System Protection

Transformer protection

Engineering Simply the Best !!!


Topics
1. Overheating
2. Gas Detection
3. Pressure Indicator and Relief Valve
4. Overcurrent
5. Differential Relaying

Engineering Simply the Best !!!


Topics
 Rating of transformer is based on the
temperature rise above an assumed maximum
ambient temperature; Under this condition no
sustained overload is usually permissible.
 Normal maximum working temp = 95°C;
8-10° rise will halve the life of the transformer
 Protective Instruments
 Liquid Temperature Indicator
 Thermal Relays

Engineering Simply the Best !!!


Overheating

Engineering Simply the Best !!!


Overheating

Engineering Simply the Best !!!


Gas Detection

Engineering Simply the Best !!!


Gas Detection

Engineering Simply the Best !!!


Pressure Indicator & Relief
Valve

Engineering Simply the Best !!!


Overcurrent
 Fuses for Small Distribution Transformer
 Overcurrent Relaying for Large Power
Transformer
 Characteristics
 Must be below the damage curve
 Must be above cold starting and magnetizing
inrush

Engineering Simply the Best !!!


Differential Relaying

Engineering Simply the Best !!!


Differential Relaying

Engineering Simply the Best !!!


Differential Relaying
 DIFFERENTIAL RELAY SETTING (GENERAL PROCEDURE)
 1. FLC Primary and Secondary
 2. Select CT Ratios
 3. Determine Currents at the secondary of the CTs
 4. Determine Tap @ primary and secondary
 5. Determine Currents at the relays (given the Tap settings in P & S)
 6. Determine CT Ratio Mismatch
 7. Determine Transformer Tap Changing Mismatch
 8. Determine CT Errors [Example: 10CXXX 10% error]
 9. Add Margin [e.g., 5%]
 10. Add: CT Ratio Mismatch + Transformer Tap Changing Mismatch
+ CT Error + Margin to Determine Differential Relay Slope

Engineering Simply the Best !!!


Differential Relaying

Engineering Simply the Best !!!


Differential Relaying

Engineering Simply the Best !!!


Differential Relaying
 Step 1: Full Load Current on Primary & Secondary

Engineering Simply the Best !!!


Differential Relaying
 Step 2: Select CT Ratios to be used

Engineering Simply the Best !!!


Differential Relaying
 Step 2: Select CT Ratios to be used

Engineering Simply the Best !!!


Differential Relaying
 Step 3: Determine the Tap at Primary and Secondary

Engineering Simply the Best !!!


Differential Relaying
 Step 4: Determine the CT Ratio Mis-match

Engineering Simply the Best !!!


Differential Relaying
 Step 5: Determine Tap Changing Mis-match

Engineering Simply the Best !!!


Differential Relaying
 Step 5: Determine Tap Changing Mis-match

Engineering Simply the Best !!!


Differential Relaying
 Step 5: Determine Tap Changing Mis-match

Engineering Simply the Best !!!


Differential Relaying
 Step 5: Determine Tap Changing Mis-match

Engineering Simply the Best !!!


Differential Relaying
 Step 5: Determine Tap Changing Mis-match

Engineering Simply the Best !!!


Differential Relaying
 Step 6: Determine the CT error
 Assume the CT error to be 10%
 Common error for protection CTs)

 Step 7: Add margin of Error


 Add margin of error of 5%

Engineering Simply the Best !!!


Differential Relaying
 Step 8: Differential Relay Slope
 Slope=CT Ratio mis-match + Transformer Tap Changing
mis-match + CT error + Margin
Slope = 1.11% + 13.24% + 10% + 5%
Slope = 29.35% ; so set the slope to be at 30%.
 This will serve as the boundary of the restrained and
operation region of the differential relay.
 If the difference measured by the relay exceeds this slope
will cause the relay to operate and trip.

Engineering Simply the Best !!!