Licenced to: LPG Serial number: [dongle]
File: Z:\TO Share\AA\Masry Group\Project (3)\CALC\INPUT\Rev.00\Elec. Room.prj - Results 13/02/2020
Error messages:
No errors detected!
VdS SCHADENVERHـTUNG CO2-Calcualtionprogramm Version 8.5 Page 2
Licenced to: LPG Serial number: [dongle]
File: Z:\TO Share\AA\Masry Group\Project (3)\CALC\INPUT\Rev.00\Elec. Room.prj - Results 13/02/2020
Input data:
Section- Start- End node Length Diff. in level Pipe type Diameter Fitting Component Nb. of cylinders
No: node Nozzle [m] [m] [mm] ** * Code Coefficient CO2 quantity
Nozzle data:
List of nozzles:
Type Number of C1 C2 C3 C4 C5 C6
orifices
1 GOD 1 0.08343 0.24800 0.00000 0.25676 0.00000 0.00000
VdS SCHADENVERHـTUNG CO2-Calcualtionprogramm Version 8.5 Page 3
Licenced to: LPG Serial number: [dongle]
File: Z:\TO Share\AA\Masry Group\Project (3)\CALC\INPUT\Rev.00\Elec. Room.prj - Results 13/02/2020
Calculation Total Ventilation Volume Opening Calcul. Max. Over Design Design Design
zone volume volume build. parts areas volume Pressure temp. concentration quantity
[m3] [m3] [m3] [m2] [m3] [°C] [% Vol] [kg]
1 Ambient 26.8 0.0 0.0 0.0 26.8 3.0 mbar 21.0 50.00 42.86
Further information:
Design with included air discharge time
Design with predeterminated orifice diameters
VdS SCHADENVERHـTUNG CO2-Calcualtionprogramm Version 8.5 Page 4
Licenced to: LPG Serial number: [dongle]
File: Z:\TO Share\AA\Masry Group\Project (3)\CALC\INPUT\Rev.00\Elec. Room.prj - Results 13/02/2020
Calculation results:
Discharge time:
Full discharge
Discharge time of air: 0.3 s
Discharge time of CO2-vapor: 0.0 s
Vaporized CO2 during the start phase: 0.0 kg
Total gas discharge time: 0.3 s
Discharge time: 51.9 s
Total discharge time: 52.2 s
System information:
Working pressure in the container: 51.3 bar abs
Working temperature in the container: 15.4 °C
Volume of the pipe system: 1.3 l
Mean CO2 quantity in the pipe system: 1.0 kg
CO2 filling ratio of the pipe system: 0.021 kg/kg CO2 Vorrat
VdS SCHADENVERHـTUNG CO2-Calcualtionprogramm Version 8.5 Page 5
Licenced to: LPG Serial number: [dongle]
File: Z:\TO Share\AA\Masry Group\Project (3)\CALC\INPUT\Rev.00\Elec. Room.prj - Results 13/02/2020
Pipe system:
Section- Start- End node Pressure Mass flow Pipe dimension
No: node Nozzle [bar abs] [kg/s] Di [mm] DN
Nozzle data:
Calculation Nozzle Nozzle Number of Pipe connection Orifice CO2 output [kg] in
zone no.: Type orifices Di [mm] DN [mm] relation to design quantity
List of components: