWER W 63 64 79
NOMINAL RUNNING CURRENT A 0.28 0.28 0.35
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE N/A
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
BRC52A62 BRC51A62 CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 380 400 440
FWMJCC-A
AIR FLOW MEDIUM CFM 290 310 330
LOW CFM 230 220 280
› Aesthetically attractive and slim front panel › Built in high pressure head drain pump USGPM 2.03 3.43 3.57
› 4 Way air discharge for better air distribution › Washable saranet air filter NOMINAL WATER FLOW RATE
litres/min 7.68 12.98 13.51
› Compact design › Easy-to-use wireless handset
HEAD LOSS (COOLING) kPa 19.3 26.9 28.8
› Easy installation and maintenance › Wired handset available (optional)
HEAD LOSS (HEATING) : 50°C kPa 16.8 23.9 26.5
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.75 0.76 0.83
SOUND PRESSURE LEVEL (H/M/L) dBA 42 / 35 / 29 45 / 38 / 30 48 / 40 / 36
UNIT DIMENSION - ( ) WITH PANEL HXWXD mm 250 X 570 X 570 (295 X 640 X 640)
PACKING DIMENSION - ( ) PANEL HXWXD mm 316 X 630 X 630 (126 X 700 X 726)
UNIT WEIGHT (UNIT + PANEL) kg 15 + 3 17 + 3 17 + 3
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05
TYPE TURBO FAN
DRIVE DIRECT
FAN HIGH RPM 725 810 900
FAN SPEED MEDIUM RPM 565 630 700

INDOOR UNIT
LOW RPM 460 480 610
TYPE INDUCTION
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
HIGH W 63 64 79
RATED
INPUT POWER MEDIUM W 51 58 73
LOW W 46 52 69
FAN MOTOR
HIGH A 0.28 0.28 0.35
RATED
RUNNING MEDIUM A 0.23 0.25 0.32
CURRENT LOW A 0.21 0.24 0.31
STARTING CURRENT A 0.32 0.30 0.47
MOTOR OUTPUT W 17 23 28
POLES 6
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m² 0.24 0.25 0.25
ROW 1 2 2
WATER VOLUME litre 0.43 0.83 0.83
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR LIGHT GREY

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27˚C DB / 19˚C WB 20˚C DB
ENTERING WATER TEMPERATURE 7˚C 50°C (2 Pipes System)
70°C (4 Pipes System)
LEAVING WATER TEMPERATURE 12˚C 45°C (2 Pipes System)
60°C (4 Pipes System)

ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

4 5
Ceiling Cassette Type (900x900) Specification for Ceiling Cassette Type
*
MODEL FWMJC6BV1 FWMJC8BV1 FWMJC9BV1 FWMJC11BV1 FWMJC13BV1
AL BL Btu/h 21000 25000 30000 38000 43000
NOMINAL COOLING CAPACITY
* Optional Item W 6150 7330 8790 11140 12600
Btu/h 16700 19200 22300 27400 31000
NOMINAL SENSIBLE COOLING CAPACITY
W 4890 5630 6540 8030 9090

NOMINAL HEATING CAPACITY Btu/h 28000 33600 38300 45500 52000


(ENTERING WATER TEMP. = 50°C) W 8210 9850 11230 13340 15240
NOMINAL TOTAL INPUT POWER W 95 126 167 186 227
NOMINAL RUNNING CURRENT A 0.44 0.55 0.74 0.85 1.03
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE N/A
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
BRC52A62 BRC51A62 CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 750 860 890 1000 1140
FWMJC-B
MEDIUM CFM 620 700 720 840 1000
AIR FLOW
LOW CFM 480 540 570 680 840
› Modern and elegant panel › Quiet operation QUIET CFM 320 380 420 540 700
› 4 way air discharge for better air distribution › Low casing height
USGPM 4.71 5.59 6.69 8.45 9.60
› Wide capacity range › Built in high pressure head drain pump NOMINAL WATER FLOW RATE
› Multi Comfort - 3 air swing patterns control › Washable saranet air filter litres/min 17.83 21.17 25.29 31.94 36.29
› 4 speeds fan motor › Easy-to-use wireless handset HEAD LOSS (COOLING) kPa 20 37 22 44 53
› Quiet function available › Wired handset available (optional) HEAD LOSS (HEATING) : 50°C kPa 19 33 19 38 47
MAX. WORKING PRESSURE kPa 1600
SURFACE AIR VELOCITY m/s 0.91 1.04 1.14 1.03 1.17
SOUND PRESSURE LEVEL (H/M/L/Q) dBA 42/38/32/23 46/42/35/27 48/43/38/30 50/47/43/33 52/49/45/39
UNIT DIMENSION - ( ) WITH PANEL H X W X D mm 265 X 820 X 820 (340 X 990 X 990) 300 X 820 X 820 (375 X 990 X 990)
PACKING DIMENSION - ( ) PANEL HXWXD mm 341 X 916 X 916 (125 X 1020 X 1020) 376 X 916 X 916 (125 X 1020 X 1020)
UNIT WEIGHT (UNIT + PANEL) kg 26 + 4 26 + 4 28 + 4 32 + 4 32 + 4
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05
TYPE TURBO FAN
DRIVE DIRECT
FAN HIGH RPM 530 600 660 710 800

INDOOR UNIT
FAN SPEED MEDIUM RPM 450 500 550 610 710
LOW RPM 360 400 450 510 610
TYPE INDUCTION
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
HIGH W 95 126 167 186 227
RATED
INPUT POWER MEDIUM W 79 103 109 151 176
LOW W 67 89 86 118 144
FAN MOTOR
HIGH A 0.44 0.55 0.74 0.85 1.03
RATED
RUNNING MEDIUM A 0.40 0.45 0.49 0.71 0.82
CURRENT LOW A 0.36 0.39 0.39 0.57 0.69
STARTING CURRENT A 0.44 0.71 0.89 1.02 1.28
MOTOR OUTPUT W 30 45 65 80 110
POLES 8
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m² 0.39 0.39 0.37 0.46 0.46
ROW 2 2 3 3 3
WATER VOLUME litre 1.36 1.34 1.97 2.35 2.35
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR LIGHT GREY

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27˚C DB / 19˚C WB 20˚C DB
ENTERING WATER TEMPERATURE 7˚C 50°C (2 Pipes System)
70°C (4 Pipes System)
LEAVING WATER TEMPERATURE 12˚C 45°C (2 Pipes System)
60°C (4 Pipes System)

ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

6 7
Standard Features Controller
Wireless Controller - BRC52A62
COMFORT FIN TYPE 1. Transmission Source
1
Turbo Mode - Rapid cooling/heating with 2. "Glow in the dark" Power ON/OFF
highest fan speed for immediate comfort AL Bare Aluminium Fin
3. Vertical Automatic Air Swing
4. Selectable Mode:
Quiet Mode - Effective cooling with Cool, Dry, Fan
lower noise level BL Anti Corrosion Hydrophilic Blue Fin 2
3 12 5. Turbo Function
4 6. Quiet Function
Dry Mode - Keeping the room dehumidified, 5
while maintaining room temperature 11 7. ON Timer Setting
6
10 8. Real Time Clock
7 9 9. OFF Timer Setting
Sleep Mode 8 10. Sleep Mode Function
11. Temperature Setting
12. Fan Speed Selection:
High, Medium, Low, Auto

AIR FLOW CONTROLLER


Selectable Fan Speed - Different fan speed is
With Wireless Remote Controller
available for comfort selection Wired Controller - BRC51A62

Belt Driven Evaporator Motor With Wired Remote Controller Features:


• Cool/Fan/Dry mode
• Auto/High/Medium/Low fan speed
Automatic Vertical Swing - Automatic movement
of air discharge louver for uniform air distribution • Temperature display in °C and °F
• Turbo and Quiet function
Manual Horizontal Air Flow - Adjustable horizontal • Sleep function
discharge grille for desired air flow direction • Swing function
• Real time clock and day display
4 Way Air Discharge • 7-days programmable timer (up to 2 sets)
• Error indicator
• Key lock and fan lock features
• Batteries back up and retain setting during power failure
• Last state memory (memory backup setting from main board)
IAQ • Delay timer (1 or 2 hours)
Washable Saranet Filter - Removal of airborne dust • Interaction with Wireless Handset (BRC52A62)
particles through saranet filter ensures cleaner air supply

20 21
Intelligent Control Series Supported Configuration

BRC51A62
Master Slave

BRC52A62
Network Interface Module (NIM) is a networking system which enables communication among Daikin air conditioners.
With the Network Interface Module (NIM), all your air conditioning systems can be controlled with just a single controller giving you benefits:
Communication Bus Connection Recommended Maximum Cable Length (m)
Network Control NIM A 2-way twisted pair cable is used as the communication First NIM to the furthest
bus. Recommended cable for communication bus is a pair connected NIM 1000

Benefits of screened & shielded, twisted single core wire with core NIM to Main Board 10
• More convenience. No more individually controlling air conditioning units diameter of 0.5mm to 1.0mm.
• Quicker and easier zone control from the master control unit NIM to Wired Controller 10
• Better control of air conditioning systems operating conditions
Connection
NIM utilizes master-slave type system whereby the master node will issue commands to each of
the slave nodes. The communication bus must be connected serially to the adjacent NIM. (Daisy chain connection). The same polarity has to be
connected between the NIMs (A to A, B to B).
Every master unit will have a group address so that every slave can only response to their
respective master. Each slave unit must have a unique address so that it can be addressed
independently of other nodes.
The master unit will be operating in conjunction with a control panel. Any settings done via the
G-Way
control panel connected to the master will overwrite the settings of its slave units.
Slave unit can be operated with or without control panel. If a slave unit is operating with a control Function
panel, its settings can be changed without following its master. • Gateway between fan coil unit and basic Building
NIM Management System (BMS).
Basic Features Note:
• DIP switch setting for Group & Unit address. • Maximum point to point communication bus up to 1000m. • Remote (On/Off) control of air conditioner via BMS.
• Master or slave system configuration. • A single master unit can control up to 15 slave units in each group. • Unit error indication via BMS and BRC51A62 controller.
• Automatic detection of control panel existence. • Each slave unit will sense their individual local temperature.
• Unit operation status monitoring via BMS.
• Error type and unit ID indication through display control panel. • Unit address range from 0 to 15 (0000-1111).
• Maximum point to point communication bus between air
conditioner and BMS of up to 1000m.
The Nim System Consists Of • DIP switch setting for control or monitoring function.
G-Way
• Main Board controller • Display control panel • NIM controller • Communications bus

Types of Operation DSW2 Setting


Connection
Control & Monitor (Ext. Switch Closed = ON A/C) 0000
Control & Monitor (Ext. Switch Open = ON A/C) 0010
Monitoring only 0001
DSW2 Setting
(up to total of
16 FCUs)
To Wired Control Panel

Dry Contact Dry Contact


CN2 Switch
Input

Unit On/Off
Master Slave Slave(s) Slave(s) To MainBoard CN1 RELAY 1 NO Dry Contact
COM Output 1 Indicator

RELAY 2
NO Dry Contact Unit Error
COM Output 2 Indicator
Main Board Controllers And Display Control Panel DIP Switch
NIM must be used in conjunction with: Terminal
• Fan coil units Blocks
• BRC52A62 or BRC51A62
1000 m
G-Way Controller BMS

22 23