4026

DIGITAL TO ANALOG CONVERTER


MAG & DIGITAL TYPE
PA-20/6

PRODUCT DESCRIPTION
The PA 20 D/A converter has been configured to fit a compact
"Y3" explosion proof enclosure. Input and output configurations
are field selectable to fit most applications.
Switch #1
ZERO and SPAN adjustments make it easy to calibrate to almost
any measurement range, with little interaction between the SPAN
adjustments. The converter will accept frequency input from 1.99
any mag pickup or digital pickup (digital mag, RF, Hall effect, ZERO
zero speed, "smart" etc...)

SPECIFICATIONS
Vs, Supply Voltage: 9.0 VDC Min. 0-5 Vout, FTV
11.0 VDC Min. 0-10 Vout, FTV Switch #2
38.0 VDC Max. REMOVABLE PLUG-IN
TERMINAL BLOCK
Input Protection: 50 VAC, reversed leads (STANDARD VERSION ONLY)

Output Protection: Short to + VDC, Common or


Signal out Continuous

Frequency Input Range: F HI: 1100 Hz to 10 kHz


F LO: 75 Hz to 1100 Hz 1.19
*.91 1 2 3 4 5 6
Input Sensitivity: Mag: See Variants LP VERSION OUT MAG DIGITAL
.67
11 -38VDC COIL IN
Digital: CMOS/TTL (30Vpp Max)

Output Setting Time: Full scale change to 95%


of final value 180mS.
Switch #1 Switch #2
Output Ripple & Noise: 5 mVp-p, <2 mVrms, 5% of FS Position #1 Position #2 Position #3 Position #4 Position #1

Temperature Coefficient: 0.13% / °C, On 10 V range(25°- 40°C)


* CURRENT
MODE 10-50 mA 0-5 V F High Digital
VOLTAGE
MODE 4-20 mA 0-10 V F Low Mag. Coil
Operating Temp. Range: -40 to 70°C (-40 to 160° F) *
* NOTE: Black Box indicates position switch high side.
ZERO/SPAN Adjustment Interaction: < 1% VOLTAGE MEASUREMENT SPECIFICTIONS
0-5V 0 - 10 V
Terminal Connections: 1. Input VDC RANGE RANGE
2. Common Vout min, (Freq. input = 0 Hz) at full
5.1 mV 10.5 mV
scale max freq. cal.
3. Signal Out
4. Mag Pick-up Vout min at full scale min freq. cal. 21 mV 43 mV
5. Mag Pick-up Vout max at Vsupply = +12Vdc 6.8 V 11.3 V
6. Digital Signal Input Vout max. at Vsupply = +24 VDC 6.8 V 13.7 V
Wiring Options: (See Page Two) Minimum Load Restistance  1/2W  1 W
Maximum Load Restistance Open Open
CE-Compliance: EN55011, EN50022-2

PART NUMBERS CURRENT MEASUREMENT SPECIFICATIONS


4026-05: 5 mVpp [Mag] & Digital Input 4-20 mA 10-50 mA
3 WIRE OUTPUT VERSION Range Range
4026-12: 12 mVpp [Mag] & Digital Input
4026-30: 30 mVpp [Mag] & Digital Input Minimum Output Current 0.07 mA 0.19 mA
4026-50: 50 mVpp [Mag] & Digital Input Maximum Output Current (Full Scale
Low Profile*: Add “LP” to the end of the above PN Min. Cal., Zero Cal. set to 4 mA and 24.1 mA 61.2 mA
10 mA)
*Low Profile terminal block is not removable. Load Resistance = <(V+-6V)
Full Scale Output
Explosion Proof 90010-03: Y3, CL1, DIV1, Enclosure
if V+ = 24 V <300 <120
Junction Boxes: 90012-03: ELBY 100, CL1, DIV1, Enclosure if V+ = 12 V <900 <360

For other Enclosure & Adapters see spec. 4001


1/28/2013, REV.7
4026 FTC/FTV CONVERTER: WIRING OPTIONS

A) VOLTAGE MEASUREMENT 1 (3 wire)


SWITCH POSITIONS: WIRE POSITIONS:
RANGE: 0-5 V or 0-10 V 1 - V+
PROGRAM: V 2 - COM
VOLT
FREQ.: F HI 3 - METER POS. METER
F LO 4 - MAG. (175min.)
10'
5 - MAG.
V+ MAG PICKUP
6 - NC
COM

B) VOLTAGE MEASUREMENT 2 (3 wire)


FOR USE WITH LONG WIRES RUNS
RESISTANT TO LINE LOSSES & EMI
SWITCH POSITIONS: WIRE POSITIONS:
RANGE: 50 mA for 0-10 V 1 - V+
20 mA for 0-5 V 2 - COM VOLT
PROGRAM: C METER 1000'
3 - METER NEG.
FREQ.: F HI 4 - MAG. V+ MAG PICKUP
F LO COM
5 - MAG. 390 
6 - NC 1/2 W
5% CURRENT

C) CURRENT MEASUREMENT 1 (2 wire)


SWITCH POSITIONS: WIRE POSITIONS:
RANGE: 10-50 mA or 1 - METER NEG. & JUMPER
4-20 mA 2 - COM
PROGRAM: C 3 - JUMPER FROM #1 AMMETER
FREQ.: F HI 4 - MAG.
F LO 1000'
5 - MAG. V+ MAG PICKUP
CURRENT
6 - NC
COM
JUMPER WIRE

D) CURRENT MEASUREMENT 2 (3 wire)


SWITCH POSITIONS: WIRE POSITIONS:
RANGE: 0-50 mA or 10-50 mA, 1 - V+ & METER POS.
0-20 mA or 4-20 mA 2 - COM
PROGRAM: C 3 - METER NEG.
FREQ.: F HI 4 - MAG.
F LO 1000'
5 - MAG.
V+ MAG PICKUP
6 - NC
COM
AMMETER
CURRENT

E) CURRENT MEASUREMENT W/ DIGITAL INPUT


SWITCH POSITIONS: WIRE POSITIONS:
RANGE: 0-50 mA or 10-50 mA, 1 - V+, METER POS., & PICKUP POS.
0-20 mA or 4-20 mA 2 - COM
PROGRAM: C 3 - METER NEG.
FREQ.: F HI 4 - NC
F LO 1000' DIGITAL
5 - PICKUP COM PICKUP
V+
6 - PICKUP SIGNAL COM
COM
AMMETER V+
CURRENT

1/28/2013, REV.7