Contents
pg
3 1. General Description
4 2. Technical Description
7 3. Technical Specifications
9 4. Capacity tables
11 6. Operation Range
11 7. Sound Data
13 9. Outlook Drawings
20 14. Installation
2
1. General
Contents
Descrip on
MKAH
This series is ideal in combination with residences, offices, hotels, hospitals, shopping malls, shops,
restaurants, etc., or for supplying water for industrial applications.
Air heat exchanger: Cross fin coil. Internally grooved copper tubes and louvered aluminium fins.
- Phase sequence - phase failure - reverse phase and voltage monitoring device.
Klimallco sa
Air to Water Chillers
3
2. Technical Descrip on
The MKAC - MKAH series air-cooled water heat pumps consists of 8 models covering capacities from 39,7 up to
168,2 kW in cooling and 45,6 up to 190,9kW in heating. It is the end result of a thorough study, and accurate design
General
by experienced Klimallco research and development teams, to develop a mid size chiller/heat pump series with
compact shape, high performance, and reliability of the highest quality standards. This series meets the highest
levels of aesthetic and technical requirements using the latest technological innovations including
environmentally friendly R410a refrigerant that is Chlorine-free and has zero ozone depletion potential. MKAC -
MKAH units are therefore ideal for installation in urban environments due to their elegant design, selected materials
Klimallco sa
Air to Water Chillers
4
Technical Descrip on
drain valve, probes for water temperature sensors, differential Compressor running time records.
pressure switch and the whole heat exchanger is wrapped in Water pump running time records.
a heavy insulation material appropriate for external Over 150 programmable parameters.
installation.
Fan motor overload protection
All unit fans are of the axial type, single phase, 6 poles, compressor/pump thermal overload.
internally protected against potential overheating, silent and Auto diagnostic function and digital display of
suitable for outdoor installation. Due to the sophisticated approximately 30 possible error codes including thermistor
aerodynamic design of the blades and inlet cones, as well as faults.
the perfect static and dynamic balancing, their operation is
Digital displays of inlet / outlet water as well as coil
completely vibration-free. The fan motor assembly has a
temperatures of each circuit.
protective grid against accidental contact with moving parts,
Remote Cool/ Heat selector switch.
which is designed according to ISO regulations. Fan motors
Remote on/ off switch.
are of the external rotor type, aerodynamically shaped so as
not to interfere with the airflow, and have permanently Remote alarm indication capability.
lubricated bearings that do not require servicing. Continuous Phase sequence - phase failure - reverse phase and
linear fan speed regulation control is achieved according to voltage monitoring.
coil temperature including fan silent mode operation. This Many optional control capabilities (listed in optional
standard feature for Klimallco MKAC - MKAH units saves accessories).
energy and reduces sound levels dramatically, optimizing
capacity.
Refrigerant circuit
Microprocessor controller Each Unit is equipped with two refrigerant circuits. Each circuit
Klimallco sa
Air to Water Chillers
5
Technical Descrip on
Optional accessories
Remote keyboard.
signal.
R407 c refrigerant.
protection.
down to 5oC.
A-meter, V-meter.
Free cooling water coil with pump and 3-way valve (FC
series)
Klimallco sa
Air to Water Chillers
6
3. Technical Specifica ons
Klimallco sa
Air to Water Chillers
7
Technical Specifica ons
Notes
Cooling mode: water temperature 12/7oC,ambient 35oCDB.
Heating mode: water temperature 40o/45oC, ambient 7oCDB
Klimallco sa
Air to Water Chillers
8
4. Capacity Tables
Notes
Bold values show nominal cooling/heating capacities.
Absorbed power and current refers to the compressor. Above figures are valid for water Δt = 5 oC.
Klimallco sa
Air to Water Chillers
9
5. Water Pressure Drop
PD 1 2 3 4 5 6
100
90
80
70
60
50
40
kpa
30
20
15
10 WF
4 5 10 15 20 30 40 50 60 70 80 100x103
I/h
Notes
PD : Pressure Drop 3. MKAC - MKAH 023
WF : Water Flow Rate 4. MKAC - MKAH 029
1. MKAC - MKAH 010 - 013 5. MKAC - MKAH 037
2. MKAC - MKAH 015 - 019 6. MKAC - MKAH 046
Klimallco sa
Air to Water Chillers
10
6. Opera on Range
47
Cooling Heating
44 20
4 0
0
-5 -5
- The accompanying operating limits are for general For operation with leaving water temperature below 6oC it is
guidance only. It may be possible for certain units to required to confirm with Klimallco at the time of order and
operate outside the confines of the graph. Please contact the addition of glycol into the system.
Klimallco if further clarification is required.
7. Sound Data
Klimallco sa
Air to Water Chillers
11
8. Free Cooling Capacity Tables
Klimallco sa
Air to Water Chillers
12
9. Outlook Drawings
Klimallco sa
Air to Water Chillers
13
10. Hydraulic Circuit
40
MKAC - MKAH037/046FC
38
36
34
MKAC - MKAH010/019FC
32
Head m
30
28
26
MKAC - MKAH023/029FC
24
22
20
0 4 8 12 16 20 24 28 32
Water flow m3/h
Klimallco sa
Air to Water Chillers
14
11. Hydronic Circuit Diagram
Notes
1. Tank with heat exchanger.
2. Air vent.
3. Pump.
4. Expansion tank.
5. Safety valve.
6. Auto filling.
7. Filter.
8. Inlet water.
9. Outlet water.
10. Filling water.
11. Drain valve.
12. Differential pressure switch.
40
35
MKAC - MKAH029HD
30
MKAC - MKAH013/023HD
25
Head m
15
10
5
0 5 10 15 20 25 30 35 40
Water flow m3/h
Klimallco sa
Air to Water Chillers
15
12. Refrigerant Circuit Diagramms
6
8. Expansion device (Ther-
mal expansion valve)
5
3 4 3
1 1
7
8
2 10
7 9 6 12
10 12 11 11
6 9
10
7
10
7
3 3
5 5
Notes
1. Compressor
2. Shell and tube heat exchanger
3. Air heat exchanger 1 1
4 4
4. Suction accumulator
5. 4-way reversing valve
6. Filter dryer
7. Expansion device (Thermal
expansion valve)
8. Liquid receiver
9. Solenoid valve
10. Check valve
11. Sight glass
12. Shut off valve
Klimallco sa
Air to Water Chillers
16
13. Wiring Diagramms
2 4 6 2 4 6 2 4 6
N T1 T2 T3 T1 T2 T3 T1 T2 T3
CC1 L1 L2 L3 NO NO NC CC2 L1 L2 L3 NO NO NC CP L1 L2 L3 NO NC
A1 1 3 5 03 53 61 A1 1 3 5 03 53 61 A1 1 3 5 13 21
A2 2 4 6 04 54 62 A2 2 4 6 04 54 62 A2 2 4 6 14 22
T1 T2 T3 T1 T2 T3 T1 T2 T3
L1 L2 L3 NC NO
1 3 5 95 97
TH
2 4 6 96 98
T1 T2 T3
MCA MCB MP
3~ 3~ 3~
PE
'PE'
L1
L2
L3
N
PE
3N~50Hz 400V/230V
FF F4
2 2
21 21
'1'
CC1
CC2
22 22
'R1' 'R2'
L
FCS
PULSE L load
RC1
RC2
0,75
N L1 L2 L3
VC U<
3Ph
~ 230V
0.75 0.75 T
L N L N
~ 24V
60VA
MF1 MF2 F5
18
1~ 1~ 0.75
0.75 0.75
VC
0.75
15
Klimallco sa
Air to Water Chillers
17
Wiring Diagramms
P1 P1 P2 P2 Off
F2
14 14
TF2
SC1
SC2
11 11
2 4 2 4 2 4
T
1 1 1 1 1 1
S1
LP1
HP1
LP2
HP2
FSW
C1 C2 F1
TC1
TC2
TF1
FCS
PULSE
T T T
H L H L ON
S1 s2 S S T SD655 SE655
S1 S2 S3 S4 TH 95
96
123 12 3
D03
D02
D01
D06
D04
D03
D02
D01
D06
REMOTE
LCD TERMINAL 5 6 7 8 9 10 11 12 5 6 7 8 9 10 11 12
CC2
CP
AL AL
Klimallco sa
Air to Water Chillers
18
Wiring Diagramms
13.4 Symbols
Gnd
SW
ON
S1
P1
P1
AL
AL
F1
S2
S4
S3
P2
P2
Pe
LF
F2
N
H
T
F
L
FSW
NTC
NTC
NTC
NTC
S1
COND. FAN 2 THERMAL PROTECTION
COND. FAN1 THERMAL PROTECTION
Klimallco sa
Air to Water Chillers
19
14. Installa on
2. The space around the unit is adequate for servicing and the 7. Make sure that the unit can be fixed directly on concrete.
minimum space air inlet and air outlet is available. If several
8. In order to avoid the transmission of vibration from the
units are being installed side by side in parallel, the
operating unit to its carrying structure, the use of
minimum service space between them must be taken into
antivibration material to install under the supports of the
account.
unit is recommended. It is suggested to install a rubber pad
3. There is no danger of fire due to leakage of inflammable between the points of support and the base of the unit, or
gas. spring antivibration mounts under each point of support of
the unit.
4. Ensure that water cannot cause any damage to the
location in case it drips out the unit.
5. Make sure that the air inlet and outlet of the unit are not
4000
2000 2000
1000
Klimallco sa
Air to Water Chillers
20
Installa on
550 550
1100 1260
826 1200
826 1400
Klimallco sa
Air to Water Chillers
21
Installa on
13
3 14
4
1 2 6 5
5 5
3 16
2 9
1
10 5
4
11
5
12
8
Klimallco sa
Air to Water Chillers
22
Installa on
15
13
3 14
4
1 2 6
5 7
5 6,1 5
5
5 55 6,1
5 6,1 5
3 12 11
16 4 5
2 9
1 10 5 5
5
11
5
5
8
8
Notes
1. Flexible
2. Thermometer
3. Manometer
4. Air vent
5. Shut off valve
6. Pump (primary circuit)
6.1 Pump (secondary circuit)
7. Water filter
8. Drainage
9. Flow switch (optional)
10. Balancing valve
11. Buffer tank
12. Electric resistance
13. Automatic make up water valve
14. Expansion membrane
15. Check valve
16 Safety valve
Klimallco sa
Air to Water Chillers
23
Installa on
Items to be controlled
PH at 20οC 6.8 - 8.0 6.8 - 8.0 7.0 - 8.0 7.0 - 8.0 corrosion + scale
Electrical Conduct (mS/m) at 25οC bellow 30 bellow 30 bellow 30 bellow 30 corrosion + scale
Chloride Ion (mg Cl/l) bellow 50 bellow 200 bellow 30 bellow 30 corrosion
Sulfate Ion (mg So 2/4/l) bellow 50 bellow 50 bellow 30 bellow 30 corrosion
M-alkalinity (ph 4.8) (mgSO3/l) bellow 50 bellow 50 bellow 50 bellow 50 corrosion
Total Hardness (CaCo3/l) bellow 70 bellow 70 bellow 70 bellow 70 corrosion
Total Hardness (mg CaCO3/l) bellow 50 bellow 50 bellow 50 bellow 50 corrosion
Silica Ion (mg Sio2/l) bellow 30 bellow 30 bellow 30 bellow 30 corrosion
Items to be refered to :
Iron (mg Fe/l) bellow 1.0 bellow 0.3 bellow 1.0 bellow 0.3 corrosion + scale
Copper (mg Cu/l) bellow 1.0 bellow 0.1 bellow 1.0 bellow 0.1 corrosion
Sulfide Ion (mg S2/l) Not detectable Not detectable Not detectable Not detectable corrosion
Amonium Ion (mg NH4/l) bellow 0.3 bellow 0.1 bellow 0.1 bellow 0.1 corrosion
Remaining Chloride (mg Cl/l) bellow 0.25 bellow 0.3 bellow 0.1 bellow 0.3 corrosion
Free Carbide(mg SO2/l) bellow 0.4 bellow 4.0 bellow 0.4 bellow 4.0 corrosion
Stability Index - - - - corrosion + scale
NOTES
The above tables are purely indicative and non-binding
Klimallco sa
Air to Water Chillers
24
Installa on
Klimallco sa
Air to Water Chillers
25
Installa on
Cooling led.
ON if the controller is in cooling mode.
Standby led.
If the led is permanantly on, Local STAND BY mode.
(from keyboard)
If the led is blinking, remote STAND BY mode.
It performs exactly the same functions as those described in
Defrost led (heat pump version). the display section.
If the led is permanantly on, the defrost mode is active.
If the led is blinking, the manual defrost mode is activated.
Economy mode
Connection with the controller is illustrated below:
Clock led
Shows current time
123
Black
Blue
Red
Klimallco sa
Air to Water Chillers
26
Air Treatment Experts
MKAC
MKAH