Sunteți pe pagina 1din 94

INTECONT PLUS®

Solids Flow Meter

Operating Manual

BV-H2219GB
PASS - Service you can rely on.
Fast, comprehensive, anywhere in the world

Quality and reliability are the cornerstones of our company’s philosophy. That is why we consider a
comprehensive service concept simply par for the course, from strict quality control, installation and
commissioning through to seamless support across the entire product life cycle.

With over 30 service stations and over 180 service specialists, you can count on us to be there whenever –
and wherever – you need us. It doesn’t matter where you are, our specialists are there to advise and assist
with the best in worldwide, personal, comprehensive service.
During office hours, service specialists from all divisions are on hand to analyse problems and failures.
Look at www.schenckprocess.com for your nearest Schenck Process Location.

Customised to meet your requirements, our comprehensive Process Advanced Service System provides you
with the best service. Are you looking for individual, perfect-fit service solutions?
Then our, the modular service system PASS, is the ticket. It covers the entire service spectrum, from simple
inspections through to full service. Interested? Then find out more about the individual components at
www.schenckprocess.com/en/service.

Free 24 h Emergency Service Hotline in Germany


Are you experiencing a failure or problem outside normal office hours? Our service staff are on call around the
clock to deal with failures, service planning and other emergencies.

J +49 171 2 251195 Heavy and Light excluding Static Weighing Equipment

J +49 172 6 501700 Transport Automation and Static Weighing Equipment

© by Schenck Process GmbH, 2009


Pallaswiesenstraße 100, 64293 Darmstadt, Germany
J +49 61 51-15 31 0
www.schenckprocess.com

All information is given without obligation. All specifications are subject to change.

Note: Translation of the original instructions


INTECONT PLUS VDM

Contents
1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Power ON· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 4
LEDs· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 4
Normal Displays · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 5
Operation in Normal Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 5
Event Messages· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 6
Function Distributor · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8
Display Check and Version Number · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8
Keyboard Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9
START/STOP Feeder · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9
EasyServe Active/Deactive · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9
Batching Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 10
Loading By Sight · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 12
Print Batch Report · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 13
Zero Setting · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 16
Read Parameters · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 17
3. Control Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5. Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6. Setting Programs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Function Distributor · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 27
Calibrating Functions · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 28
TW Tare · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 28
CW Weight Check · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 29
Simulation Mode· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 31
Set Time · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 31
7. Service Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8. Parameterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Select Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Enter Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Hardware Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Load Default Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Parameter Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9. Event Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
System Message S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Electrical System E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Calibration C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Maximum H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
0842 Minimum L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Material Flow (Batch) B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Contents
ownership and copyrights. Redaktion PDE-RD BV-H2219 GB I - 1
VDM INTECONT PLUS

Signal Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
10. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Test Plug· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 71
11. Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Start Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Batching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Data Flow Charts: Signal Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Base Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Printer Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
12. Replacement Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Replacing INTECONT PLUS FIP —> INTECONT PLUS VEG . . . . . . . . . . . . . . . . . . . . . . 85

This manual applies to software version VDM 20600-05

Edition : 0842
0842

Transmission to third parties and reproduction


Contents Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB I-2 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

1. Overview

On INTECONT: Display:

INTECONT PLUS is designed as measuring and 5 x 7 - dot matrix with 6 mm character height
evaluation system for
Upper display left : running message
Belt Weighers right : totalized amount in kg/h or
Solids Flow Meters t/h
Mass Flow Meters
Mass Flow Feeders Lower display left : event messages
Weighfeeders right : selectable
Loss-in-weight Feeders flow rate, measured load
The system is supplied in 3 variants: etc.

1. Without option card (standard) Display can be changed over to American units.
2. With option card VFE 610V
LEDs:
for additional input/outputs and printer
3. With option card for fieldbus 2 green and 3 red LEDs
VSS021V : Modbus/S5
VPB 020V: Profibus Green LEDs : Ready
VCB020V: DeviceNet Red LEDs : Error or limit value messages
VET020V: MODBUS/TCP
VET022V: ETHERNET/IP
This manual applies to mass flow meters without
prefeeder control. Keyboard:

For Further Reading: Flexible membranes with tactile touch


Fieldbus manual BVH2220
S5-RK512 (3964R)
Modbus (Comp)
FH 458
FH 525 gB Start/stop measurement

TU Preselect lower display


Select functions

O Z1 = 362.5 kg
E1 I = 1 0 0 0 kg/h

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Overview
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 1
VDM INTECONT PLUS

i Reset counter
The schematic below shows all inputs and outputs.
The sample mechanical equipment presents a system

G FUNC Call function distributor and


event texts
equipped with crossed flexure strip.

O DEL Acknowledge event message,


delete input

N ESC Abort function

f ENT Start function,


acknowledge input

P DAT Prepare input, e.g. of setpoint

B9 Enter parameters

KL Enter sign and decimal point

Some Definitions:
O Z1 = 362.5 kg
I = 1498 kg/h
I = Feed rate in kg/h or t/h
Material amount per unit time
Z = Totalized amount in kg or t

Q = Measured load
Load on load cells in kg

Measuring Principle:

Material is guided to measuring chute S free from


whirls. S = Measuring chute
Deflection force acts on load cell L/C whose output
voltage is proportional to flow rate. L/C = Load cell
INTECONT evaluates signal and computes flow rate
M = Relay output for material prefeeder
and totalized amount.
F, G = Relay output for full feed/dribble
Measuring Technique:
feed changeover
n Precision AC voltage amplifier with continuous
correction of zero point and range. Z = External totalizing counter
n Highly resolving analog-to-digital converter.
The integrated method is designed to efficiently A = Analog display for feed rate or
suppress mains voltage interferences. measured load

n 16-bit microcontroller SERIAL = Serial interface for printer and host


n Unlimited storage of counter readings, computer
configuration and calibration data.
24 V = Power supply
0842
ALARM = Relay output for ALARM

Transmission to third parties and reproduction


Overview Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 2 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

MIN = Relay output for MIN limit value

MAX = Relay output for MAX limit value

ACK = Acknowledge event messages

EXT INPUT = External interrupt input

ON = Relay output, scale started

START/STOP = Start and stop scale

Release = Release input

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Overview
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 3
VDM INTECONT PLUS

2. Control
Power ON LEDs

During power failure

all counter readings


counter pulses still to be output
preselected normal displays,
Service values, e.g. ON-time
are stored for an unlimited time.
Z1 = 2 5 0 0 kg
The internal clock continues running for approx. 5
E1 I = 0 kg/h
days.

After power-up, an automatic display and lamp test is


performed, followed by the display version number,

a
then by normal displays.
(green) POWER OK
lit if all power supplies are OK.

Message E1 b (green) CPU OK


lit if microprocessor is ready to
operate.

E1
Z1 = 2 5 0 0 kg
I = 0 kg/h X (red) ALARM
flashes if an Alarm is available.
In addition, the event code is
shown in lower display line.

reports power failure . MIN (red) MIN LIMIT VALUE


Message can be configured as ALARM or WARNING. lit if feed rate limit value is
exceeded down.
ALARM:
Red LED X and symbol E1 flash. MAX (red) MAX LIMIT VALUE
lit if feed rate limit value is
Acknowledge message before starting exceeded up.
scale.
WARNING:
LED X remains dark, symbol E1 does
not flash.
READY: The two green signal lamps light;
no Alarm is available.
No acknowledgement required.
Start scale manually or automatically.

O Acknowledge event message.

0842

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 4 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Normal Displays Operation in Normal Mode

Upper Display
g Start totalization.
Condition : External release signal
Left : Running display and operating modes.
The rotating point indicates that totalizing should be available,
counter, measuring wheel and prefeeder otherwise message S2 is
are ON. output (selectable).
Right : Totalizing counter 1 START_source (B06
should be set to OP or
Keyboard Mode active.
Operating Modes No alarm available.

Feature : Point stands still after a


selectable counter
tracking time.

B Stop totalization.
Measured load and speed continue being
acquired.

i Reset totalizing counters.

Z1 = 5 0 0 0 kg
Z2 = 6 0 0 0 kg/h
1 Enter number of desired counter (1 or 2).
FMZ No. : _
Counter 3 cannot be reset. In case of
overflow, counting resumes from 0.

Lower Display
f Acknowledge input.

Left Event reported by alphanumeric code, O Delete digits input incorrectly

Right
e.g. E1 for power failure.
Selectable N Abort input

TU Select display
TU Select lower display
(see Normal Displays).

O Acknowledge event message.


Counter Z1
Counter Z2
Z1 = 5000
Z2 = 6000
kg
kg G Call further functions, e.g. Display Event,
Calibration.
Counter Z3 Z3 = 1000 kg
Feed rate
Feed rate
I = 1000
Ir = 50,00
kg/h
% 1) N Exit function distributor.
Measured load Q = 10.000 kg
Measured load rel. Qr = 68,91% 2)
Batch Zb, ZI, Zd, Nb, Zbn, Zdn 3)

1) related to nominal feed rate


2) related to nominal measured load
3) see Batching Mode
0842 Display formats and units of Z1, Z2, Z3 and I can be
selected individually.

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Control
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 5
VDM INTECONT PLUS

n WARNING 2 Display permanent, not


Event Messages underscored.

Definitions Acknowledgement:
Not required.
All important scale functions are internally monitored.
Errors are reported by event message. n IGNORE No monitoring of events, save
MIN/MAX messages and deviation
For troubleshooting details, see chapter “Event via contact outputs and signal
Messages”. lamps.

If several events occur at the same time, the most


Z1 = 2 5 0 0 kg significant event is displayed first.
E1 I = 0 kg/h
Priority: Alarm, Warning 1, Warning 2.

Operation

Message E1 Power Failure O Acknowledge all available events of


classes Alarm and Warning 1.
Message is output in the left field of the lower display If several events are available,
in form of a group letter (e.g. E) and a number (e.g. 1). acknowledge same one after the other.
In addition, an explanatory text can be called up.
To display event texts:
The events are organized into 4 classes. The
assignment of event to class can be selected using
relevant parameter. G Call function distributor.

n ALARM Display flashing and underscored. TU Scroll “Display Events” into lower display

In addition, red signal lamp


flashes.
X f
field (normally not required).

Select function.
Totalization cuts off, scale is not
operable.

Start:
First remove cause of fault and
acknowledge message.

Acknowledgement:
If cause has not been removed
yet, flashing stops, underscores
are deleted, but message is still
available.
If fault is remedied after
acknowledgement, message
automatically effaces.

n WARNING 1 Display permanent and


underscored.
Totalization continues.

Acknowledgement:
If fault has not been remedied yet, 0842
underscore is faded out.

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 6 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

I = Feed rate
L/C = Load cell
1. Events S 2 = M06
No Release
* fault in device or cabling
** reserved for mass flow feeder

Contact Outputs

Display shows: General alarm available until


acknowledgement
Name e.g. No Release
Code e.g. S2
Min/Max outputs independent of event class,
and hint e.g. Parameter 07
active also with IGNORE.
Limit values are reported as
of respective event.
long as event is available
provided that scale is active
The hint informs the service staff of the relevant
parameter. The consecutive number relates to the
priority sequence. Automatic Zero Setting Function

TU View several events.


If automatic zero setting is selected, system
continuously acquires and corrects zero point error

N Return to normal displays.


also if measurement is stopped and measuring wheel
is running.
Zero setting is reported by feature “Zero” independent
List of Events of measurement success.

The list is sorted by display priority.


AUTOMATIC ON
System Message S S1 Memory Error *
S2 No Release
S3 Maint. Scale Run
0o Z1 = 2 5 0 0 kg
S4 Maintenance Int. Elec I = 0 kg/h
S7 Simulation Active**
S9 Data Link Host

Batching B B1 Out of Tolerance


B9 Linearization

Electrical System E E1 Power Failure


E6 External Input

Calibration C C1 L/C Input*


C5 Tare Corr. > MAX

Maximum H H1 I >MAX
H4 L/C Input > MAX

Minimum L L1 I < MIN


L4 L/C Input
0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Control
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 7
VDM INTECONT PLUS

B = If batching mode is selected, additional


Function Distributor functions can be accessed in the main
distributor.
The function distributor lets you call further functions
and/or dialogs. Abort Batch
Deselect Batch

G Call function distributor.


If no event is available, display shows the
Batch Number
Print Batch
Reload
function selected last. If an event is
available, the “Display Events” function is S = Calibrating functions accessible after
displayed. password input.
f Start function.
E =
Prompt is output after call of function
Only if an event is available
N Return to normal displays and/or
abort function. With opposed functions, e.g. START/STOP, only the
one currently availabe can be reached.

Moving in function distributor does not limit any


Function
scale-specific functions.
Display Events

Display Check and Version Number

This function lets you check displays and signal


TU Move through function distributor.
lamps.

Display Events E G Call Display Check function.

TU
Display Check 1. All display elements rhythmically
START/STOP Feeder flash.
Service Values
f
2. Version number is displayed for
START/STOP Keyb. Mode approx. 10 s.
Select Batch B Test terminates automatically.
EasyServe active/deactiv
>0< Zero Set
Programming
Calib.Functions S
Print FMZ

Read Parameters
Enter Parameters S
Load Default Par. S
Print Parameters Example:
Print Stat. Rep.
VDM : Soilds Flow Meter
START/STOP Simulation 20600-00 : Version number
TW: Tare
CW: Weight Scheck
Set Time

Programming” and “Calibrating Functions” lead to


0842
further menus you can move through using cursor
keys.

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 8 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Keyboard Mode EasyServe Active/Deactive

With the function “keyboard mode” can be put the The “EasyServe Active/Deactive” functions let you
preselected control source for switching on and off control your INTECONT using the EasyServe PC
and the default of the load desired value on the service tool.
keyboard INTECONT.
Upon changeover from external source (e.g. serial) to
keyboard, START/STOP status is maintained. GT Call function distributor.
Select “EasyServe Active” function
In reverse direction, the external signals are active.

GT
To set communication parameters, use
Call function distributor. Block R.
Select “START Keyboard Mode” or
“STOP Keyboard Mode” function.
Note: Upon power failure, the current status is
Display feature: stored, i.e. “EasyServe Active” function
needs not be re-called.
You will know Keyboard mode by the square in the left
upper display field. Connection to PC can also be made using a 9-pole
SUB-D connector on X4 (RS 232 only) or a Phoenix
connector on X5 (RS232, RS422 or RS485).
START/STOP Feeder See also Wiring Diagram in chapter DETAILS.

The “START/STOP Feeder” function lets you start and


stop material prefeeder.
In started state (ON), INTECONT controls prefeeder.
The normal Start/Stop commands cannot be used.
In Stop state, material flow is interrupted and scale
can be tared, etc.

GT Call function distributor.


Select “Start Feeder” or “Stop Feeder”
function.

f Start function.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Control
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 9
VDM INTECONT PLUS

1. Zb = Batch setpoint
Batching Mode
2. ZI = Batch actual value
Batching mode is used to feed a defined amount of (amount already
material. When batch setpoint is reached, batching discharged)
operation is complete.
3. Zd = Batch residual value
0 Start batch, open prefeeder. (amount still to be
discharged)
1 Abort batch at any time
and
2 resume. Zd = Zb-ZI
3 Change over to dribble feed by reducing prefeeder
output. 4. Nb = Consecutive batch
4 Cut off prefeeder. number.
5 Batch setpoint is reached. To set start value, use
“Batch Number“
function.
Additional Displays
Before start of a batch, ZI and Zd indicate the
amounts fed out during previous batch.
Batching mode deselected (”Deselect Batch”
function), displays are disabled but can be used again
upon next selection.

Display format corresponds to the format of Counter


1.

Select Batching Mode

Selection of Batching mode enables batching,


however, no batch is started yet.

Condition: Scale OFF


EO Z1 = 2 5 0 0 kg

G
Z2 = 4 0 0 kg
Call function distributor.

TU Scroll “Select Batch” function into display


field.
Upper display: If batching mode is selected, totals
sign Σ

is displayed left of running


f Select function.

message.
The square indicating Keyboard System prompts for input of batch setpoint.
mode is omitted. If batch is selected from external PC, setpoint input is
omitted.

TU
Lower display:
Use cursor keys to scroll 3
additional values into display field.
0842

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 10 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Enter Setpoint
Deselect Batch
Prompt for setpoint input is output automatically upon
selection or can be started in manual when batch is Lets you deselect Batching mode, i.e. mode is
complete (scale OFF). removed from available functions.
If Batching mode is deselected or a batch is running, Totals sign Σ disappears from upper display, batching
no input is possible. values ZI, Zd and Zb are not longer available but
When presetting batch setpoint via fieldbus remain stored.
(Parameter I07 Batch Source = FB), no input is
possible either. This also applies to the input of batch
number and make-up setpoint.. Conditions: Batch complete, or aborted using
“Abort Batch” function, scale OFF.

P Prepare setpoint input.


GT Call function distributor.

f
Select “Deselect Batch” function.

19 Enter setpoint.
Max. 9 digits including decimal point.
Acknowledge.

The unit is that of Counter 1.

f
The “Select Batch” function lets you reactivate
Acknowledge input. batching mode.
The old ZI, Zd and Zb values can be viewed again.

EO Setpoint
Zb = - - - - - - kg
Abort Batch

Lets you abort a running batch, i.e. batching


immediately stops.

N Abort input; old setpoint is maintained.


Batching mode remains selected.

New batch starts upon next start command, old batch


is not resumed.
O Delete faulty digits. The “Reload” function lets you complete old batch.

GT Call function distributor and select “Abort


Batch” function.
Start and Abort

g Start batch, process starts.


f Acknowledge.

Display ZI : moves from 0 towards


You can also abort batch using contact P02.
setpoint
Display Zd : moves from setpoint
towards 0

B Abort batch.

Batching continues upon next Start


command.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Control
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 11
VDM INTECONT PLUS

Reloading Batch Number Nb

Lets you add a specified amount to a complete batch. Enter batch number. Number increments by 1 upon
start of every new batch.
Conditions : Running batch complete, scale Number is printed in batch report and can be viewed
OFF. No batch report. in lower display.
Reloading operations belong to previous batch and
Display ZI : Batch actual value increments from are not counted.
value achieved.

Display Zd : Batch residual value keeps value GT Call function distributor.


Select “Batch Number” function.
achieved.

Display Zbn

Display Zdn
:

:
Make-up setpoint

Batch residual value of make-up


f Acknowledge.
Prompt for input of
amount. Nb = ——- is output.
Zdn = Zbn - make-up amount
reloaded f Acknowledge input.

All displays can be scrolled into lower display field.


Zdn and Zbn are available only until start of next
N Abort input.
Old number is maintained.
batch.
You can also change current number during batching.
GT Call function distributor.
Select “Reload” function.

f Acknowledge function.
System prompts for input of reload
setpoint in kg or t. Loading By Sight
The unit is that of counter 1.

P
Batch report can be printed only when a batch is
Change setpoint Zbn before start of complete (setpoint reached).
reloading.

gB
If you wish to batch an amount not previously
Start or abort reloading. determined and print the result, follow these steps:

1. Call “Select Batch” function.


If reloaded batch is complete, next Start command 2. Select very high batch setpoint, e.g. 999999999
starts a normal batch. kg.
To repeat reloading, re-call function. 3. Scroll batch actual value ZI into lower display field.
The “Abort Batch” function lets you also abort 4. Start scale.
reloading.
5. If amount ZI is reached, stop scale.
6. Call “Stop Batch” function.
7. Start printing (see “Print Batch”).

The “Reload” function can be performed only before


print command.
For next batch, follow steps 4...7.
0842

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 12 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Batch number : Consecutive number NB of scale


Print Batch Report
Events : Events available during printout
The printing functions require an option card to be
present.

Print Batch Print Counter Readings (FMZ)

Start of printout disables the “Reload” function for the Identical with batch report; however, the title is
batch in question. “Quantity Report”.
Function can be called only in Batching mode.
Batch number, setpoint and actual value are printed
Printing can be started: only if Batching mode is selected.

1. Manually via function distributor To call:


2. Automatically, after each complete batch
1) Select “Print FMZ” function.
(Parameter I 06).
Unlike “Print Batch”, report can also be printed
GT Call function distributor.
Select “Print Batch” function.
during batching.
2) Automatically upon each event printout

f
(Parameter J 02 = YES)
Start function.

N Abort printing.

Batch Report

07.07.03 11:45:10

Batch setpoint 0.150 t


Batch act.value 0.150 t
Counter 1 0.806 t
Counter 2 806.47 kg
Batch number 40

Events
E1 Power Failure M01

07.07.05 : Date and time

Batch setpoint: Preset batch amount

Batch act. value: Amount batched

Counter 1 : Totalizing counter 1


0842
Counter 2 : Totalizing counter 2

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Control
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 13
VDM INTECONT PLUS

Print Parameters Print Events

Lets you print out parameter list complete with current Parameter J 02 lets you decide whether event
values. messages are to be printed or not.
Parameter values varying from default settings are
cross-marked (*). Eligible settings :
As Appendix, a list of possible events and current
hardware assignment is printed. 1. No printout (NO)
2. Print events (Error)

GT Call function distributor.


Select “Print Parameters” function.
3. Print events and counter readings (YES)
(see “Batching”)

f Start function.

N Abort printing at any time.


30.04.03 11:45:21
30.04.03 11:59:01
L1 W1 à I < MIN
L1 W1 ß I < MIN

PRINT PARAMETERS L1 : Event code


INTECONT PLUS VDM 20600-00 2063 W1 : Message class, e.g. WARNING 1
−> : Event has occurred
03.06.05 7:39:25
<— : Cause removed; event
BLOCK A Scale Definitions acknowledged, if required.
01 Language ENGLISH I < MIN : Explanation
02 Units SI

BLOCK B Rated Data


01 Feed Rate Unit ——— kg/h
02 Nominal Feed Rate * 1,000 t/h Event is reported on INTECONT display as long as
etc.
available.

For details, see “Event Messages”.

0842

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 14 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Status Report
STATUS REPORT INTECONT® PLUS
Printable at any time, the status report includes most 03.06.03 13:37:12
significant status values and event messages output Software : VDM 20600-00 2063
Hardware version :1
after last printout. If status is printed for the first time, Option card version :1
counting starts from last power-on of INTECONT. Station address :1
-------------------------------

GT
Mode OP : NO
Mode Simulation : NO
Call function distributor. Scale ON : NO
Alarm : NO
Select “Status Report”. Voltage ON-time : 35 h

f
Scale ON-time : 23 h
Counter 1 : 5635 kg
Start function. Counter 2 :6t
Counter 3 :6t
-----------------------------------------------------------

N
Events after last status report

2 * S02 No Release
Abort printing at any time.

Voltage ON-time
Total voltage ON-time

Scale ON-Time
Total ON-time of measurement and INTECONT

Events after last status report


Number and type of events since last report printout.
If report is printed for the first time, counting starts
from power-On.

Counters 1, 2, 3
Totalizing counters 1-3

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Control
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 15
VDM INTECONT PLUS

Program Running:
Zero Setting

The zero setting program lets you acquire the 0o >0< 70 %


measuring system’s zero point error over a settable Tarkor 1.12 %
time.
The acquired value is used to correct the current
measuring result during operation.

Effects:
Upper display : Residual run time in % of total run
1. During zero setting, totalizing counters stop. time
2. Analog value is set to elevation value.
3. Events continue being monitored. Lower display : Zero point error related to nominal
feed rate

Conditions:

1. No material flow
N Abort program at any time.

2. Scale turned off Program Complete:


(prefeeder, if present, closes).
3. Measuring wheel running
Controlled measuring wheels automatically start
upon start of zero setting program and stop when 0o Dev. 2.45%
Tarkor 3.50 %
zero setting is complete.
Measurement starts some seconds after start of
measuring wheel.

Follow these steps: Upper display: Deviation of zero point from


previous zero setting operation

G
in % of nominal feed rate
Call function distributor.
dev = + : error increased
dev = - : error decreased

TU Scroll >0< (zero set) into lower display


field.
Lower display: Mean value of total zero point in %
of nominal feed rate

f Start function.
f Accept “Tarkor” result and enter into
Parameter D 05.

N Abort at any time


N Reject result, i.e. scale not tared.
(controlled measuring wheels cut off)
Special Messages:

1. OFF INTECONT is still ON

2. ABORTED Zero setting result has not be


accepted
3. VALUE TOO BIG Zero setting result has
exceeded specified limits
(Parameter H03). 0842
Result is rejected.

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 16 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Read Parameters

Parameters are defined as variable characteristics or


data used to match the INTECONT to the application.
Parameter input is protected by password.
The “Read Parameters” function lets you view all
parameters without jeopardizing the operating safety.

The parameters are organized into function blocks A ,


B... and consecutively numbered within a block.

GT Scroll “Programming” function into display

f
field and acknowledge.

Tf Select “Read Parameters” sub-function.

Display shows title of first parameter block.

Scale Definitions
Block: A

TU Move through parameter blocks A, B...

fT Move through parameters within a block.

Nominal Feed Rate


B02 1000.0 kg/h

N Return to blocks.

N Return to normal displays.

For details, see “Enter Parameters”.


0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Control
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 17
VDM INTECONT PLUS

This page left intentionally blank

0842

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 18 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

3. Control Overview

RUNNING MESSAGE, OPERATING STATUS


EVENT MESSAGES

Z1 = FEED AMOUNT
P = FEED RATE

ACKNOWLEDGE

READY { POWER ON
CPU OK
O Z1 = 362,5 kg ABORT
E1 I = 1 0 0 0 kg/h FUNCTION
ALARM

MIN

MAX START
STOP PREPARE FUNCTION
START ENTRY

RESET
PRESELECT LOWER
COUNTER
ENTRY

FUNCTION DISTRIBUTOR

Status Displays (Upper Display Field)

In normal mode, totalizing counter Z1 is displayed.

¦ Point rotates Scale (totalization) started

Control Keys:

gB Start/stop totalization (if selected)

U SCROLL Select lower display and functions.

T
1. Counters Z2, Z3 4. Measured load Q
2. Feed rate I 6. Batch displays Zb, ZI, Zd, Nb, Zbn, Zdn
3. Feed rate Ir in %

i RESET Reset totalizing counter.


1. Enter number of desired counter (1 or 2). Counter 3 cannot be reset.
2. Acknowledge input with ENTER key, or
3. Abort with ESCAPE key, or
4. Delete faulty input with DELETE key

G FUNCTION Call function distributor and event messages.


1. Select desired function using SCROLL keys.
If an event is available, “Display Events” function is already selected.
2. Activate function with ENTER key.
3. Pass through available event messages with SCROLL keys.
4. Return to normal display with ESCAPE key

0842 O DELETE Acknowledge event message, delete input.

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Control Overview
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 19
VDM INTECONT PLUS

N ESCAPE Abort function, return to normal displays.

f ENTER Acknowledge input, e.g. parameter.


Start function, e.g. Display Events (see FUNCTION).

P DATA Prepare input, e.g. parameters

Lower display field shows event message, if any, e.g. symbol S2 = No Release.

List of Events

sorted by display priority.

System Messages S1 Memory Error *


S2 No Release
S3 Maint. Scale Run
S4 Maintenance Int. Elec
S7 Simulation Active
S9 Data Link Host

Batching B1 Out of Tolerance


B9 Linearization

Electrical System E1 Power Failure


E6 External Input

Calibration C1 L/C Input *


C5 Tare Corr. > MAX

Maximum H1 I >MAX
H4 L/C Input > MAX

Minimum L1 I < MIN


L7 WZ Eingang <MIN

I = Feed rate
L/C = Load cell

* fault in device or cabling

0842

Transmission to third parties and reproduction


Control Overview Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 20 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

5. Technical Data

n Panel-mounting unit VEG n Surface-mounting unit: with panel mounting unit


20600/20610 VEG 20...

Front panel : 96 x 288 mm n Wall-mounting housing


Panel cut-outs : 88 x 282, wall thickness
max. 10 mm Measuring
Mounting depth : min. 225 mm systems: width x height x depth
(including 50 mm for 410x330x236mm
connectors) Feeding
Protected to : IP 20, front to IP 65 systems: width x height x depth
Material : plastic grey to RAL 7022 500x600x300mm
Display : fluorescent, 2 lines of 20 Protected to : IP 65
characters, 6 mm high Material : steel sheet, 1.5 mm, grey
Keyboard : flexible membranes with Voltage supply : 90...264V/50Hz...60Hz
tactile touch Extension : Feed unit controller
Signal lamps : LEDs, 2 x green, 3 x red
Power supply : 24 V(DC) +50 % -25%, n Environment
max. 1 A,
Temperature : -25 °C ... +45 °C,
no fuse, pole-reversal
tested to -40°C
protective circuit
Humidity : Class F (DIN 40 040) *
Ext. power supply : 90...264V/ 50HZ...60HZ
Interference :
immunity to IEC 801
Interference
suppression : to VDE 871, EN 55 011
P = 100.00 kg/h
I= 0 kg/h
Housing safety : to IEC 348
EC recommen-
dations : CE label
* Tropical version (class R) upon request

n Storage temperature

-40 °C ... +60 °C

n Connectors

Plug/screw connectors (Phoenix Combicon),


non-confusible

n Control outputs

Number : 8 N/O relay contacts


Base board : 3
Option card : 5
Load : max. 230 V(AC)
8 A resistive load, 1 A
inductive
0842 If error message “CPU Not OK” is output, all contacts
open.

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Technical Data
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 21
VDM INTECONT PLUS

n Control n External totalizing pulse counter

Number : 5 Frequency : max. 10 Hz


Base card : 3 Pulse length : selectable 50...1000 ms
Option card : 2 Output : 24 V, max. 100 mA
Type : 24 V(DC) +/-30 %, 5 mA, optionally active low or
galvanically isolated active high,
galvanically isolated,
short-circuit-proof, limited to
n Control inputs (NAMUR) apr. 350 mA,
negative amounts are stored
Number : 2 internally and must be
Type : NAMUR (DIN 19234), compensated by positive
short-circuit and cable amounts before new pulse is
breakage monitoring output.
This ensures integral
n Analog output accuracy also with minimal
belt load.
Number : 2
Base card : 1 n Serial printer interface
Option card : 1
Current : raise ...20 mA impressed Number : 1 (option card)
Raise : 0... <20 mA Type : RS 232 (V24), max. 38400
Load : max. 500 ohms baud
Reference : 0 V by user, Data format : 8 data bits, 1 stop bit, no
galvanically isolated parity
Resolution : 12 bits +/- 1 d Isolation : galvanically non-isolated
Connectors : Phoenix MSTB, contat
If error message “CPU Not OK” is output, output
spacing 3.5 mm, max.
signal turn 0 mA. 1.5 mm2
Character map : ISO-Latin-1 (ISO-8859-1)

n Load cell connection


n Analog input
Voltage supply : +/- 6 V AC (+/-3 %)
Number : 1 (apr. 66 Hz),
Current : raise ...20 mA impressed short-circuit-proof
Raise : 0... 20 mA Measuring cycle : 100ms
Load : 500 ohms Resolution : 24 Bit
Reference : 0 V internal, Load : R (load cell) = min. 80 ohms
galvanically non isolated Cable length : max. 30 % voltage drop,
Resolution : 10 bits +/- 1/2 d max. 500 m
Acuracy: <0.4% over entire Measuring range : -20mV....+50mV
temperature range with VLW:
-1.6mV...min. 32mV

0842

Transmission to third parties and reproduction


Technical Data Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 22 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

n Serial interface for service PC

Number : 1
Type : RS232; RS422 or RS 485
max. 19200 baud
Data format : 8 data bits, 1 stop bit, odd
parity changeable to even or
no
Isolation : galvanically non-isolated
Connectors : Phoenix MSTB, contact
spacing 3.5 mm, max. 1.5
mm2 or 9-pole D-Sub HD20

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Technical Data
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 23
VDM INTECONT PLUS

This page left intentionally blank.

0842

Transmission to third parties and reproduction


Technical Data Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 24 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

5. Characteristics

n Power Failure n Displays

Scale data, calibration values, counter readings and Upper display : Totalizing counter 1
pulses pending remain stored after power failure for Lower display: Totalizing counters 2...3
an unlimited period of time. The internal clock Feed rate absolute I
continues running for approx. 5 days. Feed rate relative Ir
Measured load absolute
Measured load relative
Batch data
n Dialog Language
for error messages, operation, and service Select lower display using cursor keys.
programs.

Eligible : DEUTSCH
ENGLISH n Signal Lamps (top down)
FRANCAIS
ESPANOL VOLTAGE OK (green)
ITALIANO PROCESSOR OK (green)
ALARM (red)
MIN (red) feed rate MIN limit
MAX (red) feed rate MAX limit
n Units (selectable)

SI units : kg, kg/h n Event Messages


t , t/h
m, cm Events and faults are displayed in form of an
NON-SI units : lb , lb/h alphanumeric code.
t , t/h Call clear text of events via keyboard.
f , inch Events are organized into Alarms, and Warnings
(see Parameter Shortlist) with and without acknowledgement. Alarms stop
scale, warnings don’t.

All alarms are additionally reported via relay


n Start/Stop Totalizing Counter outputs.

Select using Parameter B03.


n Operating Philosophy

Operator prompting through multi-level menus.


n Release, Emergency Stop Important configuration and calibration functions
are protected by password.
Functions are realized using a digital input O01.

n Simulation Mode

Lets you operate your system without mechanical


equipment, e.g. for system testing.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Characteristics
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 25
VDM INTECONT PLUS

n Zero Setting n Calibration

Zero setting is performed by an automatic Calibration as such is not required. All you have to
program. No material is required. do is enter some constructional data of load cells,
Program can be started speed transducer, belt inclination, etc. INTECONT
uses these data to compute all requisite display
1. manually via keyboard normalisations.
2. automatically with closed prefeeder Check, or recalibration, can be effected in two
ways:
Max. admissible zero setting amount is monitored.
a) Using material

Enter check result into INTECONT, and


measurement value will be corrected.

n Taring b) Using check weight


Designed to zero the basic tare load, the taring A special check program lets you check
program on principle has the same function as the normalizations, and correct them if technical
zero setting program. However, tare elevation is data or not exactly known. In later operation,
not monitored, and the call is protected by program can also be used to show technical
password. modifications.

n Zero Drop Out n Digital Inputs


Suppresses totalization upon measurements
around zero point, so that counter stops with small Number Name Default
feed rates. O03 DI Ackn. Events DI1
Deselect function if not desired. O01 Release DI2
B03 START Source —-(OP)
n Display Filters
O02 DI Stop Batch —-
O02 DI Ext. Event —-
can be defined individually for feed rate and
O05 DI Start —-
measured load.

n Digital Outputs
n Maintenance Hints
Nummer Name Default
through display of event s
P04 DO I-MIN D04
1. Voltage ON-time P05 DO I-MAX DO2
2. Scale ON-time P01 DO ALARM D03
P02 DO Prefeeder ON D06
P03 DO Feeder ON D01
n Adaptions P07 Full Feed —-
P08 Dribble Feed —-
The electrical system needs not be redesigned P06 DO Batch Active —-
nor adapted.

0842

Transmission to third parties and reproduction


Characteristics Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 26 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

6. Setting Programs

Function Distributor Programming and Calibration functions lead to further


menus you can move through using cursor keys.
The function distributor lets you call further functions
and/or dialogs. B = If Batching mode is selected, additional
functions can be accessed in main

G
distributor.
Call function distributor.
If an event is available, “Display Events” Abort Batch
is displayed; if no event has occurred, Deselect Batch
display shows function selected last. Batch Number

f
Print Batch
Start function. Reload

N Return to normal displays, or abort


function.
S = Calibrating functions protected by
password. Prompt for password input is
output after call of function.

E = If an event is available.
F u nc t i o n
DisplayEvents
With opposed functions, e.g. START/STOP, only the
one currently accessible can be called.

Moving through function distributor has no effect on


weighing functions.

TU Move through function distributor.

Display Events E
Display Check
START/STOP Feeder
Service Values
START/STOP Keyb. Mode
Select Batch B
EasyServe active/deactiv
>0< Zero Set
Programming
Calib.Functions S
Print FMZ

Read Parameters
Enter Parameters S
Load Default Par. S
Print Parameters
Print Stat. Rep

START/STOP Simulation
Tare
CW: Weigh Check
0842 Set Time

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Setting Programs
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 27
VDM INTECONT PLUS

Calibrating Functions TW Tare

Menu item “Calibration Functions” lets you access 3 The taring program acquires zero point error of
functions: complete measuring system over a settable time
(Parameter C 01, default = 30 s).
1. TW Tare INTECONT uses this value to correct measuring
2. CW: Weight Check result during operation.
3. Set Time In contrast to zero setting program, zero setting range
is not monitored nor limited.
4. START/STOP Simulation
Taring program deletes the zero setting result.
All functions are protected from unauthorized use by
password.
The operating sequence is the same for all programs. Effects: 1. During taring, no totalization

G
takes place.
Call function distributor. 2. Analog output is set to

TUf
elevation value.
Scroll CALIBRATION 3. Events continue being
FUNCTIONS into lower display monitored.
field and acknowledge. Conditions: 1. No material flow.

f
2. Scale cut off
...... Enter password 07734. (prefeeder closed, if present).

Follow these steps:

Display shows one of the setting programs, e.g. TW:


Tare. Gf Function distributor, Calibration functions,
password (see “Calibration Functions”).

TU Scroll “TW: Tare” function into lower


display field.

f
CALIBRATION FUNCTIONS
TW: Tare
Start function.

N Abort at any time

f Start setting program.

N Return to normal displays.


For apr. 2 min., Calibration
menu can be recalled without
password input.

0842

Transmission to third parties and reproduction


Setting Programs Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 28 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Program running:
CW Weight Check

This program lets you check the INTECONT


>0< TW: 9 0. 2 % measuring range.
Tare 5 2. 3 5 Load measuring system with a known check weight
and acquire load cell load mean value over a certain
time.
INTECONT compares result with specified setpoint
Upper display: Residual run time in % of total run and displays value.
time No automatic correction takes place.

Lower display: Continuously meaned tare in % of Effects:


nominal measured load
1. During run time, no totalization takes place.
Program complete: 2. Analog output is set to elevation value.
3. Events continue being monitored.

Conditions:
>0< Dev. 2.45 %
Tare 3.50% 1. Taring or zero setting performed
2. Effective check weight entered into Parameter C
05
3. Check weight applied in provided point
4. Scale cut off
Upper display : Deviation of tare value from
previous taring operation
in % of nominal measured load Sequence:
dev = +: tare increased
dev = - : tare decreased
Gf Function distributor, Calibration function,
password (see “Calibration Functions”)

Lower display : Mean value of total tare


in % of nominal measured load
TU Scroll “CW: Weight Check” into lower
display field.

f Accept taring result and enter value into


f Start program.
Parameter D 04.
Tare correction (D05) is set to zero.
N Abort at any time

N Reject result, i.e. scale not tared.

Special Messages:

1. STOP if INTECONT is still started


2. ABORTED if taring result is not acquired
yet

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Setting Programs
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 29
VDM INTECONT PLUS

Program running Evaluating result:

Error < 1 % : COR = 0.99...1.01


Scale OK, no further action
required.
>. CW 51.4%
SET/ACT 0.9842%
Error < 5 % : COR = 0.95...1.05
Enter KOR value into Parameter D
02 .
This makes good sense only if
Upper display : Residual run time in % of total run parameter has not yet considered
time result of check using material.

Lower display : Continuously meaned SET/ACT Error > 5 % : COR < 0.95 or COR > 1.05
measuring result Multi-percent deviations suggest
wrong data input (e.g. belt
inclination not exactly known, lever
arms) and/or mechanical faults
Program complete (misalignment, distorsions).

Check does not consider Parameter “Weight


Correction" D 02, so that check program will
>. CW 5.325 %
COR 0.9915% indicate same error quotient COR after check.

Feed rate display for check weight:

Upper display : ACTUAL measured load in kg

Lower display : Mean value COR of SET/ACT over


total run time
I = Feed rate in t/h
C05 = Check Weight in kg
C04 = Device Constant in kg/(t/h)
D02 = Weight Correction

fN Exit program.
Since result is not acquired automatically,
the two keys are equivalent.

Special hints:

1. STOP if INTECONT is still ON


2. ABORTED after exit of program

* Lets you check scale zero point without check


weight Display format: xxxxxxx,yy kg
0842

Transmission to third parties and reproduction


Setting Programs Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 30 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Simulation Mode Set Time

Simulation Mode lets you check all scale functions Unlike the other programs, date and time can be
without material at the time of commissioning. changed in Start and Stop states of scale and be read
During simulation, scale is cannot operate in normal off under SERVICE VALUES.
mode.

Gf Function distributor, Calibration functions,


Gf Function distributor, calibration functions,
password (see “Calibration Functions”).

TU
password (see “Calibration Functions”).
TU Scroll “Set Time” into lower display field.

f
Scroll “Start Simulation” into lower display
field. Call menu.

f Start program. N Abort at any time.

Display :
Event message S7
In upper line, “=” symbol
0 3 Enter year, e.g. 03, month, day, hour,
minute, and second.
flashes.

f
Function can be cut off in the same way (STOP
Simulation). Acknowledge every input.
When seconds have been
acknowledged, new date is acquired.

Features: Complete date is displayed for some seconds.

1. All operating functions can be performed. O Delete digit entered last.


2. Feed rate actual value is set to nominal rate.
3. Measured load measurement is active.
4. All control inputs and outputs operate in normal After power failure, time remains stored for min. 5
fashion. days.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Setting Programs
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 31
VDM INTECONT PLUS

This page left intentionally blank

0842

Transmission to third parties and reproduction


Setting Programs Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 32 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

7. Service Values

The Service table includes detailed system


information. Call does not affect weighing functions.
6. Inputs switching conditions

GTf Call SERVICE VALUES


function and start.
I+ : DI = 1 1 1 1 1 + 0
“1” = Contact closed
“0” = Contact open

TU
Inputs 4 + 5 on option card
Move through service values. “N” = No option card

Inputs 6 + 7 are designed as Namur inputs

N
(external input)
Return to normal displays.
“+” short-circuit; “-” cable breakage;
“1” = sensor covered; “0” = sensor free

Displays:
7. EL = 22 h
1. VDM 20600-04 2775 Version number
2. HW = 1 Hardware version Voltage ON-time
3. Opt.K: 0 (no option card)
1 option card available) Monitoring: Parameter K 01, Message S4

8. ED = 19 h
O Z1 = 1500100 kg
Opt..IND : 1 Scale On-time

Condition : Totalization ON
Monitoring : Parameter K 03, Message
S3
4. Date and time

5. Relay outputs switching conditions 9. aw = 30.988 %

I +: DO = 1 1 1 0 0 0 0 0 Load on load cells related to total of load cell


rated capacities.
“1” = Contact closed If value exceeds 100%, load cells are
“0” = Contact open overloaded.
Outputs 4-8 on option card From 110 % onward, Message H4:
“N” = No option card “L/C Input > MAX” is output.

10 wz = 1.383257 mV/V

Unnormalised output value of load cell


amplifier (Gross)

11. R_wz = 300 ohms


0842
Load cell resistance value

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Service Values
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 33
VDM INTECONT PLUS

12. AO1 = 4.15 mA

Analog output 1 output current

13. AO2 = 10.00 mA

Analog output 2 output current


(on option card)

14. ZE = 53

Pulses output across pulse output for external


totalizing counter, counted after command
“Reset Counter 1".

15. ZO = 1
Pulses still to be output.
If value keeps exceeding zero, pulse
frequency is higher than 10 Hz.
Increase weighting of smallest display digit of
Counter 1 (Parameter B 10).

16. AI = 12.54 mA

Analog input input current .

17. CS = 10851

Scale software check sum

18. CS_b = 10851

Check sum cyclically recomputed. If value


“CS_b” is unequal to “CS”, a serious fault is
given. Contact the Schenck Service.

19. Iun = 4876 kg/h

Unlinearized feed rate

20. ES-Version = 11

Current EasyServe Version

0842

Transmission to third parties and reproduction


Service Values Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 34 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

8. Parameterization

General Information
Parameters are variable characteristics or data used There are two types of parameter:
to match INTECONT to the application.
Selection parameters
Display units and format
Limit values
Nominal and calibration data, etc. Let you select from various options, e.g. WARNING,
ALARM.
Some parameters can be set in accordance with
requirements (e.g. display formats), others have to be Numeric parameters
taken from Spec Sheet supplied.
During parameter input, all functions are maintained.
However, during operation, only parameters with no Enter numeric value, e.g. nominal feed rate.
influence on measurement, e.g. display filters, should
be changed.

Default Values
Call Parameter Menu

All parameters are preset with default values. These


are proven suggestions and can normally used as
G Call function distributor.
defined.
The default values can be loaded using sub-function
TUf Scroll PROGRAMMING into
lower display field and
“Load Default Parameters”. acknowledge.
Identification TUf Select ENTER PARAMETER
function.

Bf
The parameters are organised into function blocks A,
B, ... and, within a block, described by Enter password 07734.

name
number 1, 2, 3 ..
and Display shows title of first parameter block.
value.
Values differing from default are identified by a *
before the block letter. Dialog Behaviour
Block: A

Nominal Feed Rate


B02 1000.0 kg/h

N Return to normal display.


For apr. 2 min., Parameter
menu can be recalled without
password input.
0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 35
VDM INTECONT PLUS

Select Parameters Enter Parameters


1. Block Letter
P Prepare input.

TU Selection parameter:
value flashes.
Rated Data Scroll desired value into lower
Block: B display field.

46 Go to the left (4) or to the right


(6); see “Hardware
Configuration”.

B9 Numeric parameters:
TU Move through blocks A, B ... up
and down.
Feature - - - - - - - - - - - - - - - -
Enter value using number keys.

f
Block letter flashes.

f Select block.
Acknowledge input.
Next parameter is displayed.

O
Display shows parameter
selected last. Delete digits.

2. Parameter Number N Abort input.

OFF key “0" is always active; ON key ”I" only if


parameter input is complete.
Nominal Feed Rate
B02 10000.0 kg/H

TU Move through parameter


numbers within a block.
Parameter number flashes.

f Move through parameter


numbers independent of block
(UP only).

NN Return to block titles.


Return to normal mode.

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 36 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Hardware Configuration Load Default Parameters


When parameterising the hardware, the source Lets you load the default setting.
determines whether unit, channel and level must be Function is protected by password and YES/NO
indicated or not. The table below will assist you in prompt.
configuring the hardware.
Attention!
Source Unit Channel Level All changes to parameters and calibration values
get lost.
FB

OP
G Select PROGRAMMING function,
call DEFAULT PARAMETERS.
v


B1 YES = 1
NO = 0
DI I+ DI1-DI7 HI, LO

DO I+ DO1-DO8 HI, LO f Acknowledge selection.

AI I+
Power Failure
As you can see, with “Fieldbus” (FB), “Operator
Panel” (OP), “Speed” (v) and “Not Assigned” (—) no Parameters remain stored for an unlimited period of
additional input is required. time.
“Digital Inputs” (DI) and “Digital Outputs” (DO) require
unit, channel and level to be indicated.
With “Analog Input” (AI), the unit is firmly set to I+.

Sample:

Parameter B06 “START Source" determines from


where the scale is started.

Description Source
B06 START Source OP
Alternatives FB, DI

On standard the scale is started from the INTECONT


keyboard.
Alternatively, fieldbus or digital input (DI) can be
selected. If DI is the desired source, additionally
indicate channel and level (see table above). The unit
is firmly set to I+.

4 Keys 4 (go to the left) and 6 (go to the

6
right) let you shift between source,
channel and level.
0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 37
VDM INTECONT PLUS

Parameter Overview 06 Limit Value AO 2 20.00 mA

This list applies to software: VDM 20600-05


BLOCK F Limit Values
BLOCK A Scale Definitions
01 Value for I-MIN 5.0 % Io
01 Language ENGLISH 02 Event Class I-MIN W1 (L 01)
02 Units SI 03 Value for I-MAX 120.0 % Io
03 Password (07734 or 7734) 04 Event Class I MAX W1 (H 01)
04 2.Password 2889
05 Feeder ON/OFF active
06 Keyb. Mode ON/OFF active BLOCK G Filter Setting
07 Batch ON/OFF active
08 >0: Zero ON/OF active 01 I Display 3.0 s
09 EasyServe ON/OFF active 02 I Analog Output 3.0 s
10 Totalizer1 ON/OFF active 03 Q Display 3.0 s
11 Totalizer2 ON/OFF active 04 L/C FILTER 1.0 s
05 Afterfl. Time 5.0 s
BLOCK B Rated Data

01 Feed Rate Unit ——— kg/h


02 Nominal Feed Rate 0200.000 t/h BLOCK H Additional device
03 START Source OP
04 FMZ1 Unit ———- t 01 AUTO Zero Active NO
05 FMZ 1 Pulse Dur. 0 ms 02 Autom. Zero Limit 1.00 % Io
06 FMZ 2 Unit ———- t 03 Zero Set Limit 5.00 % Io
07 FMZ 3 Unit ———- t 04 Tare Corr. MAX W1 (C 05)
08 DO Pulse Counter — 05 ZDO Active NO
09 Pulse Weighting 0.0 kg 06 ZDO Limit 1.00 % Io

BLOCK C Calibrating Data#


BLOCK I Batch Mode
01 Calibration Time 30.0 s
02 L/C Charac. Value 2.0000 mV/V 01 Batch Dribble FD 100.000 kg
03 L/C Rated Cap. 60.000 kg
04 Device Constant 0.0400 kg/h 02 Batch End 0.000 kg
05 Check Weight 1.000 kg 03 Adaption fact. 0.5
04 Batch Tolerance 100000.000 kg
BLOCK D Calibrat. Results 05 Out of Tolerance W1 (B 01)
06 AUTO Print NO
01 Nominal Platf. Load 8.00 kg 07 Batch Source OP
02 Span Correction 1.0000
03 Total Tare 0.00 kg/h
04 Basic Tare N 0.00 kg/h BLOCK J Printer Setting
05 Tare Correction T 0.00 kg/h
06 Material Corr. 1.00 01 Baud Rate 9600
02 Print Subtotal Error
BLOCK E Analog Output 03 Print Page Length 72

01 Source AO 1 I
02 Elevation AO 1 4.00 mA
03 Limit Value AO 1 20.00 mA
04 Source AO 2 Q
0842
05 Elevation AO 2 4.00 mA

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 38 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

BLOCK K Maintenance Int. 11 Contr.Magn.Elev. 0.00 mA


12 Position at Stop 0
01 Maintenance Elec. 3000 h 13 Start-Up 0.0 s
02 Event Maint. EL. W1 (S 04) 14 Store NO
03 Maint. Scale Run. 3000 h 15 Setpoint Range 20.00 mA
04 Event Maint. Run. W1 (S 03) 16 Setpoint Offset 0.00 mA
17 Bypass 10.00 mA
18 Setpoint Filt. T1 0.0 s
BLOCK L Comm. Fieldbus 19 Setpoint Filt. T2 2.0 s

01 Protocol Type NO BLOCK O Linearization


02 Host timeout 5s
01 Linearization ON NO
03 Comm.-Error Host ALARM (S 09)
02 Lin.-S1 25.00 % Io
04 Word sequence I:std/L:std
03 Lin.-I1 25.00 % Io
05 Byte sequence Low-High
04 Lin.-S2 50.00 % Io
06 Configuration FIXED
05 Lin.-I2 50.00 % Io
07 Address 1
06 Lin.-S3 75.00 % Io
08 Resolution 4096
07 Lin.-I3 75.00 % Io
09 Physics RS 485
10 Baud Rate 9600
11 Format Data 8-E-1
12 Adresse 16 BLOCK M Events
13 FLOAT-Format IEEE
14 Address 63 01 Power Failure A (E 01)
15 Baud Rate 125K 02 Memory Error A (S 01)
17 S5 Physics RS422 03 L/C Input A (C 01)
22 Hardware VxB020 04 No Release W1 (S 02)
05 L/C Input MAX A (H 04)
BLOCK M Events 06 L/C <MIN A (L 04)
07 Simulation aktiv W2 (S 07)
01 Power Failure A (E 01) 08 Error Ext. Event A (E 06)
02 Memory Error A (S 01)
03 Tacho Input A (C 02)
04 Namur Err. Tacho A (E 02) BLOCK N Linearization
05 L/C Input A (C 01)
06 No Release W1 (S 02) 01 Linearization ON NO
07 L/C Input MAX A (H 04) 02 Lin.-S1 25.00 % Io
08 Simulation active W2 (S 07) 03 Lin.-I1 25.00 % Io
09 Setpoint Limited W1 (S 08) 04 Lin.-S2 50.00 % Io
10 Error Ext. Event A (E 06) 05 Lin.-I2 50.00 % Io
06 Lin.-S3 75.00 % Io
BLOCK N Controller 07 Lin.-I3 75.00 % Io
08 Lin.-S4 100.00 % Io
01 P-COMPONENT 0.02000 mA/%
02 I-COMPONENT 3.0 s 09 Lin.-I4 100.00 % Io
03 Contr.Dev.Filter 3.0 s 10 Lineariz. error W2 (B 09)
04 Contr. Dev. Time 20.0 s
05 Max. Contr. Dev. 5.0 %
06 Deviation factor 1.0
07 Contr. Deviation W1 (B 02)
08 Controller Ltd. W1 (B 03)
0842
09 Lower Limit 0.00 mA
10 Upper Limit 20.00 mA

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 39
VDM INTECONT PLUS

BLOCK O Digital Inputs BLOCK S: Fixmode Parameter

01 Release DI I+.DI2 HI 01 ID Preset Value 1 320


02 DI Stop batch — 02 ID Preset Value 2 352
03 DI Ackn. Events DI I+.DI1 HI 03 ID Preset Value 3 384
05 DI Ext. Event — 04 ID Preset Value 4 596
06 DI Start — 05 ID Preset Value 5 594
06 ID Preset Value 6 598
07 ID Preset Value 7 0
08 ID Preset Value 8 0
09 ID Read Value 1 752
10 ID Read Value 2 784
11 ID Read Value 3 1552
12 ID Read Value 4 1872
BLOCK P Digital Outputs 13 ID Read Value 5 1874
01 DO ALARM DO I+.DO3 LO 14 ID Read Value 6 1888
02 DO Prefeeder ON DO I+.DO5 HI 15 ID Read Value 7 1876
03 DO Feeder ON DO I+.DO6 HI 16 ID Read Value 8 1894
04 DO I-MIN DO I+.DO1 LO
05 DO I-MAX DO I+.DO2 LO
06 DO Batch active —
07 DO Full feed —
08 DO Dribble feed —
09 DO Keyboard Mode —

BLOCK Q Comm. EasyServe

01 Station address 1
02 Physics RS232
03 EasyServe Baudr. 19200
04 Format Data 8-O-1

Block R: Ethernet

01 IP-Address 1 192
02 IP-Address 2 168
03 IP-Address 3 240
04 IP-Address 4 1
05 Net Mask 1 255
06 Net Mask 2 255
07 Net Mask 3 255
08 Net Mask 4 0
09 Gatway 1 192
10 Gatway 2 168
11 Gatway 3 240
12 Gatway 4 0

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 40 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block A : Scale Definitions

A 01 Language A 04 Second password


Range: DEUTSCH Default: DEUTSCH Range: 1000 - 9999 Default: 2889
ENGLISH*
AMERICAN ENG* The password for using a specific system. This
FRANCAIS password allows you to protect the basic functions in
ESPANOL the function distributor (see above). It does not allow
ITALIANO access to parameters or adjustment functions. The
Selection applies to all displays, error messages and changed password is also shown encoded. The
parameters. default value 2889 generates the return display
14389.
* identical
Note: If you forget the second password, you can
enter a new password in the A04 parameter using the
A 02 Units standard password
Range: SI Default: SI
NON-SI A 05 Feeder ON/OFF
Convert displays and parameter inputs from SI units
into American units. Range: active Default: active
not active
Password
American Units SI Units Conversion * 2. Password
lb kg 1 lb = 0.453593 kg Confirm
t t 1 t = 0.907185 t = 2000 lb
f m 1 f = 0.3048 m You can use this parameter to control access to the
inch cm 1 inch = 2.54 cm basic functions of ON/OFF prefeeder.
* You have the options below::

also applicable to compound units, e.g. kg/hr active: Access is always allowed.

not active: Access is never allowed. This function


A 03 Password is not visible in the distributor.
Range: 1000 - 9999 Default: 07734 o Password: Access is available with the standard
7734 password (A03).
The password that secures the INTECONT keyboard Second Access is available with the new
access to parameters and adjustment functions Password: second password (A04)..
can now be changed. The changed password is
shown encoded in the parameter dialog and Confirm: Access has to be confirmed again for
EasyServe. The default value 07734 (or 7734) security reasons.
generates the return display 26574 (this process is
identical to DISOCONT).
Note: The prefeeder also has to be activated with
Note: parameter M01.
If you forget your password, you have to change your
password with EasyServe or report the shown value
of the parameter A03 to Schenck Service to find out
0842
the appropriate password

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 41
VDM INTECONT PLUS

A 06 Keyb. Mode ON/OFF A 09 EasyServe ON/OFF


Range: active Range: active
not active not active
Password Password
2. Password 2. Password
Confirm Confirm

Default: active Default: active

You can use this parameter to control access to the


basic functions of keyboard ON/OFF mode. The You can use this parameter to control access to the
range of values is identical to the A05 parameter. basic functions of EasyServe activate/deactivate.
The range of values is identical to the A05 parameter.

A 10 Totalizer1 ON/OFF
A 07 Batch ON/OFF
Range: active
Range: active not active
not active Password
Password 2. Password
2. Password Confirm
Confirm
Default: active
Default: active

You can use this parameter to control deleting counter


You can use this parameter to control access to the 2. The range of values is identical to the A05
basic functions of batch preselect/deselect. The parameter.
range of values is identical to the A05 parameter.
A 11 Totalizer2 ON/OFF
Range: active
A 08 >0: Zero ON/OF not active
Password
Range: active 2. Password
not active Confirm
Password
2. Password Default: active
Confirm You can use this parameter to control deleting counter
2. The range of values is identical to the A05
Default: active parameter.

You can use this parameter to control access to the


basic function of >0: zero setting. The range of
values is identical to the A05 parameter.

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 42 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block B : Rated Data

B 01 Feed Rate Unit B 04 FMZ1 Unit


Range: - - - - - - t/h Default: Range: ------- t Default: - - - - - - - t
- - - - . - t/h - - - - - - kg/h -----.- t
- - - . - - t/h ----.-- t
- - . - - - t/h ---.--- t
- - - - - - kg/h - - - - - - t *10
- - - - . - kg/h ----- t *100
- - -. - - kg/h - - - - - - - kg
- -.- - - kg/h - - - - - . - kg
Determines feed rate display format - - - - . - - kg
- - - . - - - kg

B10 determines the display format for counter 1,


batching values and pulse weighting for external
B 02 Nominal Feed Rate counter. If no external counter is present, set
Parameter B11 to 0.
Range: 0.0001..230000.0 t/h Default:
200.0 t/h

Reference for limit values and service displays

B 03 START Source
Range: OP Default: OP
FB
DI

To start/stop totalization, there is no single solution:

OP :
From INTECONT keyboard
FB :
Via fieldbus interface
DI :
Using digital input. Default value is DI3.
You can also use any other free digital
input. Digital input operates
edge-controlled, i.e. if scale fails after
Alarm, remove START signal and re-apply.
Dialog function “Keyboard Mode” lets you change
over from selected source to keyboard, and vice
versa.

Note

G05 defines the totalizing counter tracking time.


If Parameter O01 “Release” is set to “- -”,
no release is required.
0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 43
VDM INTECONT PLUS

KEYBOARD
START/STOP MODE

B03
SERIAL FB

FEEDER RUNNING
KEYBOARD &
OP
ST
CONTACT DI START PREFEEDER

vh221904.cdr (dwg)
Release ALARM

B 05 FMZ 1 Pulse Dur.


Range: 0....1000 ms Default: 0 ms

Length of external counter output pulse. Pulse


weighting corresponds to the smallest display digit of
counter 1 (Parameter B04).

B05 < 10 ms : Pulse output is blocked.


All pulses not yet output are
deleted.

Output frequency at nominal feed rate:

PNENN = n
nominal feed rate in kg/h or t/h

Zmin = smallest display digit of counter 1


(B 04) in kg or t B 06 FMZ 2 Unit
Select Zmin (B 04) so that f does not exceed 10 Hz. As with B04; however, for counter 2
Furthermore, pulse duration B05 should be smaller
than 1/f .

B 07 FMZ 3 Unit
As with B04; however, for counter 3

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 44 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

B 08 DO Pulse Counter
Range: — Default: —
DO
The impulse output of totalizing counter 1 can now
also be output via a digital output. The impulse output
of INTECONT on plug X6, pins 8-11 is still used with
default value “—“ and the configured output is used
instead with the alternative DO.
The impulse duration is still determined with the B08
parameter. Readings less than 10 ms block the output
total and readings up to 1 second are set to 1 second
when a digital output is used.

B 09 Pulse Weighting
Range: 0.00 – 100000.00 kg Default: 0.00 kg

The weighting of an output impulse on the impulse


output of totalizing counter 1 can now be set to be
freely selected. The weighting of an impulse
corresponds to the smallest possible digit of counter 1
with default value 0.00 (refer to parameter B07).

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 45
VDM INTECONT PLUS

Block C : Calibrating Data

C 01 Calibration Time C 06 Check Weight


Range: 1...9999 s Default: 30 s Range: 0.010...22 000.0 kg Default: 1 kg

Measuring time for taring and zero settings programs The check weight is used to check weighing system
using calibration program “CW: Weight Check”.

Enter weight acting on load cell through check weight.


C 02 L/C Charac. Value
Range: 0.01...9.9999 mV/V Default: 2 mV/V

Load cell characteristic value (transmission factor)

C 03 L/C Rated Cap.


Range: 0.5000...220000.0 kg Default: 60 kg

Total of load cells rated capacities

C 04 Device Constant
Range: 0.00100...1.0 kgh/t Default:
0.04 kgh/t

Unit: kg h/t = kg / (t/h)

The device constant indicates the correlation of


measured load and feed rate, i.e. load on load cell in
kg / t/h.

Q = Measured load on load cell in kg


I = Feed rate in t/h

GK determines calibration accuracy. For value, see


technical Spec Sheet.

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 46 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block D : Calibrat. Results

D 01 Nom. Platform Load D 04 Basic Tare N


No input Default: 8000 kg No input Default: 0.00 kg/h
max. 10000 kg/h
Computed from rated data B 02 and C 04

Nominal measured load serves as reference for limit Result of taring program
values and zero setting programs.

For computation, see DETAILS chapter.

D 05 Tare Correction T
No input Default: 0.00 kg/h
D 02 Weight Correction max. +- 1000 kg/h

Range: 0.5000...2,0000 Default: 1,0000


Result of manual or automatic zero setting.
Proportionally influences feed rate I measurement
Every taring operation sets D 05 to 0.
I(corrected) = I(measured) ∗ D 02

Function: Correct measuring system through


check using material and
calibration program CW: Weight
Check
D 06 Material Corr.
Range: 0.5000...2,0000 Default: 1

D 03 Total Tare Proportionally influences measurement of linearized


feed rate I.
No input Default: 0.00 kg/h
I(corrected) = I(measured) ∗ D 06
Total tare = basic tare + tare correction
= D04 + D05 Function: Correct feed rate through check using
material

Attention!
If you enter Parameters D 02 ... D 05 in manual, enter
D 02 first.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 47
VDM INTECONT PLUS

Block E : Analog Output

E 01 Source AO 1
X
i = ELEV + (END - ELEV)
Range: I (feed rate) Default: I Xnom
Q (measured load)

X = I, Q Xnom = nominal value

One of these values can be output in analog fashion. Note:

Filters: Parameters G 02, G 04 1) Maximum output current is 20 mA.


2) Minimum output current corresponds to elevation
E 02.
3) In Stop state of scale, output for I is set to elevation
E 02 Elevation AO 1 value; for Q, measurement value is output.

Range: 0.00...20.00 mA Default: 4.00 mA

Output current of 0% value I, or Q. E 04 Source A02


Range: I (feed rate) Default: Q
Q (measured load)

E 03 Limit Value AO 1 See Parameter E01


Range: 0.00...1000.00 mA Default: 20.00 mA

Output current of 100% value I, or Q.


E 05 Elevation A02
Range: 0.00...20.0 mA Default: 4.00 mA

See Parameter E02

E 06 Limit Value A02


Range: 0.00...1000.00 mA Default: 20.00mA

See Parameter E03

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 48 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block F : Limit Values

F 01 Value for I MIN F 03 Value for I MAX


Range: -10...200.0 % Io Default: 5.0 % Io Range: -10...200.0 % Io Default: 120.0 % Io

Related to nominal feed rate B 02 Related to nominal feed rate B 02

If measurement value exceeds MIN limit, event If measurement value exceeds MAX limit, event
message L1 is output. message H1 is output.

Monitoring starts 10 s after start-up.

F 04 Event Class I MAX H1


Range: WARNING 2 Default:
WARNING 1 WARNING 1
IGNORE
F 02 Event Class I MIN L1 ALARM

Range: WARNING 2 Default:


WARNING 1 WARNING 1
IGNORE
ALARM

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 49
VDM INTECONT PLUS

Block G : Filter Settings

I = feed rate G 05 Afterfl. Time


Range: 0.0...2000.0 s Default: 3.0 s
G 01 I Display
During specified time, totalization goes on after scale
Range: 0.0...600.0 s Default: 3.0 s stop.
Feed rate display

All filters are of the first-order type


(exponential), i.e. upon abrupt
change of signal, approx. 2/3
of full scale are reached
G 02 I Analog Output after set time.
Range: 0.0...600.0 s Default. 3.0 s Long times lead to a stable
but slowly refreshing display.
Feed rate analog output

G 03 Q Display
Range: 0.0...600.0 s Default: 3.0 s

Measured load display

G 04 L/C Filter
Range: 0.0...600.0s Default: 1.0 s

Applies to all functions and displays depending on


measured load

0842
Q = measured load

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 50 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block H : Additional Device

H 01 AUTO Zero Active H 03 Zero Set Limit


Range: NO Range: 0.00...100.00 %Io Default: 5.00 %Io
YES Default: NO
Bezug: Nom. Platf. Load D01
Lets you select automatic zero setting.
Max. admissible amount of the total of all manual and
NO : No automatic zero setting zero setting operations.
If limits are exceeded, correction value is not acquired.
YES : Automatic is running, if
1. Measurement is cut off
2. No other setting program is running Monitoring : Parameter H 04, message C5
3. No parameters are input.
Start delay is 60s.

Measuring time : Parameter C 01 H 04 Tare Corr. > MAX C5


Monitorings: Parameters H 02...H04 Range: WARNING 1 Default:
WARNING 2 WARNING 1
Display feature : “0” in upper display field ALARM
IGNORE

Automatic zero setting result exceeds limit H 03.


Value is not acquired.
H 02 Autom. Zero Limit
Range: 0.00...10.00%Q Default: 1%Q

Related to: Nom. Platform Load D01 H 05 ZDO Active


Range: NO
If mean value measured by automatic zero setting
YES Default: NO
function falls below H 02 and H03 over time C01, zero
point is corrected. Active Zero Drop Out (see H 06).
Result: Parameter
: D 05
H 06 ZDO Limit
Range: 0.0...10.00 %Io Default: 1.00 %Io

Related to: Nominal Feed Rate B 02

If Zero Drop Out is active and feed rate exceeds set


limit, value is set to 0.

No display feature.

Conditions: Totalization ON or Afterfl. Time


0842 G 05.

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 51
VDM INTECONT PLUS

Block I : Batch Mode

For detailed batching sequence, see DETAILS chapter.

I 01 Batch Dribble FD I 03 Adaption Fact.


Range: 0.00...220 000 kg Default: 100.000 kg Range: 0.0...1.0 Default: 0.5

If batch setpoint (I 01-I 02) is reached, dribble feed Pre-cut-off amounts I 01 and I 02 are adapted
output (P08) is set. automatically so that the system better fits the
Signal can be used, e.g. to reduce prefeeder rate. situation upon next batch.

The two values are adapted by value


“batch error * I 03".
I 02 Batch End I 03 = 0 : no adaption
I 03 = 1 : full adaption
Range: 0.00...220 000 kg Default: 0.000 kg

If batch setpoint has reached pre-cut-off amount I 02, Intermediate values cause a filtered adaption which is
batching terminates and prefeeder stops. preferable in plants with unprecise repeatability
behaviour.

I 04 Batch Tolerance
Range: 0.0...2200000.0 kg Default:
100000.000 kg
I 02 considers material afterflow, if any.
Related to batch setpoint

Admissible deviation from setpoint. Check takes place


after completion of batch.

I 05 Out of Tolerance B1
Range: WARNING 1 Default:
WARNING 2 WARNING 1
ALARM
IGNORE

If limit value I 04 is exceeded, event message B1 is


output .
0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 52 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

I 06 AUTO Print
Range: NO Default: NO
YES

YES : Automatic printout after every complete


batch
NO: Batch report can be printed only using
control menu.

06.03.03 16:20:16
Batch Setpoint 200 kg
Batch Actual Val. 205 kg
Counter 1 31779 kg
Counter 2 32 t
Batch-Number 6

Events B1 Out of Tolerance I05

I 07 Batch Source
Range: OP
FB Default: OP

OP : Enter batch and make-up setpoints from


INTECONT keyboard
FB : Values are set via fieldbus.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 53
VDM INTECONT PLUS

Block J : Printer Settings

J 01 Baud Rate J 03 Print Page Length


Range: 2400 Default: 9600 Range: 9...127 lines Default: 72 lines
4800
9600
19200
38400 Page length for Quantity Report

Line spacing is always 1/6 inch.

Printer initializes upon change of parameter or


Speed of transmission to printer power-up.

J 02 Print Subtotal Quantity Report

Range: Error Default: Error 28.01.04 11:45:10


YES
NO Counter 1 [kg] 12000
Counter 2 [kg] 90000
Error : Every event is printed automatically as Zero set before [h] 3.00
soon as occurred
Event
YES : See above, but complete with totalizing
L1 I<MIN F2
counter (FMZ) sub-totals
NO : No printout

Printing takes place in Normal and Batching modes.

30.09.03 11:45:21 L1 W1 --> I < MIN


30.09.03 11:59:01 L1 W1 <-- I < MIN

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 54 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block K : Maintenance Int.

K 01 Maintenance Elec. K 04 Event Maint. Run. S3


Range: 0...10000 h Default: 3000 h Range: WARNING 1 Default:
Message: S4 WARNING 2 WARNING 1
(K 02) IGNORE

Alerts you on maintenance work to be effected as a


function of voltage ON-time.
Total measuring times exceeds time K 03.
If a time interval has elapsed, message S3 is output.

K 02 Event Maint. EL. S4


Range: WARNING 1 Default:
WARNING 2 WARNING 1
IGNORE

The total of power ON-times exceeds time K 01.


If a time interval has elapsed, message S4 is output.

K 03 Maint. Scale Run.


Range: 0...10000 h Default: 3000 h
Message: S3
(K 04)

Alerts you on maintenance work to be effected as a


function of scale run time.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische BV-H2219 GB 55
ownership and copyrights.
Redaktion PDE-RD
VDM INTECONT PLUS

Block L : Comm. Fieldbus

L 01 Protocol Type
Range: NO Default: NO
MODBUS COMP.
S5-BCC COMP.
MODBUS
PROFIBUS DP
DEVICENET
MODBUS/TCP
Every protocol requires an optional interface card to
be present.
“COMP” identifies the compatible protocols.

Protocol Type MODBUS/ S5-BCC Comp. MODBUS PROFIBUS DP DeviceNet MODBUS TCP ETHERNET IP
MB-COMP.

VEG VSS VSS VSS VPB 020/8020 VCB 020/8020 VET 020 VET 022

BLOCK L Default MODBUS/ PROFIBUS DEVICENET MODBUS/ ETHERNET/ S5-BCC Comp.


MB-COMP. DP TCP IP
L 01 Protocol Type NO x x x x x x
L 02 TIMEOUT Host 5s x x x x x x
L 03 Comm. Error Host IG (S 09) x x x x x x
L 04 Word sequence I:std/L:std x x x x
L 05 Byte sequence High - Low x x
L 06 Configuration FIXED x x x
L 07 Address 1 x
L 08 Resolution 4096 x
L 09 Physical attributes RS 485 x
L 10 Baud Rate 9600 x x
L 11 Data format 8-E-1 x x
L 12 Adresse 16 x
L 13 FLOAT-FORMAT IEEE x x
L 14 Address 63 x
L 15 Baud Rate 125K x
L 16 S5-Physical attributes RS422 x
L 22 Hardware VxB020 x x

L 03 Comm. Error Host S9


L 02 TIMEOUT Host
Range: IGNORE Default: ALARM
Range: 1...600s Default: 10s W1 (Warnung 1)
W2 (Warnung 2)
If timeout value exceeds zero, a message from host A (Alarm)
system is expected to arrive during set time.
If no message is received during the time set by
Parameter L02, event message S9 “Data Link Host” is
output.

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 56 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

L 04 Word sequence L 09 Physical attributes


Range: I: std/L:std Default: I: std/L: std Range: RS485
I: swp/L: std RS422
I: std/L: swp RS232
I: swp/L: swp Default: RS 485
The parameter determines the word sequence within
a double word. Modbus baud rate.
“I” stands for IEEE-754 values (floating point values)
“L” stands for 4-Byte integer values L 10 Baud Rate
“std” does not reverse the word order, “swp” swaps
them. Range: 2400 Default: 9600
4800
9600
19200
L 05 Byte sequence 38400
Modbus-Baudrate.
Range: LOW-High Default: LOW-High
High-LOW
Determines the byte sequence in a data word.
L 11 Data format
L 06 Configuration
Range: 8-E-1 Default: 8-E-1
Range: FIXED Default: FIXED 8-0-1
NO-PARA-ID 8-N-2
PARA-ID 8-N-1
PARA-6ID* Modbus data format (data bits-parity-stop bits).
Determines the structure and the size of the process
image.

Only with fieldbus card VxB8020. L 12 Address


Range: 0...126 Default: 16
L 07 Address
Range: 1...254 Default: 1 Profibus DP Slaveadresse

Slave address for Modbus protocol.

L 13 FLOAT-FORMAT
Range: SIEMENS-KG Default: IEEE
L 08 Resolution
IEEE
Range: 1...32767 Default: 4096 Determines the display of the floating point value for
the Profibus DP protocol.
Resolving the data in the Modbus protocol nominal
value (integer format).
L 14 Address
Range: 0...63 Default: 16

DeviceNet slave address.


0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 57
VDM INTECONT PLUS

L 15 Baud rate
Range: 125k Default: 125k
250k
500k
DeviceNet baud rates.

L 17 S5 Physical attributes
Range: RS422 Default RS 422
RS232
Setting the physical interface attributes for the S5
BCC protocol.

L 22 Hardware
Range: VxB020 Default: VxB020
VxB8020
Select fieldbus hardware for Profibus DP and
DeviceNet.

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 58 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block M: Events

M 01 Power Failure E1 M 05 L/C Input > MAX H4


Range: ALARM Default: ALARM Range: ALARM Default: ALARM
WARNING 1 WARNING 1
WARNING 2 WARNING 2
IGNORE

Load on load cell exceeds 110 % of the total of load


cell rated capacities (C 03).

Scale does not start automatically regardless of event Full scale: approx. 115 % with CSD load cells
class. 160% with HBM load cells

M 02 Memory Error S1
M 06 L/C Input < MIN L4
ALARM: No changes possible
Range: ALARM
Scale no longer operable WARNING 1
WARNING 2 Default: ALARM

Load on load cells is smaller than 1% of total load


cells rated capacities (C 03)
M 03 L/C Input C1
Range: ALARM Default: ALARM Meldung: L4
WARNING 1
WARNING 2 M 07 Simulation Active S7
Range: WARNING 1 Default:
1. Load cell not (or improperly) connected. WARNING 2 WARNING 2
2. Analog-to-digital converter of measuring amplifier ALARM
is in saturation (see Service Value wz). IGNORE
3. Supply voltage is below 19V. Simulation Mode is active.

Error must be available for at least 3 s. M 08 Error Ext. Event E6


Range: IGNORE Default: ALARM
WARNING 1
WARNING 2
M 04 No Release S2 ALARM
Range: WARNING 1 Default:
WARNING 2 WARNING 1
Event is output if external digital input (Parameter
IGNORE
O04) is set.
ALARM

0842 No RELEASE input signal

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 59
VDM INTECONT PLUS

Block N: Linearization

N 01 Linearization ON N 06 Lin.-S3
Range: NO Default: NO Range: 0.10...1000.00%Io Default: 75%Io
YES
Linearization point 3:
This function lets you linearize feed rate
measurement. See N 02
The 4 linearization points can be determined through
checks using material. Place points not needed, or
measured, outside the measuring range or interpolate.
N 07 Lin.-I3
N 02 Lin.-S1
Range: 0.1...1000.0%Io Default: 75%Io
Range: 0.10...1000.00%Io Default: 25%Io
Linearization point 3:
Related to nominal feed rate B02
See N 03
Linearization point 1:

Material amount fed out divided by measuring time N 08 Lin.-S4


Range: 0.10...1000.0%Io Default: 100%Io
N 03 Lin.-I1
Linearization point 4:
Range: 0.1...1000.0%Io Default: 25%Io
See N 02
Related to nominal feed rate B02

Linearization point 1:
N 09 Lin.-I4
Check amount displayed on INTECONT divided by Range: 0.1...1000.0%Io Default: 100%Io
measuring time
Linearization point 4:
N 04 Lin.-S2
See N03
Range: 0.10...1000.00%Io Default: 50%Io
N 10 Lineariz. Error B9
Linearization point 2:
Range: WARNING 1 Default:
See N 02 WARNING 2 WARNING 2
ALARM
IGNORE
N 05 Lin.-I2
Range: 0.1...1000.0%Io Default: 50%Io Monitoring for monotonously rising compensation
takes place only if linearization is active.
Linearization point 2:
1. Upon start of linearization
0842
See N03 2. Upon change to parameter

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 60 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block O: Digital Inputs

O 01 Release O 06 DI Start
Range: DI Default: DI (DI2) Range: DI Default: —
— __

Determines digital input used to release scale. If OP has been selected for start source, digital input
“DI Start” can be configured and used to start feeder
Setting “- - ” means that no release is required. using a start pulse (key). Feeder is stopped by a pulse
output across digital input “Release”.
Default is DI2; however, any other free digital input This configuration is possible parallel to the
can be used as well. START/STOP keys on INTECONT keyboard.

O 02 DI Stop batch
Range: DI Default: —

Digital input signal used to stop a running batch

O 03 DI Ackn. Events
Range: DI Default: DI (DI1)

Determines digital input used to acknowledge events

O 05 DI Ext. Event
Range: DI Default: - -

Digital input used to output external fault signal

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 61
VDM INTECONT PLUS

Block P: Digital Outputs

P 01 DO Alarm Q 06 DO I-MAX
Range: DO Default: DO (DO3) Range: DO Default: DO (D02)
— —

Digital output used to report general alarm Digital output signal used to report that maximum feed
rate (F03) is exceeded up.
Contact output is independent of event class (F04).

P 02 DO Prefeeder ON
Range: DO Default: DO (DO6) P 06 DO Batch Active

Range: DO Default: —
Digital output used to START/STOP prefeeder —

Digital output signal used to report that a batch is


running.
Signal becomes active upon start of batch, and is
P 03 DO Feeder ON reset after batch complete. If batch is stopped, signal
continues being available.
Range: DO Default: DO (DO5)

Digital output signal used to report START/STOP P 07 DO Full Feed


states of scale
Range: DO Default: —

P 04 DO I-MIN
Range: DO Default: DO (DO1) Full feed signal is available from start of batch until
— amount batched = batch setpoint - I01-I02 is
reached. Feeding continues in dribble feed.

Digital output signal used to report that minimum feed


rate (F01) is exceeded down.
Contact output is independent of event class (F02).
P 08 DO Dribble Feed
Range: DO Default: —

Dribble feed signal is output when full feed phase is


complete (see P07).
0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 62 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

P 09 DO Keyboard Mode
Range: — Default:: —
DO
Digital output signal to report activated keyboard
mode.

Block Q: Comm. EasyServe

Q 01 Station Address Q 04 Format Data


Range: 1...254 Default: 1 Range: 8-0-1 Default: 8-0-1
8-E-1
Make sure station address and baud rate of scale and 8-N-1
EasyServe are identical. EasyServe uses either a 10- or 11-bit character frame.
EasyServe lets you search for proper setting including
COM interface (menu: Tools/Options/Communication).
The station address is specially designed for plants Example:
using a service bus. If the latter is not available,
select 1. 8-0-1 means:
Connection to PC can also be made using a 9-pole
SUB-D connector on X4 (RS 232 only) or a Phoenix 1 start bit, 8 data bits, odd parity, 1 stop bit
connector on X5 (RS232, RS422 or RS485). (N = No Parity, E = Even Parity)
See also Wiring Diagram in chapter DETAILS.

Q 05 Connection
Q 02 Physics
Range: Serial Default: Serial
Range: RS 232 Default: RS 232 SERIAL+TCP
RS 422 If MODBUS/TCP (Ethernet) has been selected for
RS 485 fieldbus, communication between feeder and
Physics of data transmission protocol EasyServe can also take place via Ethernet.
To do so, set Connection parameter to SERIAL-TCP.

Q 03 EasyServe Baudr.
Q 06 MODBUS Idle Time
Range: 9600 Default: 19200
19200 Range: 2...20ms Default: 4 ms
38400
Data transmission rate For Modbus driver, single character timeout (idle time)
for end recognition can be adjusted using this
parameter (see BVH2220).

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 63
VDM INTECONT PLUS

Block R: Ethernet

R 01 IP Address1 R 07 Net mask 3


Range: 0-255 Default: 192 Range: 0-255 Default: 255

Manual IP address assignment Delegating the subnetwork masks

R 02 IP Address 2 R 08 Net mask 4


Range: 0-255 Default: 168 Range: 0-255 Default: 0

Manual IP address assignment Delegating the subnetwork masks

R 03 IP Address 3 R 09 Gatway 1
Range: 0-255 Default: 240 Range: 0-255 Default: 192

Manual IP address assignment Festlegung der Standard-Gateway-Adresse.

R 04 IP Address 4 R 10 Gatway 2
Range: 0-255 Default: 1 Range: 0-255 Default: 168

Manual IP address assignment Delegating the standard gateway address

R 05 Net mask1 R 11 Gatway 3


Range: 0-255 Default: 255 Range: 0-255 Default: 240

Delegating the subnetwork masks Delegating the standard gateway address

R 06 Net mask2 R 12 Gatway 4


Range: 0-255 Default: 255 Range: 0-255 Default: 0

Delegating the subnetwork masks Delegating the standard gateway address

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 64 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Block S Fixmode Parameters

As of version VDM20600-05, the options FIXED-1 and S 07 ID preset value 7


FIXED-2 in parameter L06, “Configuration”, are no
longer available and have been replaced by Range: 0...4096 Default: 0
FIXED.The values carried over with the setting FIXED
are determined by the following parameters. The
settings of the original values correspond to the
previous FIXED mode 1.A list of all available S 08 ID preset value 8
identifiers and FIXED mode examples can be found in
the manual BV-H2220. Range: 0...4096 Default: 0

S 01 ID preset value 1
Range: Fest eingestellt Default: 320 S 09 ID read value 1
Command 4+5 Range: 0...4096 Default: 752

Status 2+3
S 02 ID preset value 2
Range: 0...4096 Default: 352 S 10 ID read value 2
Command 6+7 Range: 0...4096 Default: 784

Status 4+5
S 03 ID preset value 3
Range: 0...4096 Default: 384 S 11 ID read value 3
Command 8+9 Range: 0...4096 Default: 1552

Highest priority event


S 04 ID preset value 4
Range: 0...4096 Default: 596 S 12 ID read value 4
Reload setpoint [kg] Range: 0...4096 Default: 1872

Actual flow rate [kg/hr]


S 05 ID preset value 5
Range: 0...4096 Default: 594

Batch setpoint [kg] S 13 ID read value 5


Range: 0...4096 Default: 1874

Totalizing counter 1 [kg]


S 06 ID preset value 6
Range: 0...4096 Default: 598
0842
Batch number

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Parameterization
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 65
VDM INTECONT PLUS

S 14 ID read value 6
Range: 0...4096 Default: 1882

Measuring load [kg]

S 15 ID read value 7
Range: 0...4096 Default: 1876

Totalizing counter 2 [kg]

S 16 ID read value 8
Range: 0...4096 Default: 1894

Effective setpoint [kg]

0842

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 66 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

9. Event Messages

System Message S S7 : Simulation Active

Operating in Simulation Mode, scale is not


S1 : Memory Error prepared for normal operation.
In Simulation Mode, all scale functions can
Program and parameter memories are be tested without material at the time of
checked in cycles. If an error is detected, commissioning.
scale is normally inoperable. Action : Stop “Simulation” function.
Action : Contact the SCHENCK Parameter : M 07
Service.
Parameter: M02 S9 : DATA LINK HOST

Serial communication interrupted for longer


S2 : No Release than timeout period.
Action : Check cable connections.
No external RELEASE signal. Parameter : L 03
Scale cannot start.
Parameter : M 04

S3 : Maint. Scale Run.

Total ON-time of totalization exceeds set Electrical System E


limit.
Perform requisite service work, if
necessary. E1 : Power Failure
Acknowledgement of message does not
influence time intervals. Power failed or cut off.
Parameters : K 03, K 04 It is possible that totalization has stopped
during this time.
Action : Acknowledge message.
Parameter : M 01
S4 : Maintenance Int.Elec

The INTECONT power supply has been E6 : External Input


switched on for a set time.
Perform requisite service work, if External fault signal available across fault
necessary. input.
Acknowledgement of message does not Parameter : M08
influence time intervals.
Parameters : K 01, K 02

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Event Messages
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 67
VDM INTECONT PLUS

Calibration C Maximum H

C1 : L/C Input H1 : I > MAX


1. Load cell cable broken, not (or
improperly) connected. Current feed rate exceeds set limit value.
2. Supply voltage smaller than 19V Action : Normally none, unless
Action : Check cabling. message H4 is additionally
If OK, check load cell available or system-
amplifier. specific limits have to be
Parameter : M05 observed.
Parameters : F 03, F 04

H4 : L/C Input > MAX


C5 : Tare Corr. > MAX
Scale overloaded. Errors in measurement
Automatic zero setting result exceeds can occur.
zeroing limit. No correction takes place. Action : Check material infeed.
Action: Retare device. Parameter : M 05
Parameters: H 03, H 04

Minimum L

L1 : I < MIN

Current feed rate has fallen below set limit


value.
Action : System-specific
Parameters : F 01, F 02

L4 : L/C Input < MIN

Weighing system is underloaded, or not


positively tied. Measurement can fail.
Action : Check mechanical scale
system and cabling.
Parameter : Q 06

0842

Transmission to third parties and reproduction


Event Messages Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 68 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Material Flow (Batch) B Signal Lamps

B1 : Out of Tolerance a (green) POWER OK


LED not lit:
Batch not completed with preset accuracy. 1. No power supply
Tolerance : Parameter I04 2. Device defective
Event : Parameter I05 3. All other functions OK, LED
Cause : Automatic adaption probably defective. Call
connected (Parameter display test.
I 03)?
Material infeed faulty ? b (green) CPU OK
If display is pending or flashing,
processor system is faulty,
Scale is inoperable.
B9 : Linearization

Linearisation for feed rate measurement


X (red) ALARM
flashes if an Alarm is available.
improperly set. Display additionally shows
Message is output only if linearization is event code.
active.
Action : Check relevant parameters Action:
to see if preset curve see relevant event code.
features plateaus or
turning points. MIN (red) MIN LIMIT VALUE
Parameters : N 01...N 10 lit if feed rate limit value is
exceeded down.

Action:
see L1: I<MIN

MAX (red) MAX LIMIT VALUE


lit if feed rate limit value is
exceeded up.

Action:
see H1: I>MAX.

No power supply:

Upon short circuit on the secondary side of the power


supply, internal overload protection responds.
Disconnect power for approx. 1 min., and it is ready to
operate again.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Event Messages
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 69
VDM INTECONT PLUS

This page left intentionally blank

0842

Transmission to third parties and reproduction


Event Messages Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 70 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

10. Commissioning

Test Plug

Almost any possible error in operation is reported by


event message. For interpretation, see Chapter 10.

Check INTECONT for proper operation by using a


simple test plug. This helps to see whether the fault is
with load cell, cabling or electrical equipment.

1. Switch plug as shown in drawing.


2. Withdraw load cell connector X7 and replace by
test plug.

At the indicated resistance values, the following


service values result:

1. wz apr. 1.1mV/V
2. Load cell apr. 55 % (C02 =2mV/V)
utilization aw apr. 39% (C02 =2.85mV/V)

If wz is in specified range, measuring amplifier


operates properly.

Note:
With different R1 and R2 resistance values, the
following raw measured value results:

Raw measured value ~ 500 * R2 / R1 [mV/V].

Note:
The test plug ordering number is V037426.B01.
0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Commissioning
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 71
VDM INTECONT PLUS

This page left intentionally blank

0842

Transmission to third parties and reproduction


Commissioning Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 72 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

11. Details
Start Sources

Fig.: START Sources

Sources START/STOP Synchronization

The “Start/Stop” functions can be started from different Upon changeover from external setpoint source or
control sources preselected via parameters. keyboard, external setpoint is acquired. In reverse
The “Keyboard Mode” dialog function lets you shift direction, the external source is active.
from preselected sources to keyboard and vice versa.

Parameter:

B 03 START Source FB (fieldbus)


OP (keyboard)
DI (contact)

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Details
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 73
VDM INTECONT PLUS

Control Inputs/Outputs

Fig.: Control Inputs/Outputs

Operating Sequence

1 As long as no Release signal is available (contact


open), no start command is effective.
2 Scale is released.
3 L-H edge of Start input or Start command from
another source starts measurement and prefeeder.

4 Cut-off command
Prefeeder immediately stops, measurement and
totalization continue for time G 05.
5 Feed rate acquisition and totalization complete.

Measured load is acquired and displayed also in Stop


state of scale.
Running display (rotating point) reports all phases
during which totalization is active.
Cut-off after alarm is identical with normal cut-off
sequence.

0842

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 74 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Batching

Principle:
Sequence:
When batch is complete, material prefeeder cuts off.
0 Start batch using Start command.
Changeover from full feed to dribble feed can be
Prefeeder and totalizing counter start operating.
effected using prefeeder speed or opening angle. .
1 Stop batch using Stop command.
Output signals (Batch Running, Full Feed, Dribble Measurement continues for time G 05.
Feed) can be placed on free output contacts, if 2 Continue batch using Start command.
required.
0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Details
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 75
VDM INTECONT PLUS

3 Dribble feed changeover point Alarm:


FM = SET - A - F is reached. Dribble Feed signal
changes its level. Batch stops (measuring wheel and prefeeder
A and F are the cut-off amounts defined by immediately cut off) and can be resumed after
parameters I 01 and I 02. removal of cause and acknowledgement of event
message.
4 Cut-off point
AM = SET - A is reached and batch is complete.
Prefeeder stops.

5 Material afterflow
Power OFF:
If parameters A and F are properly set, defined
setpoint is exactly reached.
Batch aborts, batching mode remains selected.
If note, see “Adaption”.
All counter readings and amounts batched are stored
for an unlimited period of time.
Next Start command starts new batch.

Adaption:

After every complete batch, INTECONT uses the


missing material amount to compute a correction
value (I02). Dribble feed changeover point is adapted
automatically.

Error = SETPOINT - amount batched

Cut-off point for next batch is computed from error and


an evaluation factor.

A(new) = A(old) + FAK * error

A(new) = Batch cut-off point I02

FAK = Adaption factor I03

Errors smaller than smallest display digit are not


corrected.

DI Complete Batch:

The Complete Batch contact acts like a Stop


command with additional abort of batch. Next Start
command starts new batch.

0842

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 76 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Data Flow Charts: Signal Flow

Fig.: Simplified Signal Flow Chart

Note: Code Meaning


WZ Load cell
In normal INTECONT operation, the data flow charts D Cross-flexure strip for chute and check weight
Qwz Measured load on load cell
need not be known.
QPRF Measured load on load cell C05
In special cases, they can be used to trace internal
LWZ Load cell lever arm
normalizations relevant for precalibration (theoretical LPG Check weight lever arm
calibration). QP Check weight
GK Device constant C04
GEWKOR Weight correctionr D02
TARA Basic tare D04
TARKOR Tare correction D05
MATKOR Material correction D06
WZF0 Load cell rated capacity C03
WZKENN Load cell characteristic value C02
Q Measured load
P Flow rate

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Details
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 77
VDM INTECONT PLUS

Device Constant GK C04 in kg/(t/h) Calibration CW

GK indicates the correlation of load cell load and feed The CW calibration program compares the effective
rate and thus determines calibration accuracy. check weight entered (load on load cell through check
weight) with measured load cell load.
GK = QNOM / PNOM

QNOM = Spec Sheet value; does not refer to


Parameter L/C Rated Cap. (C 03)!

L/C Rated Cap. WZF0 C03 in kg

Enter total of load cells rated capacities.

WZF0 influences calibration accuracy.

L/C Charac. Value WZKENN C02 in mV/V

Load cell transmission coefficient WZKENN is an


important calibration value.

Ua = Ue x WZKENN x (F / WZF0)

Ua Output voltage in mV
Ue Input voltage in V

CSD load cells WZKENN 2.85mV/V


HBM load cells WZKENN 2 mV/V 1)

1) With certain types, WZKENN is not calibrated.

For exact value, see type plate.

Effective Check Weight QPRFC05 in kg

Enter the force the check weight exerts on load cell.

Effective check weight QPRF = U2 x check weight

U2 = LPG / LWZ (see Fig.)

Feed rate is P = QPRF / GK in kg/h

(MATKOR = 1, TARKOR = 0, LIN on Linear)

0842

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 78 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Wiring Diagram
Base Card

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Details
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 79
VDM INTECONT PLUS

0842

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 80 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Option Card

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Details
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 81
VDM INTECONT PLUS

Namur Inputs: n Cable fastening

> 8 mA = short circuit


1.65...8 mA = level 0
0.1...1.65 mA = level 1 (sensor covered)
< 0.1 mA =cable breakage

Option Card:

The option card is affixed to the INTECONT cover.


Signal exchange with base card is via a pluggable flat
cable connector.
If pulled off, system behaves as if no option card was
present and only the operating functions and In the rear wall of the INTECONT, under each
parameters of the base card can be used. connector, several slots are provided. The upper slot
pair is reserved for the cable clamp which presses the
Cabling Hints:
shielded cable against the rear wall. The shield needs
not be separately connected. The lower cut-out serves
n All cables are led to the device from the rear
for accommodation of a pull relief, e.g. by cable
(front-of-panel mounting housing) or from below
(flush mounting housing) and connected with binders.
special connectors. Connectors cannot be
confused. Attention!
n The INTECONT is isolated from the mounting
surface by its plastic housing. Connectors to base card require to be plugged-in
The rear earthing connector is internally with screwed connections up; connectors to option
connected with the electronics zero potential. card, with screwed connections down.
The protective ground used requires to be hum-
and transient-free. n Connectors on INTECONT rear wall:
The power supply zero potential (0V ext.) is not
connected to the earthing connector. Normally no
earthing is required..
n Make sure no leakage currents are conducted
over cable shields. Therefore shields are applied
to one side of INTECONT. The load cell housing is
not connected with shields.
Shields of data cables to host computer are
connected to ground on either side.
n The consumers connected to the relay and pulse
outputs require to be radioshielded, e.g. by
suppressor diodes or RC elements.
n Analog outputs
Long cables, particularly to frequency
transducers, can interact on analog outputs. We
suggest to use an isolating amplifier..
n Make sure the space between power and
measuring cables, if run in parallel, is min. 0.30 m.
If this is not possible lay measuring cable in steel
conduit. The same holds if the measuring cable is
laid over free stretches or close to powerful
transmitters (e.g. broadcasting stations). 0842

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 82 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

Printer Connection
Interface : Serial, see “Technical Data”. Switch
1-1 : OFF 8-bit message
Character map : ISO-Latin-1 (ISO-8859-1) 1-2 : OFF No parity bit
1-3 : egal Even/odd
Cable : The connection diagram refers to 1-4 : OFF Postive edge
EPSON and CITIZEN printers. 1-5...8 : OFF, ON, OFF, OFF 9600 baud
2-1...6 : ON, ON, OFF, OFF, OFF, OFF
(default)

Use Parameter J 01 to set baud rate to 9600. On the


right side of printer, there are two additional DIP
switches. Diagram view corresponds to top of printer.

Fig. EPSON Printer

Fig. Printer Cable Switch


1-1 : OFF 10 CPI character spacing
1-2 : OFF Zero without backslash
1-3 : ON Graphics character set
EPSON printer: LX 850 1-4 : OFF AUTO hyphenation activated
1-5 : ON Normal sprint speed .
1-6...8 : ON, ON, ON USA
2-1 : ON 12" page length
2-2 : OFF No single sheet
2-3 : OFF Jump over performation
2-4 : OFF No AUTO line feed

Information on switch position can be printed using


the printer self-test function. (Press line feed key while
starting printer).

CITIZEN Printer: 120D

Fig. EPSON Interface

The interface board is equipped with 2 DIP switches


used for selection of serial message base data.
Fig. Serial Interface
To initialize:

0842 Printer is initialised via serial interface, 5s after


power-up of INTECONT PLUS.

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
Technische Details
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 83
VDM INTECONT PLUS

This page left intentionally blank

0842

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
Schenck Process GmbH reserves all rights of
BV-H2219 GB 84 Redaktion PDE-RD ownership and copyrights.
INTECONT PLUS VDM

12. Replacement Instructions

Replacing INTECONT PLUS FIP —> INTECONT PLUS VEG


INTECONT PLUS, type “VEG”, is equipped with added functions for INTECONT PLUS, type “FIP”. Logical
inputs/outputs can now be assigned to hardware at will. Please also check all connectors with relevant
parameter assignment.
When using our convenient replacement set (ordering no. V036910.B01), hardware is adapted by plugging.
The EasyServe setting program supplied enables easy assignment and transfer of all software parameters.

FIP base card wiring diagram

0842 FIP option card wiring diagram

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of Technische Replacement Instructions
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 85
VDM INTECONT PLUS

The FIP base and option cards connection diagrams Load Cell
indicate for every digital input and output the relevant
INTECONT VEG parameter numbers used for FIP Physical Signal VEG
distribution on physical signals.
X5 3 OUT1 X7 3
The tables below compares the connector X5 4 REF1 X7 4
assignments of FIP and VEG for all physical signals. X5 5 IN2 X7 6
X5 6 IN1 X7 5
Digital Outputs X5 7 REF2 X7 7
X5 8 OUT2 X7 8
FIP Physical Signal VEG

X1 1,2 DA1 X1 1,2 Attention:


X1 3,4 DA2 X1 3,4 Signals IN1 and IN2 are swapped between FIP and
X1 5,6 DA3 X1 5,6 VEG. (VEG is compatible to DISOCONT).
X6 1,2 DA4 X8 1,2
X6 3,4 DA5 X8 3,4
X6 5,6 DA6 X8 5,6
X6 7,8 DA7 X8 7,8 Power Supply
X6 9,10 DA8 X8 9,10
FIP Physical Signal VEG
Digital Inputs X2 1 0V ext X2 1
X2 2 24V ext X2 2
FIP Physical Signal VEG X2 3 ext. supply 0V X2 3
X2 4 ext. supply 24V X2 4
X3 1,2 DE1 X3 1,2
X9 1,2 DE2 X3 3,4
X9 3,4 DE3 X6 6,7 Printer
—- DE4 X9 1,2
—- DE5 X9 3,4 FIP Physical Signal VEG
X3 5,6 Ext. input X3 5,6
X8 1 Screen X10 1
X8 2 TX X10 2
Analog Inputs/Outputs X8 3 RX X10 3

FIP Physical Signal VEG


Pulse Output
X9 9,10 A01 X6 4,5
—- A02 X9 5,6 FIP Physical Signal VEG

—- AI X6 1,2,3 X9 5 24V X6 8
X9 6 Open collector X6 9
X9 7 Open emitter X6 10
X9 8 0V X6 11

With VEG, fieldbus is connected via separate fieldbus


cards (FIP: Connector X7). See Fieldbus Manual
BVH2220.

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Replacement Instructions Technische Schenck Process GmbH reserves all rights of
ownership and copyrights.
BV-H2219 GB 86 Redaktion PDE-RD
INTECONT PLUS VDM

Connector Size

FIP

X1 Phoenix contact spacing 5mm : 6 pins


X2 Phoenix contact spacing 5mm : 4 pins
X3 Phoenix contact spacing 5mm : 7 pins
X5 Phoenix contact spacing 5mm : 8 pins
X6 Phönix Raster 5mm : 8 or 10 pins
X7 SUB-D : 9 pins
X8 SUB-D : 9 pins
X9 Phoenix contact spacing 5mm : 12 pins
X11 Phoenix contact spacing 5mm : 3 pins

VEG

X1 Phoenix contact spacing 5mm : 6 pins


X2 Phoenix contact spacing 5mm : 4 pins
X3 Phoenix contact spacing 3.5mm: 6 pins
X4 SUB-D : 9 pins
X5 Phoenix contact spacing 3.5mm: 7 pins
X6 Phoenix contact spacing 3.5mm: 11 pins
X7 Phoenix contact spacing 3.5mm: 8 pins
X8 Phoenix contact spacing 5mm : 10 pins
X9 Phoenix contact spacing 3.5mm: 9 pins
X10 Phoenix contact spacing 3.5mm: 7 pins

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Schenck Process GmbH reserves all rights of Technische Replacement Instructions
ownership and copyrights.
Redaktion PDE-RD BV-H2219 GB 87
VDM INTECONT PLUS

This page left intentionally blank

0842

Transmission to third parties and reproduction


of this documentation are not permitted.
Replacement Instructions Technische Schenck Process GmbH reserves all rights of
ownership and copyrights.
BV-H2219 GB 88 Redaktion PDE-RD

S-ar putea să vă placă și